036-21410-001-A-0502

TABLE 7: COOLING CAPACITIES FOR DJ180 AT 115°F

 

 

 

 

 

 

 

 

 

RETURN AIR

 

 

OUTDOOR AMBIENT TEMPERATURE (°F): 115

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WB

GROSS

INPUT

 

 

 

GROSS SENSIBLE CAPACITY1 (MBH)

 

 

CFM

CAPACITY1

POWER2

 

 

(RETURN AIR DRY BULB TEMP. - (°F) )

 

 

TEMP °F

 

 

 

 

 

(MBH)

(kW)

 

 

 

 

 

 

 

 

 

 

 

 

 

86

 

83

 

80

77

 

74

 

71

68

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

178.8

17.24

107.6

 

94.7

 

81.9

69.1

 

56.2

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4500

67

163.6

16.78

137.2

 

124.4

 

111.6

98.8

 

85.9

 

73.1

60.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

62

154.2

16.31

154.2

 

144.3

 

131.5

118.7

 

105.9

 

93.0

80.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

152.0

16.24

152.0

 

148.0

 

135.1

122.3

 

109.5

 

96.6

83.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

183.3

17.38

119.6

 

104.5

 

89.3

74.1

 

59.0

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5250

67

167.7

16.91

152.0

 

136.8

 

121.7

106.5

 

91.3

 

76.2

61.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

62

158.1

16.44

158.1

 

153.1

 

143.4

128.2

 

113.1

 

97.9

82.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

155.8

16.37

155.8

 

153.8

 

147.4

132.2

 

117.0

 

101.9

86.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

187.8

17.52

131.7

 

114.2

 

96.7

79.2

 

61.7

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6000

67

171.8

17.05

166.8

 

149.3

 

131.8

114.3

 

96.8

 

79.3

61.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

62

161.9

16.57

161.9

 

161.9

 

155.3

137.8

 

120.3

 

102.8

85.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

159.6

16.50

159.6

 

159.6

 

159.6

142.1

 

124.6

 

107.1

89.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

193.0

17.53

142.5

 

122.6

 

102.6

82.7

 

62.8

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6750

67

176.5

17.06

174.0

 

159.8

 

139.8

119.9

 

100.0

 

80.1

60.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

62

166.4

16.59

166.4

 

166.4

 

163.1

143.2

 

123.2

 

103.3

83.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

164.0

16.52

164.0

 

164.0

 

164.0

144.1

 

124.1

 

104.2

84.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

198.1

17.55

153.3

 

130.9

 

108.6

86.2

 

63.8

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7500

67

181.3

17.08

181.3

 

170.3

 

147.9

125.6

 

103.2

 

80.8

58.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

62

170.9

16.60

170.9

 

170.9

 

170.9

148.5

 

126.2

 

103.8

81.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

168.4

16.54

168.4

 

168.4

 

168.4

146.0

 

123.7

 

101.3

79.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat, MBH = 3.415 x kW. Refer to the appro- priate blower performance table for the kW of the supply air blower motor.

2.These ratings include condenser fan motor and compressor motor power but not the supply air blower motor power.

16

Unitary Products Group

Page 16
Image 16
York 300 warranty Cooling Capacities for DJ180 AT 115F