York 300 warranty Cooling Capacities for DJ240 AT 105F

Models: 300

1 56
Download 56 pages 19.65 Kb
Page 25
Image 25

036-21410-001-A-0502

TABLE 16: COOLING CAPACITIES FOR DJ240 AT 105°F

RETURN AIR

 

 

OUTDOOR AMBIENT TEMPERATURE (°F): 105

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WB

GROSS

INPUT

 

 

GROSS SENSIBLE CAPACITY1 (MBH)

 

 

CFM

CAPACITY1

POWER2

 

(RETURN AIR DRY BULB TEMP. - (°F) )

 

 

TEMP °F

 

 

 

 

(MBH)

(kW)

 

 

 

 

 

 

 

 

 

 

 

 

86

83

 

80

77

 

74

 

71

68

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

244.1

20.09

146.5

129.4

 

112.3

95.2

 

78.1

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6000

67

225.3

19.63

186.7

169.6

 

152.5

135.4

 

118.3

 

101.2

84.1

 

 

 

 

 

 

 

 

 

 

 

 

 

62

202.7

19.37

202.7

194.9

 

177.7

160.6

 

143.5

 

126.4

109.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

211.7

19.63

211.7

205.7

 

188.6

171.5

 

154.4

 

137.3

120.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

250.6

20.15

162.5

142.2

 

122.0

101.8

 

81.6

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7000

67

231.3

19.69

206.2

185.9

 

165.7

145.5

 

125.3

 

105.1

84.9

 

 

 

 

 

 

 

 

 

 

 

 

 

62

208.1

19.43

208.1

204.2

 

193.1

172.9

 

152.7

 

132.5

112.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

217.3

19.70

217.3

214.3

 

204.9

184.7

 

164.5

 

144.3

124.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

257.0

20.22

178.4

155.1

 

131.7

108.4

 

85.1

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8000

67

237.3

19.76

225.6

202.3

 

178.9

155.6

 

132.3

 

109.0

85.6

 

 

 

 

 

 

 

 

 

 

 

 

 

62

213.5

19.50

213.5

213.5

 

208.5

185.2

 

161.9

 

138.5

115.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

222.9

19.77

222.9

222.9

 

221.3

197.9

 

174.6

 

151.3

128.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

264.1

20.56

191.3

165.6

 

139.9

114.3

 

88.6

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8700

67

243.8

20.09

238.0

215.7

 

190.0

164.4

 

138.7

 

113.0

87.3

 

 

 

 

 

 

 

 

 

 

 

 

 

62

219.4

19.83

219.4

219.4

 

216.9

191.2

 

165.5

 

139.8

114.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

229.0

20.10

229.0

229.0

 

228.2

202.5

 

176.9

 

151.2

125.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

271.1

20.91

204.1

176.1

 

148.1

120.1

 

92.1

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9400

67

250.3

20.43

250.3

229.2

 

201.1

173.1

 

145.1

 

117.1

89.1

 

 

 

 

 

 

 

 

 

 

 

 

 

62

225.2

20.16

225.2

225.2

 

225.2

197.2

 

169.2

 

141.1

113.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

235.2

20.43

235.2

235.2

 

235.2

207.1

 

179.1

 

151.1

123.1

1.The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat, MBH = 3.415 x kW. Refer to the appro- priate blower performance table for the kW of the supply air blower motor.

2.These ratings include condenser fan motor and compressor motor power but not the supply air blower motor power.

Unitary Products Group