Athena Technologies 16C instruction manual Glossary

Page 43

Glossary

Alarm Delay - the time delay between the detection of the alarm

condi-

tion and the initiation and indication of the output action.

 

Alarm Inhibit - prevents low setpoint alarm activation during cold startup applications.

Bias - allows the operator to compensate for any difference between sensor temperature and the point to be measured. The process display and set- point will be offset by the value entered in the Bias parameter in the input menu. Ex: Desired temperature is 150 degrees. Sensor is adjacent to heater and reads 50 degrees higher than the actual process temperature. Enter bias of -50. Enter setpoint of 150. Process will display 150 even though sensor will be measuring 200 degrees.

Blanking - controls the time the setpoint value display remains on. After the set time, the setpoint value display turns off. Pressing any button causes the setpoint value display to reappear for the selected time interval.

Cycle Time - The period of time in which the controller’s output completes an on-off cycle (Proportional Output Type only).

Example: Output type = Mechanical relay Cycle time = 10 seconds Output power = 50%

Controller output = 5 seconds closed, 5 seconds open

Deadband - In On/Off temperature control, it is the band above or below the setpoint where there is no output action. It has the effect of moving the apparent setpoint.

Derivative (rate) - Adjusts the controller gain quickly in response to load changes.

Failsafe State - designates the percentage of power output that the con- troller defaults to after it detects a loop break condition and after the loop break time has elapsed.

Filter (in Display menu) - changes the filtering speed for the process value display only. It does not affect control. This parameter is mainly used to slow down the flickering of the display when the decimal position chosen is greater than zero.

Filtering (in Input menu) - sets the time period over which the process value is averaged.

Highest Reading - records the highest process value read by the controller. It may be reset to zero by using the Raise or Lower arrow keys. Hysteresis - In On/Off temperature control, hysteresis represents the band where the output changes state from deactivated to activated. It prevents chattering around the setpoint and prevents rapid output cycling.

Integral (automatic reset) - slowly adjusts the position of the Proportional Band (range of power output) to eliminate offset error.

Loop Break - a condition where the input is not changing or responding properly to the output action. This could be caused by a thermocouple or

39

Image 43
Contents 16C Introduction Precautions FeaturesSafety Warning Contents Installation Mounting DimensionsContact Identification WiringLead resistance. For long runs Wire RTDs should be used Make sure that you are using Appropriate thermocoupleRTDs. Connect 2-wire RTDs Wire, if necessary, to minimizeA 120/240 Vac relay, but normally closed output 2 only Output TypesRaise Key Menu Access KeyMode/Enter Key Lower KeySecurity Level, Menu System, and Operating Mode Power OnSecurity Levels Security Levels and Access RestrictionsManual Operating ModesMenu System Overview Been installed. Pressing the Menu Access key indexesMenu System Overview Menu SystemChart of Series 16C Menu System Security Levels On Next See options manual for parameter selections Descriptions Menus and ParameterDisplay Parameter Selection Input MenuJMPØ2 Output Menu Display MenuDisplay Parameter Output Menu Control Menu Output Type Recommended Setting secondsParameter Selection On/Off Output TypeBelow alarm setting Setpoint. High process alarmDeviation Alarm Alarm Output Type Autotune Damping Menu Recipe Ramp/ Soak Menu Eter should be set to which will disable itPower Fail Resume Supervisor Menu Options Menu Calibration MenuTo place the controller in Autotune mode AutotuningAutotuning Procedure Diagram Time Seconds Manual TuningBand Number is the correct DerivativePossible error codes are Error CodesDisplay Problem Actions Technical Specifications For rated accuracy Platinum 2- and 3-wire, 100 ohms atThermocouple Maximum lead resistance 100 ohmsModel Input Calibration Type Ordering CodesRTD Calibration Values Quick-Helps Press and hold For 3 sec + PV + BUYER’S Remedy is Limited to Either i Repair or Warranty Repairs Two-Year Limited Warranty Other than those expressly stated herein, There are noUnit Repairs Fuse rating=100 mA Requirements250 Vpk 20 mA Glossary Applications for On/Off Control Quick Setup Instructions Series 16C Temperature Controller Configured Parameters Reference Data Page For Toll-FreeTechnical Assistance in the USA Call Toll Free