268890-UIM-B-0607

TABLE 18: Blower Performance CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODELS

 

 

Airflow with Top Return - without Filters (CFM)

 

Airflow with Top Return - without Filters (m3min)

Input/

Speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External Static Pressure, Inches W.C.

 

 

 

External Static Pressure, Inches (kPa)

 

 

Airflow/

Tap

 

 

 

 

 

 

Cabinet

 

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

0.025

0.050

0.075

0.099

0.124

0.149

0.174

0.199

0.224

0.249

 

High

1635

1590

1535

1480

1415

1340

1280

1185

NR

NR

46

45

43

42

40

38

36

34

NR

NR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40/1200/A

Med-High

1179

1170

1160

1140

1135

1098

1048

1026

NR

NR

33

33

33

32

32

31

30

29

NR

NR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Med-Low

969

967

967

959

938

905

860

802

NR

NR

27

27

27

27

27

26

24

23

NR

NR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low

774

753

745

726

698

674

652

612

NR

NR

22

21

21

21

20

19

18

17

NR

NR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High

1687

1652

1631

1595

1557

1511

1456

1382

1313

1211

48

47

46

45

44

43

41

39

37

34

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60/1200/B

Med-High

1193

1183

1173

1162

1142

1115

1076

1036

982

950

34

33

33

33

32

32

30

29

28

27

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Med-Low

933

933

921

911

902

872

825

793

771

712

26

26

26

26

26

25

23

22

22

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low

752

745

731

718

698

652

602

580

536

496

21

21

21

20

20

18

17

16

15

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High

1686

1658

1623

1572

1534

1465

1391

1305

1202

1091

48

47

46

44

43

41

39

37

34

31

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80/1200/B

Med-High

1257

1223

1218

1203

1177

1142

1094

1026

939

874

36

35

34

34

33

32

31

29

27

25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Med-Low

977

982

976

955

934

899

843

791

738

686

28

28

28

27

26

25

24

22

21

19

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low

775

777

757

733

698

663

627

584

549

490

22

22

21

21

20

19

18

17

16

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High

2071

2026

1981

1935

1864

1796

1713

1625

1532

1401

59

57

56

55

53

51

48

46

43

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80/1600/C

Med-High

1583

1590

1569

1554

1532

1502

1457

1409

1327

1221

45

45

44

44

43

43

41

40

38

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Med-Low

1256

1275

1275

1288

1275

1265

1232

1187

1126

1023

36

36

36

36

36

36

35

34

32

29

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low

937

939

936

945

942

936

912

874

810

726

27

27

26

27

27

26

26

25

23

21

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High

1996

1961

1938

1896

1836

1779

1707

1625

1531

1399

56

56

55

54

52

50

48

46

43

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100/1600/C

Med-High

1449

1480

1495

1488

1488

1449

1417

1368

1299

1208

41

42

42

42

42

41

40

39

37

34

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Med-Low

1167

1192

1192

1187

1202

1192

1182

1140

1097

1018

33

34

34

34

34

34

33

32

31

29

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low

932

900

871

840

805

761

710

663

641

623

26

25

25

24

23

22

20

19

18

18

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High

2404

2320

2225

2138

2034

1924

1816

1692

1559

1422

68

66

63

61

58

54

51

48

44

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100/2000/C

Med-High

2018

1955

1883

1815

1750

1670

1586

1497

1394

1246

57

55

53

51

50

47

45

42

39

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Med-Low

1626

1581

1531

1488

1418

1363

1291

1225

1123

964

46

45

43

42

40

39

37

35

32

27

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low

1336

1291

1249

1205

1155

1091

1018

951

884

759

38

37

35

34

33

31

29

27

25

21

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High

2520

2432

2353

2251

2152

2042

1947

1815

1701

1525

71

69

67

64

61

58

55

51

48

43

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120/2000/D

Med-High

2018

1979

1945

1911

1863

1779

1705

1599

1493

1353

57

56

55

54

53

50

48

45

42

38

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Med-Low

1586

1545

1501

1457

1407

1351

1287

1216

1081

926

45

44

42

41

40

38

36

34

31

26

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low

1321

1266

1213

1163

1111

1071

987

864

763

700

37

36

34

33

31

30

28

24

22

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Airflow expressed in standard cubic feet per minute (CFM) and in cubic meters per minute (m3/min).

2.Motor voltage at 115 V.

3.NR = Operation at this static pressure is not recommended.

FILTER PERFORMANCE

The airflow capacity data published in Table 18 represents blower per- formance WITHOUT filters. To determine the approximate blower per- formance of the system, apply the filter drop value for the filter being used or select an appropriate value from the Table 19.

TABLE 19: Filter Performance - Pressure Drop Inches W.C. and (kPa)

NOTE: The filter pressure drop values in Table 19 are typical values for the type of filter listed and should only be used as a guideline. Actual pressure drop ratings for each filter type vary between filter manufactur- ers.

Airflow Range

Minimum

 

 

Filter Type

 

 

Opening Size

Disposable

Washable Fiber

Pleated

 

 

 

 

 

 

 

 

 

 

 

 

CFM

m3/min

in2

cm2

In W.C.

kPA

In W.C.

kPA

In W.C.

kPA

0 - 750

0 - 21.4

230

1484

0.01

0.00249

0.01

0.00249

0.15

0.03736

 

 

 

 

 

 

 

 

 

 

751 - 1000

21.25 - 28.32

330

2129

0.05

0.01245

0.05

0.01245

0.20

0.04982

 

 

 

 

 

 

 

 

 

 

1001 - 1250

28.33 - 35.40

330

2129

0.10

0.02491

0.10

0.02491

0.20

0.04982

 

 

 

 

 

 

 

 

 

 

1251 - 1500

35.41 - 42.48

330

2129

0.10

0.02491

0.10

0.02491

0.25

0.06227

 

 

 

 

 

 

 

 

 

 

1501 - 1750

42.49 - 49.55

380

2452

0.15

0.03736

0.14

0.03487

0.30

0.07473

 

 

 

 

 

 

 

 

 

 

1751 - 2000

49.56 - 56.63

380

2542

0.19

0.04733

0.18

0.04484

0.30

0.07473

 

 

 

 

 

 

 

 

 

 

2001 & Above

56.64 - Above

463

2987

0.19

0.04733

0.18

0.04484

0.30

0.07473

Unitary Products Group

37

Page 37
Image 37
York GY9S*DH, GM9S*DH Filter Performance, Models, Airflow Range Minimum Filter Type Opening Size Disposable, Pleated

GF9S*DH, GY9S*DH, GM9S*DH specifications

The York GM9S*DH, GF9S*DH, and GY9S*DH series air conditioning systems are known for their robust performance, reliability, and energy efficiency. These models are well-suited for both residential and light commercial applications, making them versatile options for a range of users.

One of the standout features of these systems is their high efficiency. The GM9S*DH is equipped with advanced heating and cooling technologies that allow it to achieve excellent SEER (Seasonal Energy Efficiency Ratio) ratings. This translates to lower energy consumption and reduced utility bills for homeowners and business operators alike. The GF9S*DH model further enhances this efficiency by incorporating variable-speed blowers that adjust airflow based on specific needs, ensuring that the system operates only as necessary.

Reliability is another key characteristic of the York GM9S*DH, GF9S*DH, and GY9S*DH series. These models are engineered with durable components and rigorous performance testing, which contributes to their long lifespan and minimizes the need for repairs. Moreover, they come with robust warranties that provide peace of mind for consumers.

In terms of technology, these units utilize a smart thermostat feature that allows for precise temperature control and programmable settings. This feature not only enhances comfort but also contributes to energy savings by allowing users to set optimal cooling or heating schedules. The systems are also designed with quiet operation in mind, employing sound-dampening features that minimize noise levels, which is particularly beneficial for residential installations.

The installation of the York GM9S*DH, GF9S*DH, and GY9S*DH systems is straightforward, offering flexibility in placement and integration with various home or office setups. Their compact design allows them to fit seamlessly into different environments without compromising on performance.

Additionally, the systems are equipped with advanced filtration options that improve indoor air quality by capturing allergens and pollutants. This is particularly beneficial for families with children or members who suffer from allergies.

Overall, the York GM9S*DH, GF9S*DH, and GY9S*DH series provide exceptional performance, energy efficiency, and reliability, making them an ideal choice for maintaining a comfortable indoor environment. With their cutting-edge technologies and user-friendly features, these systems represent an excellent investment for anyone looking to enhance their heating and cooling experience.