Generac 005031-2 owner manual Scheduled Maintenance, Service Maintenance Interval Information

Page 24
4.10 SCHEDULED MAINTENANCE

Section 4 — Maintenance

Liquid-cooled 25 kW Generators

4.10 SCHEDULED MAINTENANCE

The following is a recommended maintenance schedule for small standby and residential generator sets. The established intervals in the schedule are the maximum recommended when the unit is used in an average service application. They will need to be decreased (performed more frequently) if the unit is used in a severe applica- tion. Use the unit hour meter or calendar time, whichever occurs first, from the previous maintenance interval to determine the next required maintenance interval.

Service Maintenance Interval Information:

The various service maintenance intervals are designated by interval numbers as follows:

1An early inspection of the generator set to insure it is ready to operate when required and to identify any poten- tial problem areas.

Performed monthly this requires approximately .5 man-hours per unit to complete.

This inspection may be performed by the end user providing the following safety steps are taken to prevent the engine from starting automatically without warning:

To prevent injury, perform the following steps in the order indicated before starting any maintenance:

Disable the generator set from starting and/or connecting to the load by setting the control panel AUTO/OFF/MANUAL switch to the OFF position.

Remove the 5 amp and 15 amp control panel fuses.

Turn off the battery charger (turn OFF utility supply to ATS).

Remove the negative battery cable.

The battery charger must be turned off BEFORE removing the battery cable to prevent an over current condition from burning out sensitive control panel components and circuits.

Following all maintenance, reverse these steps to insure the unit is returned to standby setup for normal operation when required.

2A break-in service inspection of the generator set to insure it is ready to operate and carry the load when required, and to identify any potential problem areas.

Performed ONLY ONCE following the first three months of operation after purchase of the unit and requires approximately 2.5 man-hours per unit to complete.

This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge to accomplish and should be performed only by an Authorized Service Dealer.

3An operational inspection of the generator set to insure it is ready to operate and carry the load when required, and to identify any potential problem areas.

Performed semi-annually this requires approximately 1.5 man-hours per unit to complete.

This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge to accomplish and should be performed only by an Authorized Service Dealer.

4A mid-level inspection of the generator set to insure it is ready to operate and carry the load when required, and to identify any potential problem areas.

Performed annually this requires approximately 4.0 man-hours per unit to complete.

This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge to accomplish and should be performed only by an Authorized Service Dealer.

22

Image 24
Contents SHOULD ATTEMPT INSTALLATION Liquid-cooled,Prepackaged Standby GeneratorsModel Number 005031-225kW This manual should remain with the unitAUTHORIZED SERVICE DEALER LOCATION ‹OPERATION AND MAINTENANCE‹HOW TO OBTAIN SERVICE INTRODUCTIONINTRODUCTION  GENERAL HAZARDS ELECTRICAL HAZARDSWARNING  FIRE HAZARDS  EXPLOSION HAZARDS‹STANDARDS INDEX 1.2TRANSFER SWITCH 1.1GENERATOR1.3ATS MODE AUTOMATIC OPERATION 1.4GENERATOR AC CONNECTION SYSTEMS‹1.7.1 LOW OIL PRESSURE SWITCH ‹1.7.2 HIGH COOLANT TEMPERATURE SWITCH‹1.7.3 LOW COOLANT LEVEL SWITCH Figure 1.4 - Low Oil Pressure Switch1.10 SPECIFICATIONS ‹1.7.6 LOW BATTERY‹1.8.1 UNPACKING PRECAUTIONS 1.8UNPACKING1.12RECONFIGURING THE FUEL SYSTEM FOR LP VAPOR Figure 1.8 - Reconfigure the Fuel System1.11 FUEL CONSUMPTION 1.13 ENGINE OIL RECOMMENDATIONS2.1STANDBY GENERATOR INSTALLATION 1.15 BEFORE INSTALLATION1.14 COOLANT RECOMMENDATIONS ‹2.1.1 NFPA STANDARDS2.2GENERATOR LOCATION 2.3GENERATOR MOUNTING AND SUPPORT2.4BASIC STANDBY ELECTRIC SYSTEM ‹2.1.2 OTHER PUBLISHED STANDARDS2.9USING A “GTS” TRANSFER SWITCH 2.5EMERGENCY CIRCUIT ISOLATION METHOD2.6TOTAL CIRCUIT ISOLATION METHOD 2.7GROUNDING THE GENERATOR2.10 BATTERY INSTALLATION Pos2 OFF — ATS Application‹2.10.1 VENTED BATTERIES 3.1GTS TRANSFER SWITCH ‹2.11.2 TRANSFER SWITCH2.11 PREPARATION BEFORE START-UP ‹2.11.4 GENERATOR SET LUBRICATION‹3.2.1 AUTO/OFF/MANUAL SWITCH ‹3.2.2 FAULT INDICATOR LEDS3.2CONTROL CONSOLE COMPONENTS GTS Mode Operation‹3.2.5 SET EXERCISE TIME SWITCH ‹3.2.3 15 AMP FUSE‹3.2.4 5 AMP FUSE ‹3.2.6 SYSTEM READY LED3.4ENGINE GOVERNOR GAIN ADJUSTMENTS 3.3MANUAL TRANSFER AND START-UP3.5MANUAL RETRANSFER AND SHUTDOWN Figure 3.2 - Engine Governor Adjustment3.8CONTROL BOARD DIP SWITCH SETTINGS Figure 3.3 - “Set Exercise Time” Switch3.6AUTOMATIC OPERATION 3.7WEEKLY EXERCISE CYCLE3.9VOLTAGE REGULATOR ADJUSTMENT ‹EVERY THREE MONTHS‹ONCE EVERY SIX MONTHS ‹ONCE ANNUALLY4.2EXHAUST MANIFOLD PROCEDURE 4.3INTAKE MANIFOLD PROCEDURE4.4CYLINDER HEAD PROCEDURE Figure 4.1 - Intake Manifold Installation4.8MAINTENANCE OWNER/ OPERATOR CAN PERFORM ‹4.7.2 BATTERY FLUID‹4.8.2 CHECK BATTERY 4.6OVERLOAD PROTECTION FOR‹4.8.11 CHANGING THE ENGINE AIR CLEANER Figure 4.4 - Setting the Spark Plug Gap‹4.8.7 INSPECT EXHAUST SYSTEM ‹4.8.8 CHECK FAN BELT4.9MISCELLANEOUS MAINTENANCE ‹4.9.1 CLEANING THE GENERATOR‹4.9.2 BATTERY ‹4.9.3 BATTERY MAINTENANCE4.10 SCHEDULED MAINTENANCE Service Maintenance Interval InformationTasks Level TROUBLESHOOTING POINTS PROBLEMCAUSE CORRECTIONSection 6 - Electrical Data Section 6 - Electrical Data Section 6 - Electrical Data Liquid-cooled25 kW GeneratorsSection 6 - Electrical Data Section 6 - Electrical Data Liquid-cooled25 kW GeneratorsSection 6 - Electrical Data Section 6 - Electrical Data Liquid-cooled25 kW GeneratorsSection 6 - Electrical Data Section 7 - Exploded Views and Parts Lists DESCRIPTION Mounting Base - Drawing No. 0F0104-B38 3 45 39 32 18 LATCH DETAIL Enclosure - Drawing No. 0F1645-H Section 7 - Exploded Views and Parts Lists 0F0790 Control Panel 25kW - Drawing No. 0E7615-C Section 7 - Exploded Views and Parts Lists FOR HARNESS GROUND STEPPERONLY RADIATOREngine - Drawing No. 0E9918-F COVER Fuel System - Drawing No. 0E9980-D LOCKTIGHT LEADS0F1659A Muffler - Drawing No. 0F2930-C Stepper Motor - Drawing No. 0E9979-C Radiator - Drawing No. 0E9965-F TO THERMOSTATADAPTER Section 8 - Installation Diagram YOUR WARRANTY RIGHTS AND OBLIGATIONS PURCHASER’S/OWNER’S WARRANTY RESPONSIBILITIESCALIFORNIA EMISSION CONTROL WARRANTY STATEMENT EMISSION CONTROL SYSTEM WARRANTY EMISSION RELATED PARTS INCLUDE THE FOLLOWINGWARRANTY SCHEDULE THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING