York GF9S*DH, GM9S*DH UIM-B-0607, Specific Safety Rules And Precautions, Safety Requirements

Models: GF9S*DH GY9S*DH GM9S*DH

1 40
Download 40 pages 62.69 Kb
Page 2
Image 2
SPECIFIC SAFETY RULES AND PRECAUTIONS

268890-UIM-B-0607

SPECIFIC SAFETY RULES AND PRECAUTIONS

1.Only Natural gas or Propane (LP) gas are approved for use with this furnace. Refer to the furnace rating plate or Section IV of these instructions.

2.Install this furnace only in a location and position as specified in SECTION I of these instructions.

3.A gas-fired furnace for installation in a residential garage must be installed as specified in SECTION I of these instructions.

4.Provide adequate combustion and ventilation air to the furnace space as specified in SECTION VI of these instructions.

5.Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in SEC- TION VII of these instructions.

FIRE OR EXPLOSION HAZARD

Failure to follow the safety warnings exactly could result in serious injury, death or property damage.

Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for detection of leaks to check all connections. A fire or explosion may result causing prop- erty damage, personal injury or loss of life.

6.Tests for gas leaks as specified in SECTION X of these instruc- tions.

7.Always install the furnace to operate within the furnace’s intended temperature rise range. Only connect the furnace to a duct system which has an external static pressure within the allowable range, as specified on the furnace rating plate.

8.When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the fur- nace casing and terminating outside the space containing the fur- nace.

9.It is permitted to use the furnace for heating of buildings or struc- tures under construction. Installation must comply with all manu- facturer’s installation instructions including:

Proper vent installation;

Furnace operating under thermostatic control;

Return air duct sealed to the furnace;

Air filters in place;

Set furnace input rate and temperature rise per rating plate marking;

Means for providing outdoor air required for combustion;

Return air temperature maintained between 55ºF (13ºC) and 80ºF (27ºC);

The air filter must be replaced upon substantial completion of the construction process;

Clean furnace, duct work and components upon substantial completion of the construction process, and verify furnace- operating conditions including ignition, input rate, temperature rise and venting, according to the manufacturer’s instructions.

10.When installed in a Non-HUD-Approved Modular Home or building constructed on-site, combustion air shall not be supplied from occupied spaces.

11.The size of the unit should be based on an acceptable heat loss calculation for the structure. ACCA, Manual J or other approved methods may be used.

SAFETY REQUIREMENTS

This furnace should be installed in accordance with all national and local building/safety codes and requirements, local plumbing or wastewater codes, and other applicable codes. In the absence of local codes, install in accordance with the National Fuel Gas Code ANSI Z223.1/NFPA 54, National Fuel Gas Code, and/or CAN/CGA B149.1 Natural Gas and Propane Installation Code (latest editions). Furnaces have been certified to the latest edition of standard ANSI Z21-47 • CSA 2.3.

Refer to the unit rating plate for the furnace model number, and then see the dimensions page of this instruction for return air ple- num dimensions in Figure 3. The plenum must be installed according to the instructions.

Provide clearances from combustible materials as listed under Clearances to Combustibles in Table 1.

Provide clearances for servicing ensuring that service access is allowed for both the burners and blower.

These models ARE NOT CSA listed or approved for installation into a HUD Approved Modular Home or a Manufactured (Mobile) Home.

This furnace is not approved for installation in trailers or recre- ational vehicles.

Failure to carefully read and follow all instructions in this manual can result in furnace malfunction, death, personal injury and/or property damage.

Furnaces for installation on combustible flooring shall not be installed directly on carpeting, tile or other combustible material other than wood flooring.

Check the rating plate and power supply to be sure that the elec- trical characteristics match. All models use nominal 115 VAC, 1 Phase, 60-Hertz power supply. DO NOT CONNECT THIS APPLI-

ANCE TO A 50 HZ POWER SUPPLY OR A VOLTAGE ABOVE 130 VOLTS.

Furnace shall be installed so the electrical components are pro- tected from water.

Installing and servicing heating equipment can be hazardous due to the electrical components and the gas fired components. Only trained and qualified personnel should install, repair, or service gas heating equipment. Untrained service personnel can perform basic maintenance functions such as cleaning and replacing the air filters. When working on heating equipment, observe precau- tions in the manuals and on the labels attached to the unit and other safety precautions that may apply.

These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances these instructions exceed certain local codes and ordinances, especially those who have not kept up with changing residential and non-HUD modular home construction practices. These instructions are required as a minimum for a safe installation.

COMBUSTION AIR QUALITY (LIST OF CONTAMINANTS)

The furnace will require OUTDOOR AIR for combustion when the fur- nace is located in any of the following environments.

Restricted Environments

Commercial buildings

Buildings with indoor pools

Furnaces installed in laundry rooms

Furnaces installed in hobby or craft rooms

Furnaces installed near chemical storage areas

Chemical exposure

The furnace will require OUTDOOR AIR for combustion when the fur- nace is located in an area where the furnace is being exposed to the fol- lowing substances and / or chemicals.

Permanent wave solutions

Chlorinated waxes and cleaners

Chlorine based swimming pool chemicals

Water softening chemicals

De-icing salts or chemicals

Carbon tetrachloride

Halogen type refrigerants

Cleaning solvents (such as perchloroethylene)

Printing inks, paint removers, varnishes, etc.

Hydrochloric acid

Cements and glues

Antistatic fabric softeners for clothes dryers

Masonry acid washing materials

When outdoor air is used for combustion, the combustion air intake pipe termination must be located external to the building and in an area where there will be no exposure to the substances listed above.

2

Unitary Products Group

Page 2
Image 2
York GF9S*DH, GM9S*DH, GY9S*DH installation manual UIM-B-0607, Specific Safety Rules And Precautions, Safety Requirements