TABLE 20: COOLING CAPACITIES FOR DJ300 AT 95°F

RETURN AIR

 

 

OUTDOOR AMBIENT TEMPERATURE (°F): 95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WB

GROSS

INPUT

 

 

GROSS SENSIBLE CAPACITY1 (MBH)

 

 

CFM

CAPACITY1

POWER2

 

(RETURN AIR DRY BULB TEMP. - (°F) )

 

 

TEMP °F

 

 

 

 

(MBH)

(kW)

 

 

 

 

 

 

 

 

 

 

 

86

83

 

80

77

74

 

71

68

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

324.4

25.42

191.5

170.2

 

148.8

127.4

106.0

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

7500

67

305.5

24.73

245.9

224.5

 

203.1

181.7

160.4

 

139.0

117.6

 

 

 

 

 

 

 

 

 

 

 

 

62

301.1

24.23

295.5

274.2

 

252.8

231.4

210.0

 

188.6

167.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

292.2

24.07

292.2

277.1

 

255.7

234.3

212.9

 

191.5

170.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

326.8

25.46

207.5

182.3

 

157.0

131.7

106.4

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

8750

67

307.7

24.76

264.9

239.6

 

214.4

189.1

163.8

 

138.5

113.3

 

 

 

 

 

 

 

 

 

 

 

 

62

303.3

24.26

300.5

289.8

 

266.7

241.5

216.2

 

190.9

165.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

294.3

24.10

294.3

286.7

 

269.8

244.5

219.3

 

194.0

168.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

329.1

25.49

223.5

194.4

 

165.2

136.1

106.9

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

10000

67

309.9

24.79

283.9

254.7

 

225.6

196.4

167.3

 

138.1

108.9

 

 

 

 

 

 

 

 

 

 

 

 

62

305.5

24.29

305.5

305.5

 

280.7

251.6

222.4

 

193.2

164.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

296.4

24.13

296.4

296.4

 

283.9

254.8

225.6

 

196.5

167.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

336.1

25.73

238.9

205.7

 

172.5

139.3

106.1

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

11250

67

316.4

25.02

302.0

268.8

 

235.5

202.3

169.1

 

135.9

102.7

 

 

 

 

 

 

 

 

 

 

 

 

62

311.9

24.52

311.9

311.9

 

293.1

259.9

226.7

 

193.5

160.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

302.7

24.36

302.7

302.7

 

296.5

263.2

230.0

 

196.8

163.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

343.1

25.96

254.3

217.1

 

179.8

142.5

105.3

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

12500

67

323.0

25.25

320.0

282.8

 

245.5

208.2

171.0

 

133.7

96.5

 

 

 

 

 

 

 

 

 

 

 

 

62

318.4

24.74

318.4

318.4

 

305.5

268.2

231.0

 

193.7

156.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

309.0

24.58

309.0

309.0

 

309.0

271.7

234.4

 

197.2

159.9

 

 

 

 

 

 

 

 

 

 

 

 

 

1.The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat, MBH = 3.415 x kW. Refer to the appro- priate blower performance table for the kW of the supply air blower motor.