Accessories and Modifications (continued)
MARINE WATER BOXES
Marine water boxes allow service access for cleaning of the heat exchanger tubes without the need to break the water piping. 
KNOCK-DOWN  SHIPMENT
The chiller can be shipped 
required to rig into tight spaces. This is particularly con- venient for existing buildings where equipment room access does not allow rigging a factory packaged chiller.
REFRIGERANT STORAGE/RECYCLING SYSTEM
A refrigerant storage/recycling system is a 
SI Metric Conversion
The following factors can be used to convert from English to the most common Sl Metric values.
| MEASUREMENT | MULTIPLY THIS | BY | TO OBTAIN THIS | |
| ENGLISH VALUE | METRIC VALUE | |||
| 
 | 
 | |||
| 
 | 
 | 
 | 
 | |
| CAPACITY | TONS REFRIGERANT EFFECT (ton) | 3.516 | KILOWATTS (kW) | |
| POWER | KILOWATTS (kW) | NO CHANGE | KILOWATTS (kW) | |
| 
 | 
 | 
 | ||
| HORSEPOWER (hp) | 0.7457 | KILOWATTS (kW) | ||
| 
 | ||||
| FLOW RATE | GALLONS / MINUTE (gpm) | 0.0631 | LITERS / SECOND (L/s) | |
| LENGTH | FEET (ft) | 304.8 | MILLIMETERS (mm) | |
| 
 | 
 | 
 | ||
| INCHES (in) | 25.4 | MILLIMETERS (mm) | ||
| 
 | ||||
| 
 | 
 | 
 | 
 | |
| WEIGHT | POUNDS (lb) | 0.4536 | KILOGRAMS (kg) | |
| VELOCITY | FEET / SECOND (fps) | 0.3048 | METERS / SECOND (m/s) | |
| PRESSURE DROP | FEET OF WATER (ft) | 2.989 | KILOPASCALS (k Pa) | |
| POUNDS / SQ. INCH (psi) | 6.895 | KILOPASCALS (k Pa) | ||
| 
 | ||||
| 
 | 
 | 
 | 
 | 
Integrated Part Load Value (IPLV)
In the English 
| 
 | 
 | 
 | 
 | 
 | 
 | 1 | 
 | 
 | 
 | 
 | 
| IPLV* = | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 0.01 | + | 0.42 | + | 0.45 | + | 0.12 | 
 | |||
| 
 | 
 | |||||||||
| 
 | 
 | A | 
 | B | C | D | ||||
| 
 | 
 | 
 | 
 | 
 | 
 | |||||
| Where: A = | kW / ton at 100% Load @ 85°F ECFT | |||||||||
| 
 | B = | kW / ton at | 75% Load @ 75°F ECFT | |||||||
| 
 | C = | kW / ton at | 50% Load @ 65°F ECFT | |||||||
| 
 | D = | kW / ton at | 25% Load @ 65°F ECFT | |||||||
In SI Metric, the formula is:
IPLV* = 0.01A + 0.42B + 0.45C + 0.12D
Where: A = COP at 100% Load @ 29.4°C ECFT
B= COP at 75% Load @ 23.9°C ECFT
C= COP at 50% Load @ 18.3°C ECFT
D= COP at 25% Load @ 18.3°C ECFT
NOTE:
*The 
| 18 | YORK INTERNATIONAL | 
| 
 | 