Recipe (Ramp/ Soak) Menu
For Ramp Events and Soak Events to be employed, Alarm 1 or Alarm 2 must be set for
event usage in the Alarm Menu.
Supervisor Menu
The Failsafe State is only enforced when a problem is detected with the process input. It is not reli- ably enforceable in instances of internal circuitry failure such as EEPROM problems.
Output % High Limits are ignored when the unit enters a Failsafe State.
NOTE: The following seven parameters are only available when
Display Parameter | Selection |
Recycle Number | |
(Recipe Executions) |
|
Power Fail Resume | Off |
| On |
Ramp Times | |
Ramp Events | Alarm 1 On |
| Alarm 1 Off |
| Alarm 2 On |
| Alarm 2 Off |
| Disabled |
Soak Levels 1- 8 | Display Units, FS |
Soak Times | |
Soak Events | Alarm 1 On |
| Alarm 1 Off |
| Alarm 2 On |
| Alarm 2 Off |
| Disabled |
Display Parameter | Selection |
Output 1 | 0 to 100% |
Failsafe State | of output |
Output 2 | 0 to 100% |
Failsafe State | of output |
Loop Break Time | Off, |
Highest Reading | n/a |
Lowest Reading | n/a |
Load Default |
|
Parameters |
|
Choosing “Yes” to Load Default Parameters resets all menu parameters to factory settings.
24