Technical
Specifications
Operating Limits |
|
Ambient Temperature | 32°F to 140°F (0°C to 60°C) |
Relative Humidity Tolerance | 90%, |
Power | 100 to 250 V |
| 50/60 Hz |
| 100 to 250 Vdc |
| 24 Vac/dc |
Power Consumption | Less than 6 VA |
Performance |
|
Accuracy | ±0.20% of Full Scale |
| (±0.10% Typical), ±1 Digit |
Setpoint Resolution | 1 Count / 0.1 Count |
Repeatability | ±1 Count |
Temperature Stability | 5 µV /°C (Maximum) |
TC | 0.05°C /°C Ambient |
Noise Rejection | >100 dB Common Mode, |
| >70 dB Series Mode |
Process Sampling | 10 Hz (100 ms) |
Control Characteristics |
|
Setpoint Limits | Automatically Adjust to |
| Selected TC/RTD |
Alarms | Adjustable for High/Low; |
| Selectable Process, Deviation, |
| or Band Alarms |
Proportional Band | 1 to Span of Sensor |
Integral | 0 to 9600 Seconds |
Derivative | 0 to 2400 Seconds |
Cycle Time | 200 ms; 1 to 120 sec |
Control Hysteresis | 1 to Span of Sensor |
Autotune | Operator Initiated from |
| Front Panel |
Manual Control | Operator Initiated from |
| Front Panel |
Mechanical Characteristics |
|
Display | Dual, |
| LED display |
| Process Value: Orange |
| Setpoint Value/Menu: Green |
Numeric Range | |
1.771” x 1.771” | |
| (45 mm x 45 mm) |
Depth Behind Panel | 3.937” (100 mm) |
Front Panel Rating | NEMA 4X |
Operating Temperature | 32 to 140° F (0 to 60° C) |
Humidity Conditions | 90% R.H. max., |
| |
Parameter Retention | |
| memory |
Connections | Input and output via barrier |
| strip with locking terminals |
Contacts | Twin bifurcated |
30