036-21410-001-A-0502

TABLE 21: COOLING CAPACITIES FOR DJ300 AT 105°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RETURN AIR

 

 

OUTDOOR AMBIENT TEMPERATURE (°F): 105

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WB

GROSS

INPUT

 

 

GROSS SENSIBLE CAPACITY1 (MBH)

 

 

CFM

CAPACITY1

POWER2

 

(RETURN AIR DRY BULB TEMP. - (°F) )

 

 

TEMP °F

 

 

 

 

(MBH)

(kW)

 

 

 

 

 

 

 

 

 

 

 

 

86

83

 

80

77

 

74

 

71

68

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

301.8

27.73

184.5

163.2

 

141.8

120.4

 

99.0

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7500

67

289.0

27.27

238.8

217.4

 

196.0

174.6

 

153.2

 

131.9

110.5

 

 

 

 

 

 

 

 

 

 

 

 

 

62

283.6

26.57

280.8

259.7

 

238.3

216.9

 

195.5

 

174.1

152.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

271.5

26.43

271.5

260.3

 

238.9

217.6

 

196.2

 

174.8

153.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

306.8

27.83

201.3

176.1

 

150.8

125.5

 

100.2

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8750

67

293.9

27.37

259.0

233.7

 

208.5

183.2

 

157.9

 

132.7

107.4

 

 

 

 

 

 

 

 

 

 

 

 

 

62

288.3

26.67

286.9

276.4

 

253.4

228.1

 

202.8

 

177.6

152.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

276.1

26.53

276.1

270.5

 

254.1

228.8

 

203.5

 

178.3

153.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

311.8

27.93

218.1

188.9

 

159.8

130.6

 

101.5

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10000

67

298.7

27.47

279.3

250.1

 

220.9

191.8

 

162.6

 

133.5

104.3

 

 

 

 

 

 

 

 

 

 

 

 

 

62

293.1

26.77

293.1

293.1

 

268.5

239.3

 

210.2

 

181.0

151.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

280.6

26.63

280.6

280.6

 

269.2

240.0

 

210.9

 

181.7

152.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

318.7

28.19

233.1

199.9

 

166.7

133.5

 

100.3

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11250

67

305.4

27.73

294.9

263.7

 

230.5

197.3

 

164.1

 

130.9

97.7

 

 

 

 

 

 

 

 

 

 

 

 

 

62

299.6

27.02

299.6

299.6

 

280.1

246.9

 

213.7

 

180.5

147.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

286.8

26.88

286.8

286.8

 

280.9

247.7

 

214.5

 

181.2

148.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

325.6

28.46

248.2

210.9

 

173.6

136.4

 

99.1

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12500

67

312.0

27.99

310.5

277.4

 

240.1

202.8

 

165.6

 

128.3

91.1

 

 

 

 

 

 

 

 

 

 

 

 

 

62

306.0

27.27

306.0

306.0

 

291.8

254.5

 

217.3

 

180.0

142.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

293.0

27.13

293.0

293.0

 

292.5

255.3

 

218.0

 

180.8

143.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat, MBH = 3.415 x kW. Refer to the appro- priate blower performance table for the kW of the supply air blower motor.

2.These ratings include condenser fan motor and compressor motor power but not the supply air blower motor power.

30

Unitary Products Group

Page 30
Image 30
York warranty Cooling Capacities for DJ300 AT 105F