UNIT OPERATING CHARACTERISTICS

Unit shall be capable of starting and running at 125° F outdoor temperature, exceeding maximum load criteria of ARI Standard 210/240. The compressor, with standard controls, shall be capable of operation down to 25° F outdoor temperature. Accessory low ambient kit shall be available for operation to 0° F. Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms up (Gas heat only).

ELECTRICAL REQUIREMENTS

All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring.

STANDARD LIMITED WARRANTIES

Compressor 5 Years

Heat Exchanger 10 Years

Electric Heat Element 5 Years

Other Parts 1 Year

OPTIONAL OUTDOOR AIR (Shall be made available by either/or):

ELECTRONIC ENTHALPY AUTOMATIC ECONO- MIZER - Outdoor and return air dampers that are inter- locked and positioned by a fully-modulating, spring- return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potenti- ometer shall be provided to adjust the outdoor and return air damper assembly to take in CFM of outdoor air to meet the minimum ventilation requirement of the condi- tioned space during normal operation. During econo- mizer operation, a mixed-air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55°F. Changeover from compressor to economizer oper- ation shall be provided by an integral electronic enthalpy control that feeds input into the basic module. The out- door intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/fil- ters shall be provided. Simultaneous economizer/com- pressor operation is also possible. Dampers shall fully close on power loss.

MOTORIZED OUTDOOR AIR DAMPERS - Outdoor and return air dampers that are interlocked and positioned by a 2-position,spring-return damper actuator. The maxi- mum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust

036-21410-001-A-0502

the outdoor and return air damper assembly to take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space during normal operation. Whenever the indoor fan motor is energized, the dampers open up to one of two pre-selected posi- tions - regardless of the outdoor air enthalpy. Dampers return to the fully closed position when the indoor fan motor is de-energized. Dampers shall fully close on power loss.

OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE

ROOF CURB - 14" high, full perimeter curb with wood nailer (shipped knocked-down).

100% BAROMETRIC RELIEF DAMPER - Contains a rain hood, air inlet screen, exhaust damper and mount- ing hardware. Used to relieve internal air pressure through the unit.

PROPANE CONVERSION KIT - Contains new orifices and gas valve parts to convert from natural to L.P. gas. One per unit required.

HIGH ALTITUDE - NATURAL GAS - Contains orifices required for applications between 2000 and 6000 feet altitude.

HIGH ALTITUDE - PROPANE GAS - Contains orifices required for applications between 2000 and 6000 feet altitude. Must be used with propane conversion kit.

BURGLAR BARS - Designed to work with above roof curbs, depending on unit model. Fits duct openings of curb supply and return air openings.

SIDE DUCT FLANGE - Supply and return air duct flanges for side duct applications. Do not use on units with power exhaust.

HIGH SPEED DRIVE - Includes blower pulley and belt for higher CFM and/or static pressure requirements.

WOOD SKID - Allows unit to be handled with 90" forks.

ECONOMIZER/MOTORIZED DAMPER RAIN HOOD (DJN/E/C300 only) - Contains all hood panels and the hardware for assembling.

ANTI-RECYCLE TIMER - Assures 5-minute off time between compressor cycles.

LOW AMBIENT KIT - Provides unit cooling operation down to 0°F.

COIL GUARD KIT - Guard for cooling coil.

OTHER FACTORY INSTALLED OPTIONS

POWER EXHAUST OPTION - To work in conjunction with economizers.

STAINLESS STEEL HEAT EXCHANGER

52

Unitary Products Group

Page 52
Image 52
York 300 warranty Other Factory Installed Options