FLA =

Motor kW

x Max. Motor FLA

Max. Motor kW

 

 

The benefit from the FLA correction is the possible use of smaller power wiring and/or starter size.

The locked rotor amperes (LRA) are read directly from Tables 3 and 4 for specific Motor Code and voltage. This is because the LRA is dependent only on motor size and voltage and is independent of input power (kW).

Inrush amperes (IRA) depend on LRA and the type of starter applied. The inrush can be calculated using a percentage of LRA shown in Table 5.

TABLE 3 – 60 HZ ELECTRICAL DATA

 

NAME-

AMP

 

 

 

 

 

 

 

 

MOTOR DATA

 

 

 

 

 

 

 

 

COMP.

PLATE

(MAX)

100%

90%

80%

70%

60%

50%

40%

30%

20%

MAX.

 

VOLT.

FLA

LRA

PF

EFF

PF

EFF

PF

EFF

PF

EFF

PF

 

EFF

PF

EFF

PF

EFF

PF

EFF

PF

EFF

KW (hp)

 

200

850

3634

88.2

94.8

87.8

95.2

87.3

95.5

85.8

95.7

84.3

 

95.9

80.4

96.0

76.5

96.0

65.8

95.2

55.1

94.4

 

 

208

825

3779

86.6

95.0

85.6

95.3

84.6

95.5

82.6

95.7

80.5

 

95.9

75.5

95.8

70.5

95.7

59.0

94.8

47.4

93.8

 

 

230

725

2901

89.2

94.5

89.1

95.0

89.0

95.4

88.2

95.7

87.3

 

96.0

84.5

96.1

81.6

96.2

72.4

95.6

63.1

94.9

 

 

240

695

3027

88.2

94.9

87.7

95.2

87.2

95.5

85.8

95.8

84.3

 

96.0

80.4

96.0

76.5

96.0

65.8

95.2

55.0

94.4

 

T0/T1

380

438

1727

89.3

94.6

89.3

95.0

89.2

95.4

88.5

95.7

87.8

 

96.0

85.1

96.1

82.4

96.2

73.5

95.6

64.6

95.0

251.6

 

440

370

1390

89.6

94.2

89.8

94.7

90.0

95.2

89.6

95.6

89.2

 

95.9

87.2

96.1

85.2

96.3

77.7

95.9

70.1

95.4

(321)

 

460

354

1453

89.2

94.6

89.1

95.0

88.9

95.4

88.1

95.7

87.3

 

96.0

84.5

96.1

81.6

96.2

72.4

95.6

63.1

94.9

 

 

480

339

1516

88.2

94.9

87.7

95.2

87.2

95.5

85.8

95.8

84.3

 

96.0

80.4

96.0

76.5

96.0

65.8

95.2

55.0

94.4

 

 

575

300

1162

89.2

94.6

89.1

95.0

88.9

95.4

88.1

95.7

87.3

 

96.0

84.4

96.1

81.5

96.2

72.3

95.6

93.1

95.0

 

 

600

288

1213

88.2

94.9

87.7

95.3

87.2

95.6

85.8

95.8

84.3

 

96.0

80.4

96.0

76.5

96.0

65.8

95.3

55.0

94.5

 

 

200

882

4048

90.4

94.8

90.2

95.2

90.0

95.5

89.2

95.8

88.3

 

96.0

85.6

96.0

82.9

96.0

73.8

95.3

64.7

94.6

 

 

208

860

4210

89.1

95.0

88.5

95.3

87.8

95.6

86.4

95.8

94.9

 

96.0

81.3

96.0

77.6

95.9

67.1

95.0

56.5

94.1

 

 

230

760

3520

90.5

94.7

90.4

95.1

90.2

95.4

89.5

95.7

88.7

 

95.9

86.2

96.0

83.7

96.0

75.0

95.4

66.3

94.7

 

 

240

737

3673

89.3

95.0

88.8

95.3

88.3

95.5

86.9

95.7

85.4

 

95.9

81.9

95.9

78.3

95.9

67.9

95.0

57.5

94.1

 

T2/T3

380

464

2130

90.3

94.8

90.1

95.2

89.9

95.5

89.1

95.8

88.2

 

96.0

85.6

96.0

82.9

96.0

73.8

95.3

64.7

94.6

275.9

 

440

400

1603

91.0

94.4

91.2

94.9

91.4

95.3

91.1

95.6

90.8

 

95.9

89.3

96.1

87.7

96.2

80.9

95.7

74.0

95.1

(351)

 

460

383

1676

90.5

94.7

90.4

95.1

90.2

95.5

89.5

95.8

88.7

 

96.0

86.2

96.1

83.7

96.1

75.0

95.4

66.2

94.7

 

 

480

372

1749

89.3

95.0

88.8

95.3

88.2

95.6

86.8

95.8

85.4

 

96.0

81.8

96.0

78.2

95.9

67.9

95.0

57.5

94.1

 

 

575

305

1408

90.7

94.7

90.7

95.1

90.6

95.5

90.0

95.8

89.4

 

96.0

87.2

96.1

85.0

96.2

77.0

95.5

68.9

94.8

 

 

600

293

1469

89.9

95.0

89.5

95.3

89.1

95.6

88.0

95.8

86.9

 

96.0

83.8

96.0

80.7

96.0

71.0

95.2

61.2

94.4

 

NOTE: FLA = Full-load Amps;

LRA = Locked Rotor Amps; PF = Power Factor;

EFF = Motor Efficiency

 

 

 

 

 

 

100% Loading is Percentage of Maximum Motor Load; not of Specific Application

 

 

 

 

 

 

 

 