FORM 160.81-EG1

Accessories and Modifications (continued)

MARINE WATER BOXES

Marine water boxes allow service access for cleaning of the heat exchanger tubes without the need to break the water piping. Bolted-on covers are arranged for con- venient access. Victaulic nozzle connections are stan- dard; flanges are optional. Marine water boxes are avail- able for condenser and/or evaporator.

KNOCK-DOWN SHIPMENT

The chiller can be shipped knocked-down into major assemblies (evaporator, condenser, driveline, etc.) as

required to rig into tight spaces. This is particularly con- venient for existing buildings where equipment room access does not allow rigging a factory packaged chiller.

REFRIGERANT STORAGE/RECYCLING SYSTEM

A refrigerant storage/recycling system is a self-contained package consisting of a refrigerant compressor with oil separator, storage receiver, water-cooled condenser, fil- ter drier and necessary valves and hoses to remove, replace and distill refrigerant. All necessary controls and safety devices are a permanent part of the system. Typi- cally not required if unit isolation valves are provided.

SI Metric Conversion

The following factors can be used to convert from English to the most common Sl Metric values.

MEASUREMENT

MULTIPLY THIS

BY

TO OBTAIN THIS

ENGLISH VALUE

METRIC VALUE

 

 

 

 

 

 

CAPACITY

TONS REFRIGERANT EFFECT (ton)

3.516

KILOWATTS (kW)

POWER

KILOWATTS (kW)

NO CHANGE

KILOWATTS (kW)

 

 

 

HORSEPOWER (hp)

0.7457

KILOWATTS (kW)

 

FLOW RATE

GALLONS / MINUTE (gpm)

0.0631

LITERS / SECOND (L/s)

LENGTH

FEET (ft)

304.8

MILLIMETERS (mm)

 

 

 

INCHES (in)

25.4

MILLIMETERS (mm)

 

 

 

 

 

WEIGHT

POUNDS (lb)

0.4536

KILOGRAMS (kg)

VELOCITY

FEET / SECOND (fps)

0.3048

METERS / SECOND (m/s)

PRESSURE DROP

FEET OF WATER (ft)

2.989

KILOPASCALS (k Pa)

POUNDS / SQ. INCH (psi)

6.895

KILOPASCALS (k Pa)

 

 

 

 

 

Integrated Part Load Value (IPLV)

In the English I-P system, IPLV is calculated by the fol- lowing formula. A full explanation is shown on page 4:

 

 

 

 

 

 

1

 

 

 

 

IPLV* =

 

 

 

 

 

 

 

 

 

 

0.01

+

0.42

+

0.45

+

0.12

 

 

 

 

 

A

 

B

C

D

 

 

 

 

 

 

Where: A =

kW / ton at 100% Load @ 85°F ECFT

 

B =

kW / ton at

75% Load @ 75°F ECFT

 

C =

kW / ton at

50% Load @ 65°F ECFT

 

D =

kW / ton at

25% Load @ 65°F ECFT

In SI Metric, the formula is:

IPLV* = 0.01A + 0.42B + 0.45C + 0.12D

Where: A = COP at 100% Load @ 29.4°C ECFT

B= COP at 75% Load @ 23.9°C ECFT

C= COP at 50% Load @ 18.3°C ECFT

D= COP at 25% Load @ 18.3°C ECFT

NOTE:

*The Non-Standard Part-Load Value (NPLV) uses the IPLV formula with the following exceptions: the ECFT for part-load points varies linearly from the selected EFT to 65°F (18.3°C) from 100% to 50% loads, and fixed at 65°F (18.3°C) for 50% to 0% loads.

18

YORK INTERNATIONAL

 

Page 18
Image 18
York YR manual SI Metric Conversion, Marine Water Boxes, KNOCK-DOWN Shipment, Refrigerant STORAGE/RECYCLING System