036-21410-001-A-0502

TABLE 14: COOLING CAPACITIES FOR DJ240 AT 85°F

RETURN AIR

 

 

OUTDOOR AMBIENT TEMPERATURE (°F): 85

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WB

GROSS

INPUT

 

 

GROSS SENSIBLE CAPACITY1 (MBH)

 

 

CFM

CAPACITY1

POWER2

 

(RETURN AIR DRY BULB TEMP. - (°F) )

 

 

TEMP °F

 

 

 

 

(MBH)

(kW)

 

 

 

 

 

 

 

 

 

 

 

86

83

 

80

77

74

 

71

68

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

273.1

16.90

149.8

132.7

 

115.6

98.5

81.4

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

6000

67

248.6

16.43

197.6

180.5

 

163.4

146.3

129.1

 

112.0

94.9

 

 

 

 

 

 

 

 

 

 

 

 

62

231.2

16.44

227.9

210.8

 

193.7

176.6

159.5

 

142.4

125.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

216.6

15.98

216.6

210.2

 

193.1

176.0

158.9

 

141.8

124.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

278.7

16.96

165.8

145.6

 

125.4

105.1

84.9

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

7000

67

253.8

16.49

217.5

197.3

 

177.1

156.9

136.7

 

116.5

96.2

 

 

 

 

 

 

 

 

 

 

 

 

62

236.0

16.50

234.4

225.8

 

210.0

189.8

169.6

 

149.4

129.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

221.1

16.04

221.1

217.9

 

209.3

189.1

168.9

 

148.7

128.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

284.4

17.02

181.8

158.4

 

135.1

111.8

88.4

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

8000

67

259.0

16.55

237.5

214.2

 

190.9

167.5

144.2

 

120.9

97.6

 

 

 

 

 

 

 

 

 

 

 

 

62

240.8

16.56

240.8

240.8

 

226.3

203.0

179.7

 

156.4

133.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

225.6

16.10

225.6

225.6

 

225.6

202.3

178.9

 

155.6

132.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

291.0

17.43

193.1

167.5

 

141.8

116.1

90.4

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

8700

67

265.0

16.95

251.7

226.0

 

200.3

174.7

149.0

 

123.3

97.6

 

 

 

 

 

 

 

 

 

 

 

 

62

246.4

16.96

246.4

246.4

 

237.6

211.9

186.2

 

160.5

134.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

230.8

16.49

230.8

230.8

 

230.8

205.2

179.5

 

153.8

128.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

297.7

17.84

204.5

176.5

 

148.5

120.5

92.4

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

9400

67

271.0

17.35

265.8

237.8

 

209.8

181.8

153.7

 

125.7

97.7

 

 

 

 

 

 

 

 

 

 

 

 

62

252.0

17.36

252.0

252.0

 

248.8

220.7

192.7

 

164.7

136.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

236.1

16.88

236.1

236.1

 

236.1

208.1

180.1

 

152.0

124.0

 

 

 

 

 

 

 

 

 

 

 

 

 

1.The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat, MBH = 3.415 x kW. Refer to the appro- priate blower performance table for the kW of the supply air blower motor.

2.These ratings include condenser fan motor and compressor motor power but not the supply air blower motor power.

Unitary Products Group

23