036-21410-001-A-0502

TABLE 11: COOLING CAPACITIES FOR DJ210 AT 105°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RETURN AIR

 

 

OUTDOOR AMBIENT TEMPERATURE (°F): 105

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WB

GROSS

INPUT

 

 

GROSS SENSIBLE CAPACITY1 (MBH)

 

 

CFM

CAPACITY1

POWER2

 

(RETURN AIR DRY BULB TEMP. - (°F) )

 

 

TEMP °F

 

 

 

 

(MBH)

(kW)

 

 

 

 

 

 

 

 

 

 

 

 

86

83

 

80

77

 

74

 

71

68

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

210.2

17.65

131.0

113.9

 

96.8

79.7

 

62.6

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6000

67

195.1

17.21

167.5

150.4

 

133.3

116.2

 

99.1

 

82.0

64.9

 

 

 

 

 

 

 

 

 

 

 

 

 

62

186.9

17.01

186.9

170.6

 

153.5

136.4

 

119.3

 

102.2

85.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

174.4

16.80

174.4

172.3

 

155.2

138.1

 

121.0

 

103.9

86.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

218.3

17.77

143.8

125.0

 

106.3

87.5

 

68.7

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6500

67

202.6

17.33

183.9

165.1

 

146.4

127.6

 

108.8

 

90.1

71.3

 

 

 

 

 

 

 

 

 

 

 

 

 

62

194.1

17.12

194.1

186.0

 

168.5

149.8

 

131.0

 

112.2

93.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

181.1

16.92

181.1

180.1

 

170.4

151.7

 

132.9

 

114.1

95.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

226.4

17.89

156.6

136.2

 

115.7

95.3

 

74.9

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7000

67

210.1

17.45

200.2

179.8

 

159.4

139.0

 

118.6

 

98.2

77.8

 

 

 

 

 

 

 

 

 

 

 

 

 

62

201.3

17.24

201.3

201.3

 

183.6

163.1

 

142.7

 

122.3

101.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

187.8

17.03

187.8

187.8

 

185.6

165.2

 

144.8

 

124.4

104.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

228.5

17.97

171.3

148.0

 

124.8

101.5

 

78.3

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7875

67

212.1

17.53

207.1

193.3

 

171.9

148.6

 

125.4

 

102.2

78.9

 

 

 

 

 

 

 

 

 

 

 

 

 

62

203.2

17.32

203.2

203.2

 

194.3

171.0

 

147.8

 

124.5

101.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

189.6

17.11

189.6

189.6

 

188.5

165.2

 

142.0

 

118.7

95.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

230.6

18.05

186.0

159.9

 

133.8

107.7

 

81.7

 

#N/A

#N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8750

67

214.0

17.61

214.0

206.7

 

184.4

158.3

 

132.2

 

106.1

80.0

 

 

 

 

 

 

 

 

 

 

 

 

 

62

205.0

17.40

205.0

205.0

 

205.0

178.9

 

152.8

 

126.8

100.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

191.3

17.19

191.3

191.3

 

191.3

165.2

 

139.1

 

113.0

87.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat, MBH = 3.415 x kW. Refer to the appro- priate blower performance table for the kW of the supply air blower motor.

2.These ratings include condenser fan motor and compressor motor power but not the supply air blower motor power.

20