APPLYING FILTER PRESSURE DROP TO DETERMINE SYSTEM AIRFLOW
To determine the approximate airflow of the unit with a filter in place, fol- low the steps below:
1.Select the filter type.
2.Determine the External System Static Pressure (ESP) without the filter.
3.Select a filter pressure drop from the table based upon the number of return air openings or return air opening size and add to the ESP from Step 2 to determine the total system static.
4.If total system static matches a ESP value in the airflow table (i.e. 0.20, 0.60, etc,) the system airflow corresponds to the intersection of the ESP column and Model/Blower Speed row.
5.If the total system static falls between ESP values in the table (i.e. 0.58, 0.75, etc.), the static pressure may be rounded to the nearest value in the table determining the airflow using Step 4 or calculate the airflow by using the following example.
Example: For a 120,000 Btuh furnace operating on high speed blower, it is found that total system static is 0.58" w.c. To determine the system airflow, complete the following steps:
1.Obtain the airflow values at 0.50" & 0.60" ESP.
Airflow @ 0.50": 2152 CFM
Airflow @ 0.60": 2042 CFM
2.Subtract the airflow @ 0.50" from the airflow @ 0.60" to obtain air- flow difference.
2042 - 2152 =
3.Subtract the total system static from 0.50" and divide this differ- ence by the difference in ESP values in the table, 0.60" - 0.50", to obtain a percentage.
(0.58 - 0.50) / (0.60 - 0.50) = 0.8
4.Multiply percentage by airflow difference to obtain airflow reduc- tion.
(0.8) x
5.Subract airflow reduction value to airflow @ 0.50" to obtain actual airflow @ 0.58" ESP.
2152 - 88 = 2064
| FIELD INSTALLED ACCESSORIES - | ||
MODEL NO. | DESCRIPTION | USED WITH | |
1NP0347 | PROPANE (LP) CONVERSION KIT | ALL MODELS | |
1CT0302 | CONCENTRIC INTAKE/VENT 2” | ALL MODELS EXCEPT 120 MBH | |
1CT0303 | CONCENTRIC INTAKE/VENT 3” | ALL MODELS | |
1PS0904 |
| 40 | |
1PS0901 | HIGH ALTITUDE PRESSURE SWITCH KIT | 60/100/120 | |
| (Does Not Include Orifices) |
| |
1PS0902 | 80/1200 | ||
1PS0903 |
| 80/1600 | |
1NK0301 | CONDENSATE NEUTRALIZER KIT | ALL MODELS | |
1HT0901 | SIDEWALL VENT TERMINATION KIT 3” | ALL MODELS | |
1HT0902 | SIDEWALL VENT TERMINATION KIT 2” | ALL MODELS | |
1CB0314 | COMBUSTIBLE FLOOR BASE | ||
| These kits are required in downflow application when using G*F* |
| |
1CB0317 | |||
| series coils. These kits are not required with MC/FC series coils, |
| |
1CB0321 | 21” CABINET | ||
but please ensure that the coil and furnace are secured and that | |||
1CB0324 | 24 1/2” CABINET | ||
there are noair leaks. | |||
|
|
| |
1TK0914 |
| ||
1TK0917 | COIL TRANSITION KIT | ||
1TK0921 | 21” CABINET | ||
| |||
1TK0924 |
| 24 1/2” CABINET | |
1VK0901 | All MODELS |
38 | Unitary Products Group |