Athena Technologies 16C Error Codes, Possible error codes are, Display Problem Actions

Page 33

Error Codes

If an error code cannot be cleared by using the actions provided, contact factory.

Display

Problem

Actions

 

Open Sensor

Check sensor,

 

 

wiring, and Input.

 

Reversed Sensor

Check the type

 

 

selection in

 

 

the Input menu,

 

 

and check sensor

 

 

polarity.

 

Loop Break

Correct problem

 

 

and reset controller.

 

Checksum Error

Press any key

 

RAM Error

to perform a

 

Defaults Loaded

soft reset and

 

EEPROM Write Failure

reinitialize

 

 

controller.

 

Power Fail Resume

No further resume

 

Feature Disabled

actions available.

Plus other

Unexpected or

Reset

2-Digit

Invalid Interrupt

controllers

Code

 

 

Autotune Errors

If a tune error condition occurs, the upper display will toggle

between and a numeric error code for three seconds before the tune process terminates. The controller will then automatically go into Standby mode when a tuning error occurs. Possible error codes are:

02 = No PID Device Configured

03 = Incorrect Output Action

05 = Insufficient Setpoint-Process Value Deviation

08 = Invalid Tune Results

09 = Tune Timeout

Ramp/Soak Errors

Possible error codes are:

02 = Recipe Empty (i.e. no non-zero ramp times) 05 = Insufficient Setpoint-Process Value Deviation

29

Image 33
Contents 16C Introduction Precautions FeaturesSafety Warning Contents Installation Mounting DimensionsContact Identification WiringRTDs. Connect 2-wire RTDs Make sure that you are using Appropriate thermocoupleWire, if necessary, to minimize Lead resistance. For long runs Wire RTDs should be usedA 120/240 Vac relay, but normally closed output 2 only Output TypesMode/Enter Key Menu Access KeyLower Key Raise KeySecurity Level, Menu System, and Operating Mode Power OnSecurity Levels Security Levels and Access RestrictionsManual Operating ModesMenu System Overview Been installed. Pressing the Menu Access key indexesMenu System Overview Menu SystemChart of Series 16C Menu System Security Levels On Next See options manual for parameter selections Descriptions Menus and ParameterDisplay Parameter Selection Input MenuJMPØ2 Display Menu Output MenuDisplay Parameter Output Menu Control Menu Output Type Recommended Setting secondsParameter Selection On/Off Output TypeSetpoint. High process alarm Below alarm settingDeviation Alarm Alarm Output Type Autotune Damping Menu Recipe Ramp/ Soak Menu Eter should be set to which will disable itPower Fail Resume Supervisor Menu Options Menu Calibration Menu To place the controller in Autotune mode AutotuningAutotuning Procedure Diagram Band Manual TuningNumber is the correct Derivative Time SecondsError Codes Possible error codes areDisplay Problem Actions Technical Specifications Thermocouple Platinum 2- and 3-wire, 100 ohms atMaximum lead resistance 100 ohms For rated accuracyModel Input Calibration Type Ordering CodesRTD Calibration Values Quick-Helps Press and hold For 3 sec + PV + Two-Year Limited Warranty Warranty RepairsOther than those expressly stated herein, There are no BUYER’S Remedy is Limited to Either i Repair orUnit Repairs Requirements Fuse rating=100 mA250 Vpk 20 mA Glossary Applications for On/Off Control Quick Setup Instructions Series 16C Temperature Controller Configured Parameters Reference Data Page For Toll-FreeTechnical Assistance in the USA Call Toll Free