Installation Instructions

Connecting the Panel to the XADC AC Side

When following the procedure, see Table 2 on page 24 for wire lengths and Table 1 on page 24 for torque values. See Figure 4 on page 8 for panel electrical connection diagrams. Refer to local electrical codes for wire gauge sizes.

To connect the panel to the XADC AC side:

1.Remove the AC wiring compartment panel on the XADC (see Figure 8).

2.Route the all AC cables from the XADC, through the AC wiring compartment hole in the top of the XADC. Ensure factory-installed grommet is still present.

3.Connect the AC ground (green) cable from the XADC to the front AC bus on the panel, marked “Equipment Grounding Terminal”.

4.Connect the neutral (white) cable from the XADC to the rear AC bus on the panel, marked “AC Neutral Terminal”.

5.Connect the AC line black cable from the XADC to the any breaker on the panel that is not reserved for the AC main line. Tighten as per the manufacturer’s recommended torque rating (usually located on the side of breakers).

XADC AC ground connection to Equipment Grounding Terminal

XADC AC neutral connection to AC Neutral Terminal

AC wiring compartment hole

AC line connection to breaker 1 (30A panel) or breaker 4+5 (50A panel)

XADC AC cables to any breaker except reserved AC line breaker

Figure 16 Connecting Panel to XADC AC Side