York GM9S*DH, GY9S*DH Section Iv Gas Piping, UIM-B-0607, Gas Safety, Gas Piping Installation

Models: GF9S*DH GY9S*DH GM9S*DH

1 40
Download 40 pages 62.69 Kb
Page 9
Image 9
SECTION IV: GAS PIPING

ANGLE IRON

 

SUPPORT

BRACKET

 

BRACKET

1” MAX. BETWEEN

 

 

ROD & FURNACE

6” MIN. BETWEEN

 

 

1” MAX. BETWEEN

 

ROD & FURNACE

 

ROD & FURNACE

 

 

FIGURE 6: Typical Suspended Furnace / Crawl Space Installation

In any application where temperatures below freezing are possible,

268890-UIM-B-0607

EXTERNAL MANUAL

SHUTOFF VALVE

TO GAS

 

 

 

 

 

 

 

 

 

 

TO GAS

SUPPLY

 

 

 

 

 

 

 

 

 

 

SUPPLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GROUNDED JOINT UNION

DRIP

 

 

 

MAY BE INSTALLED

LEG

 

 

 

INSIDE OR OUTSIDE UNIT.

FIGURE 8: Downflow Gas Piping

MANUAL

SHUT-OFF

VALVE

see “BELOW FREEZING LOCATIONS”.

GAS PIPE

DRIP LEG

SECTION IV: GAS PIPING

GAS SAFETY

GAS PIPE

GAS SAFETY GAS BURNERS

GAS PIPING INSTALLATION GAS VALVE

An overpressure protection device, such as a pressure regulator, must be installed in the gas piping system upstream of the furnace and must act to limit the downstream pressure to the gas valve so it does not exceed 0.5 PSI {14" w.c. (3.48 kPa)}. Pressures exceed- ing 0.5 PSI {14” w.c. (3.48 kPa)} at the gas valve will cause damage to the gas valve, resulting in a fire or explosion or cause damage to the furnace or some of its components that will result in property damage and loss of life.

DRIP

MANUAL

LEG

SHUT-OFF VALVE

FIGURE 9: Horizontal Gas Piping

IMPORTANT: An accessible manual shutoff valve must be installed upstream of the furnace gas controls and within 6 feet (1.8 m) of the fur- nace.

The furnace must be isolated from the gas supply piping system by closing its individual external manual shutoff valve during any pressure testing of the gas supply piping system at pressures equal to or less

OUTLET

PRESSURE

PORT

INLET

WRENCH BOSS

INLET PRESSURE PORT

 

VENT PORT

 

OUTLET

OFF

 

ON

MAIN REGULATOR

ON/OFF SWITCH

ADJUSTMENT

 

(Shown in ON position)

 

than 1/2 psig (3.5 kPa).

Never apply a pipe wrench to the body of the gas valve when installing piping. A wrench must be placed on the octagonal hub located on the gas inlet side of the valve. Placing a wrench to the body of the gas valve will damage the valve causing improper oper- ation and/or the valve to leak.

FIGURE 7: Gas Valve

IMPORTANT: Plan your gas supply before determining the correct gas pipe entry. Use 90-degree service elbow(s), or short nipples and con- ventional 90-degree elbow(s) to enter through the cabinet access holes.

GAS PIPING INSTALLATION

Properly sized wrought iron, approved flexible or steel pipe must be used when making gas connections to the unit. If local codes allow the use of a flexible gas appliance connection, always use a new listed con- nector. Do not use a connector that has previously serviced another gas appliance.

Some utility companies or local codes require pipe sizes larger than the minimum sizes listed in these instructions and in the codes. The furnace rating plate and the instructions in this section specify the type of gas approved for this furnace - only use those approved gases. The instal- lation of a drip leg and ground union is required. Refer to Figure 8.

Gas piping may be connected from either side of the furnace using any of the gas pipe entry knockouts on both sides of the furnace. Refer to Figure 3 dimensions.

GAS ORIFICE CONVERSION FOR PROPANE (LP)

This furnace is constructed at the factory for natural gas-fired operation, but may be converted to operate on propane (LP) gas by using a fac- tory-supplied LP conversion kit. Follow the instructions supplied with the LP kit. Refer to Table 6 or the instructions in the propane (LP) con- version kit for the proper gas orifice size.

HIGH ALTITUDE GAS ORIFICE CONVERSION

This furnace is constructed at the factory for natural gas-fired operation at 0 – 8,000 feet (0-m – 2,438 m) above sea level.

The manifold pressure must be changed in order to manitain proper and safe operation when the furnace is installed in a location where the altitude is greater than 8,000 feet (2,438 m) above sea level. Refer to to Table 6 for proper manifold pressure settings.

HIGH ALTITUDE PRESSURE SWITCH CONVERSION

For installation where the altitude is less than 8,000 feet (2,438 m), it is not required that the pressure switch be changed. For altitudes above 8,000 feet (2,438 m), see Field Installed Accessories - High Altitude pressure Switch.

Unitary Products Group

9

Page 9
Image 9
York GM9S*DH Section Iv Gas Piping, UIM-B-0607, Gas Safety, Gas Piping Installation, Gas Orifice Conversion For Propane Lp