Installation Instructions

5

 

 

4

 

 

3

 

6

2

 

7

1

 

POS

NEG

 

(+)

(-)

 

 

8

 

9

 

Figure 2

XADC Internal Components

 

Item

Description

 

1

AC wiring compartment hole

 

2

Black AC line cable

 

3

White AC neutral cable

 

4

Green AC ground cable

 

5

Grommet (supplied)

 

6

Strain relief (not supplied)

 

7

DC wiring compartment hole ½ in. - 3/8 in. trade size (with ¾ in. knockout)

8

DC fuses

 

9

DC positive (+) and negative (-) connection lugs

AC/DC Distribution Panel

The XADC may be pre-installed with an AC/DC Distribution Panel. The panel is available in two configurations which provides the approved wiring boxes for AC and DC connections:

30A (Part Number: 810-0030-00 XADC P30) – eight output breakers

50A (Part Number: 810-0050-00 XADC P50) – 10 output breakers

In each configuration there are also 11 unassigned DC fuses and four reserved fuses for the battery connections.

Figure 3 and Figure 5 show the main components of the XADC with AC/DC Distribution Panel.

Important: The XADC P30 and XADC P50 panels are not intended for use with rigid conduit systems.