York YR manual HZ Electrical Data

Models: YR

1 40
Download 40 pages 10.54 Kb
Page 24
Image 24

FORM 160.81-EG1

TABLE 4 – 50 HZ ELECTRICAL DATA

 

NAME-

AMP

 

 

 

 

 

 

 

 

 

MOTOR DATA

 

 

 

 

 

 

 

 

COMP.

PLATE

(MAX)

100%

90%

80%

70%

60%

 

50%

40%

30%

20%

MAX.

 

VOLT.

FLA

LRA

PF

 

EFF

PF

EFF

PF

EFF

PF

EFF

PF

EFF

 

PF

EFF

PF

EFF

PF

EFF

PF

EFF

KW (hp)

 

380

364

1414

89.3

 

93.7

89.2

94.3

89.1

94.8

88.4

95.2

87.7

95.6

 

84.9

95.8

82.1

95.9

73.3

95.3

64.5

94.7

210.2

T0/T1

400

348

1488

88.2

 

94.1

87.7

94.6

87.2

95.0

85.9

95.3

84.5

95.6

 

80.4

95.7

76.3

95.7

65.6

94.9

54.9

94.1

 

 

(267)

 

415

333

1544

89.2

 

93.8

89.1

94.4

88.9

94.9

88.1

95.3

87.3

95.6

 

84.3

95.8

81.3

95.9

72.2

95.3

93.1

94.6

 

 

 

 

 

380

390

1639

90.4

 

94.0

90.3

94.5

90.1

94.9

89.4

95.3

88.6

95.6

 

86.2

95.8

83.7

96.0

75.2

95.4

66.6

94.8

231.9

T2/T3

400

371

1725

89.6

 

94.4

89.1

94.8

88.6

95.2

87.3

95.5

85.9

95.7

 

82.4

95.8

78.9

95.8

68.5

95.1

58.1

94.3

 

 

(292)

 

415

354

1790

90.4

 

94.0

90.3

94.5

90.1

94.9

89.3

95.3

88.5

95.6

 

86.1

95.8

83.6

95.9

75.1

95.4

66.5

94.8

 

 

 

 

NOTE: FLA = Full-load Amps;

LRA = Locked Rotor Amps;

PF = Power Factor;

EFF = Motor Efficiency

 

 

 

 

 

 

 

100% Loading is Percentage of Maximum Motor Load; not of Specific Application

 

 

 

 

 

 

 

 

 

TABLE 5 – MOTOR STARTERS

 

TYPE

SOLID

STAR DELTA

AUTO TRANSFORMER

ACROSS

 

 

STATE

 

 

STARTER

THE LINE

 

 

STARTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60HZ

200-600

200-600

200-600

200-600

200-600

200-600

200-600

 

 

50 HZ

380-415

380-415

380-415

380-415

380-415

380-415

380-415

 

 

TRANSITION

NONE

CLOSED

OPEN

CLOSED

CLOSED

CLOSED

 

 

% TAP

57.7

65

80

 

 

INRUSH

45

33

33

33

42.3

64

100

 

 

AS A % OF LRA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TABLE 6 – AVAILABLE COMPRESSOR/SHELL COMBINATIONS

COMPRESSOR

EVAPORATOR

CONDENSER

CODE

SHELL

SHELL

T0, T1

TB, TC, TD

TB, TC, TD

VB, VC, VD

VB, VC, VD

 

T1

WB, WC, WD

WB, WC, WD

T2/T3

WB, WC, WD

WB, WC, WD

XB, XC, XD

XB, XC, XD

 

 

 

 

24

YORK INTERNATIONAL

 

Page 24
Image 24
York YR manual HZ Electrical Data