FORM 160.81-EG1

collecting the data, but the oldest data drops off the graph from left to right at the next data collection inter- val. For ease of identification, each plotted parameter, title and associated Y-axis labeling is color coordinated.

Display Only:

This screen allows the user to view the graphical trending of the selected parameters and is a gate- way to the graph setup screens.

Programmable:

Start

Stop

y-axis

x-axis

The TREND SETUP screen is used to configure the trending screen. The parameters to be trended are se- lected from the Trend Common Slots screen, accessed from the Slot Numbers button or the Master Slot Num- bers List found in the Operating Manual. The interval at which all the parameters are sampled is selected under the Collection Interval button. The data point minimum and maximum values may be adjusted closer to in- crease viewing resolution.

Programmable:

Chart Type (select continuous or one screen)

Collection Interval

Select

Data Point Slot Number (1 - 6)

Data Point Min. (1 - 6)

Data Point Max (1 - 6)

The TREND COMMON SLOTS screen displays the Master Slot Numbers List of the monitored parameters.

Display Only:

• Slot Numbers

Programmable:

Page Up

Page Down

Print

DISPLAY MESSAGES

The Control Center continuously monitors the operat- ing system, displaying and recording the cause of any shutdowns (Safety, Cycling or Normal). The condition of the chiller is displayed at the System Status line that contains a message describing the operating state of the chiller; whether it is stopped, running, starting or shutting down. A System Details Line displays Warn- ing, Cycling, Safety, Start Inhibit and other messages that provide further details of the Status Bar messages. Messages are color-coded: Green – Normal Operations; Yellow – Warnings; Orange – Cycling Shutdowns; and Red – Safety Shutdowns to aid in identifying problems quickly.

Status messages include:

System Ready To Start

Cycling Shutdown – Auto Restart

Safety Shutdown – Manual Restart

Start Sequence Initiated

System Run (with countdown timers)

Start Inhibit

Slide Valve Closing Before Shutdown

System Lockout Delay

Run Messages include:

Leaving Chilled Liquid Control

Motor Pulldown Limit

Motor – High Current Limit

Start Inhibit Messages include:

Anti-Recycle XX min/sec.

Slide Valve – Position >30%

Motor Current >15% FLA

LCSSS – High-Temperature Phase X - Stopped

Warning Messages include:

Real Time Clock Failure

Setpoint Override

Condenser – High Pressure Limit

Evaporator – Low Pressure Limit

Freeze Threat From Operating Chiller

Freeze Threat, Condenser Flow Switch Open

Low Discharge Superheat Limit