In the USA use the following formula to calculate the furnace input.

For natural gas multiply the heat content of the gas BTU/SCF or Default 1030 BTU/SCF (38.4 MJ/m3), times 2 cubic ft. (0.056 m) of gas measured at the gas meter, times a barometric pressure and temperature correction factor of 0.960; times 3600, then divided by the time (In seconds) it took to measure 2 cubic ft. (0.056 m) of gas from the gas meter.

For propane (LP) gas multiply the heat content of the gas BTU/SCF or Default 2500 BTU/SCF (93.15 MJ/m3), times 1 cubic ft. (0.028 m) of gas mea- sured at the gas meter, times a barometric pressure and temperature correction factor of 0.960; times 3600, then divided by the time (In seconds) it took to measure 1 cubic ft. (0.028 m) of gas from the gas meter.

The formula for US input calculation using a cubic foot gas meter:

BTU/ft3 x 2 cu.ft. x 0.960 x 3600

=

BTU/H

BTU/ft3 x 1 cu.ft. x 0.960 x 3600

 

=

BTU/H

Seconds it took to measure the 2 cu.ft. of gas

Seconds it took to measure the 1 cu.ft. of gas

 

 

 

 

NATURAL GAS INPUT CALCULATION

 

 

PROPANE (LP) GAS INPUT CALCULATION

 

 

EXAMPLE:

 

 

EXAMPLE:

 

 

1030 x 2 x 0.960 x 3600

=

78,666.90

2500 x 1 x 0.960 x 3600

=

80,000.00

90.5

108

 

 

 

 

 

 

Natural Gas

 

 

Propane Gas

 

 

1030 BTU/SCF

 

 

2500 BTU/SCF

 

 

In Canada you will use the following formula to calculate the furnace input if you are using a cubic foot gas meter.

For Natural Gas multiply the Heat content of the gas MJ/m3 (or Default 38.4), times 2 cubic ft. of gas x 0.028 to convert from cubic feet to cubic meters measured at the gas meter, times a barometric pressure and temperature correction factor of 0.960; times 3600, then divided by the time it took to measure 2 cubic ft. (0.056 m) of gas from the gas meter.

For Propane (LP) Gas multiply the Heat content of the gas MJ/m3 (or Default 93.15), times 1 cu. ft. of gas x 0.028 to convert from cubic feet to cubic meters measured at the gas meter, times a barometric pressure and temperature correction factor of 0.960; times 3600, then divided by the time it took to measure 1 cubic ft. (0.028 m) of gas from the gas meter.

The formula for metric input calculation using a cubic foot gas meter:

MJ/m3 x 2 cu.ft. x 0.028 x 0.960 x 3600

 

=

MJ/H

x

0.2777

=

kW

x

3412.14

=

BTU/H

Seconds it took to measure the 2 cu.ft. of gas

 

 

 

 

 

 

 

 

 

 

NATURAL GAS INPUT CALCULATION

 

 

 

 

 

 

 

 

 

 

EXAMPLE:

 

 

 

 

 

 

 

 

 

 

38.4 x 2 x 0.028 x 0.960 x 3600

=

82.12

x

0.2777

=

22.80

x

3412.14

=

77,796.80

90.5

 

 

 

 

 

 

 

 

 

 

 

 

Natural Gas

 

 

 

 

 

 

 

 

 

 

1030 BTU/SCF = 38.4 MJ/m3

 

 

 

 

 

 

 

 

 

 

PROPANE (LP) GAS INPUT CALCULATION

 

 

 

 

 

 

 

 

 

 

EXAMPLE:

 

 

 

 

 

 

 

 

 

 

93.15 x 1 x 0.028 x 0.960 x 3600

=

83.46

x

0.2777

=

23.18

x

3412.14

=

79,093.4

108

 

 

 

 

 

 

 

 

 

 

 

 

Propane Gas

2500 BTU/SCF = 93.15 MJ/m3

In Canada use the following formula to calculate the furnace input if you are using a gas meter that measures cubic meters.

For Natural Gas multiply the Heat content of the gas MJ/m3 (or Default 38.4), times 0.10 m3 of gas measured at the gas meter, times a barometric pressure and temperature correction factor of 0.960; times 3600, then divided by the time it took to measure 0.10 m3 of gas from the gas meter.

For Propane (LP) Gas multiply the Heat content of the gas MJ/m3 (or Default 93.15), times 0.10 m3 of gas measured at the gas meter, times a baro- metric pressure and temperature correction factor of 0.960; times 3600, then divided by the time it took to measure 0.10 m3 of gas from the gas meter.

The formula for metric input calculation using a cubic meter gas meter:

MJ/m3 x m3 x 0.960 x 3600

=

MJ/H

x

0.2777

=

kW

x

3412.14

=

BTU/H

Seconds it took to measure the 0.10 m3 of gas

 

 

 

 

 

 

 

 

 

 

NATURAL GAS INPUT CALCULATION

 

 

 

 

 

 

 

 

 

 

EXAMPLE:

 

 

 

 

 

 

 

 

 

 

38.4 x 0.1 x 0.960 x 3600

=

82.94

x

0.2777

=

23.03

x

3412.14

=

78,581.60

160

 

 

 

 

 

 

 

 

 

 

Natural Gas

 

 

 

 

 

 

 

 

 

 

1030 BTU/SCF = 38.4 MJ/m3

 

 

 

 

 

 

 

 

 

 

PROPANE (LP) GAS INPUT CALCULATION

 

 

 

 

 

 

 

 

 

 

EXAMPLE:

 

 

 

 

 

 

 

 

 

 

93.15 x 0.1 x 0.960 x 3600

=

83.19

x

0.2777

=

23.10

x

3412.14

=

78,826.3

387

 

 

 

 

 

 

 

 

 

 

Propane Gas

2500 BTU/SCF = 93.15 MJ/m3

DO NOT ADJUST the manifold pressure regulator if the actual input is equal to or within 8% less than the furnace input specified on the rating plate or if the furnace rise is above the specified rise range on the rating plate.

If the actual input is significantly higher than the furnace input specified on the rating plate then replace the gas orifices with the gas orifices of the proper size for the type of gas you are using.

Unitary Products Group

33

Page 33
Image 33
York GM9S*DH, GY9S*DH, GF9S*DH installation manual USA use the following formula to calculate the furnace input

GF9S*DH, GY9S*DH, GM9S*DH specifications

The York GM9S*DH, GF9S*DH, and GY9S*DH series air conditioning systems are known for their robust performance, reliability, and energy efficiency. These models are well-suited for both residential and light commercial applications, making them versatile options for a range of users.

One of the standout features of these systems is their high efficiency. The GM9S*DH is equipped with advanced heating and cooling technologies that allow it to achieve excellent SEER (Seasonal Energy Efficiency Ratio) ratings. This translates to lower energy consumption and reduced utility bills for homeowners and business operators alike. The GF9S*DH model further enhances this efficiency by incorporating variable-speed blowers that adjust airflow based on specific needs, ensuring that the system operates only as necessary.

Reliability is another key characteristic of the York GM9S*DH, GF9S*DH, and GY9S*DH series. These models are engineered with durable components and rigorous performance testing, which contributes to their long lifespan and minimizes the need for repairs. Moreover, they come with robust warranties that provide peace of mind for consumers.

In terms of technology, these units utilize a smart thermostat feature that allows for precise temperature control and programmable settings. This feature not only enhances comfort but also contributes to energy savings by allowing users to set optimal cooling or heating schedules. The systems are also designed with quiet operation in mind, employing sound-dampening features that minimize noise levels, which is particularly beneficial for residential installations.

The installation of the York GM9S*DH, GF9S*DH, and GY9S*DH systems is straightforward, offering flexibility in placement and integration with various home or office setups. Their compact design allows them to fit seamlessly into different environments without compromising on performance.

Additionally, the systems are equipped with advanced filtration options that improve indoor air quality by capturing allergens and pollutants. This is particularly beneficial for families with children or members who suffer from allergies.

Overall, the York GM9S*DH, GF9S*DH, and GY9S*DH series provide exceptional performance, energy efficiency, and reliability, making them an ideal choice for maintaining a comfortable indoor environment. With their cutting-edge technologies and user-friendly features, these systems represent an excellent investment for anyone looking to enhance their heating and cooling experience.