036-21410-001-A-0502
32 UnitaryProducts Group
TABLE23: COOLING CAPACITIES FOR DJ300 AT 125°F
RETURNAIR OUTDOORAMBIENT TEMPERATURE (°F): 125
CFM WB
TEMP°F
GROSS
CAPACITY1
(MBH)
INPUT
POWER2
(kW)
GROSSSENSIBLE CAPACITY1(MBH)
(RETURNAIR DRY BULB TEMP.- (°F) )
86 83 80 77 74 71 68
7500
72 256.5 32.33 170.6 149.2 127.8 106.4 85.0 #N/A #N/A
67 256.1 32.35 224.5 203.1 181.8 160.4 139.0 117.6 96.2
62 248.4 31.25 248.4 230.7 209.3 187.9 166.5 145.2 123.8
57 230.3 31.16 230.3 226.9 205.5 184.1 162.7 141.3 120.0
8750
72 266.9 32.57 188.9 163.6 138.4 113.1 87.8 #N/A #N/A
67 266.3 32.60 247.2 222.0 196.7 171.4 146.2 120.9 95.6
62 258.4 31.48 258.4 249.5 226.7 201.4 176.1 150.9 125.6
57 239.7 31.39 239.7 237.9 222.6 197.3 172.1 146.8 121.5
10000
72 277.3 32.82 207.3 178.1 148.9 119.8 90.6 #N/A #N/A
67 276.5 32.84 270.0 240.8 211.7 182.5 153.3 124.2 95.0
62 268.3 31.71 268.3 268.3 244.1 214.9 185.7 156.6 127.4
57 249.0 31.63 249.0 249.0 239.7 210.6 181.4 152.3 123.1
11250
72 284.0 33.13 221.6 188.3 155.1 121.9 88.7 #N/A #N/A
67 283.2 33.15 280.7 253.7 220.5 187.3 154.1 120.8 87.6
62 274.8 32.01 274.8 274.8 254.2 221.0 187.8 154.6 121.4
57 255.0 31.92 255.0 255.0 249.7 216.5 183.3 150.1 116.9
12500
72 290.7 33.44 235.9 198.6 161.3 124.1 86.8 #N/A #N/A
67 289.8 33.46 289.8 266.6 229.3 192.0 154.8 117.5 80.3
62 281.3 32.32 281.3 281.3 264.4 227.1 189.9 152.6 115.3
57 261.0 32.22 261.0 261.0 259.7 222.4 185.2 147.9 110.7
1. Thecapacities are gross ratings. For netcapacity, deduct the supply air blower motor heat, MBH = 3.415 x kW. Refer to the appro-
priateblower performance table for the kW of the supply air blower motor.
2. Theseratings include condenser fan motor and compressor moto rpower but not the supply air blower motor power.