WITH BURNER BOX COVER IN PLACE
WITH BURNER BOX COVER REMOVED
TEEGAS
FITTING VALVE
BURNER BOX
PRESSURE
REFERENCE
HOSE
|
| 6 |
|
| 5 |
|
| 4 |
|
| 3 |
| 2 | |
| 1 | |
MANOMETER |
| 0 |
| 1 | |
|
| 2 |
|
| 3 |
|
| 4 |
|
| 5 |
|
| 6 |
3.5 IN
WATER COLUMN GAS PRESSURE SHOWN
GAS VALVE
BURNER BOX
PRESSURE
REFERENCE
HOSE
|
| 6 |
|
|
|
|
| 5 |
|
|
|
|
|
| |||
|
| 4 |
|
| 3.5 IN |
| 3 |
|
| ||
| 2 |
|
| WATER COLUMN | |
MANOMETER |
| 1 |
|
| |
| 0 |
|
| GAS PRESSURE | |
|
| 1 |
|
| |
|
| 2 |
|
| SHOWN |
|
| 3 |
|
| |
|
| 4 |
|
|
|
|
| 5 |
|
|
|
|
| 6 |
|
|
|
|
|
|
|
|
|
FIGURE 39: Reading Gas Pressure
ADJUSTMENT OF TEMPERATURE RISE
The temperature rise, or temperature difference between the return air and the supply (heated) air from the furnace, must be within the range shown on the furnace rating plate and within the application limitations shown in Table 7 “ELECTRICAL AND PERFORMANCE DATA”.
The supply air temperature cannot exceed the “Maximum Supply Air Temperature” specified in these instructions and on the fur- nace rating plate. Under NO circumstances can the furnace be allowed to operate above the Maximum Supply Air Temperature. Operating the furnace above the Maximum Supply Air Temperature will cause premature heat exchanger failure, high levels of Carbon Monoxide, a fire hazard, personal injury, property damage, and/or death.
The temperature rise, or temperature difference between the return air and the heated supply air from the furnace, must be within the range shown on the furnace rating plate and within the application limitations as shown in Table 7.
After about 20 minutes of operation, determine the furnace temperature rise. Take readings of both the return air and the heated air in the ducts, about six feet (1.83 m) from the furnace where they will not be affected by radiant heat. Increase the blower speed to decrease the temperature rise; decrease the blower speed to increase the rise.
TWIN
FAN OFF |
|
|
|
|
ADJUSTMENT | Y/Y2 | 180 | 120 | 60 90 |
JUMPER |
| DELAY | BLOWER OFF | |
|
|
|
| |
| W |
|
|
|
| R |
|
|
|
| G |
|
|
|
| C |
|
|
|
FIGURE 40: Furnace Control Board
All
Do not energize more than one motor speed at a time or damage to the motor will result.
ADJUSTMENT OF FAN CONTROL SETTINGS
This furnace is equipped with a
The blower speed connections shown in Figure 40 are typical. How- ever, these connections may vary from model to model and may be changed as needed to give proper heating and cooling airflow.
PARK PARK |
| |
|
| |
| HI COOL | |
| HEAT | |
|
| |
|
| |
| L1 |
|
| XFMR |
|
NEUTRALS |
|
|
HUM
Unitary Products Group | 35 |