036-21410-001-A-0502

TABLE 4: COOLING CAPACITIES FOR DJ180 AT 85°F

RETURN AIR

 

 

OUTDOOR AMBIENT TEMPERATURE (°F): 85

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WB

GROSS

INPUT

 

 

GROSS SENSIBLE CAPACITY1 (MBH)

 

 

CFM

CAPACITY1

POWER2

 

 

(RETURN AIR DRY BULB TEMP. - (°F) )

 

 

TEMP °F

 

 

 

 

 

(MBH)

(kW)

 

 

 

 

 

 

 

 

 

 

 

86

83

 

80

77

74

 

71

68

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

210.2

12.36

121.0

108.2

 

95.3

82.5

69.7

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

4500

67

193.0

11.97

151.5

138.6

 

125.8

113.0

100.2

 

87.3

74.5

 

 

 

 

 

 

 

 

 

 

 

 

62

177.6

11.68

177.6

167.6

 

154.8

141.0

129.1

 

116.3

103.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

182.7

11.62

182.1

169.2

 

156.4

143.6

130.7

 

117.9

105.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

216.7

12.47

133.6

118.4

 

103.3

88.1

72.9

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

5250

67

198.9

12.08

166.6

151.4

 

136.3

121.1

105.9

 

90.8

75.6

 

 

 

 

 

 

 

 

 

 

 

 

62

183.1

11.78

183.1

178.1

 

167.6

152.5

137.3

 

122.1

107.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

188.4

11.72

188.0

181.6

 

169.4

154.2

139.0

 

123.9

108.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

223.2

12.58

146.2

128.7

 

111.2

93.7

76.2

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

6000

67

204.9

12.19

181.7

164.2

 

146.7

129.2

111.7

 

94.2

76.7

 

 

 

 

 

 

 

 

 

 

 

 

62

188.6

11.89

188.6

188.6

 

180.5

163.0

145.5

 

128.0

110.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

194.0

11.83

194.0

194.0

 

182.4

164.9

147.4

 

129.9

112.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

229.7

12.61

157.8

137.9

 

118.0

98.1

78.1

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

6750

67

210.8

12.21

195.6

175.6

 

155.7

135.8

115.9

 

95.9

76.0

 

 

 

 

 

 

 

 

 

 

 

 

62

194.0

11.91

194.0

194.0

 

190.0

170.1

150.1

 

130.2

110.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

199.6

11.86

199.6

199.6

 

193.6

173.6

153.7

 

133.8

113.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

236.1

12.64

169.5

147.2

 

124.8

102.5

80.1

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

7500

67

216.7

12.24

209.4

187.1

 

164.7

142.4

120.0

 

97.7

75.3

 

 

 

 

 

 

 

 

 

 

 

 

62

199.5

11.94

199.5

199.5

 

199.5

177.1

154.8

 

132.4

100.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

205.2

11.88

205.2

205.2

 

204.8

182.4

160.1

 

137.7

115.3

 

 

 

 

 

 

 

 

 

 

 

 

 

1.The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat, MBH = 3.415 x kW. Refer to the appro- priate blower performance table for the kW of the supply air blower motor.

2.These ratings include condenser fan motor and compressor motor power but not the supply air blower motor power.

Unitary Products Group

13

Page 13
Image 13
York 300 warranty Cooling Capacities for DJ180 AT 85F