Generac 005031-2 Battery Installation, Pos2 OFF — ATS Application, ‹2.10.1 VENTED BATTERIES

Page 13
Pos2 OFF — ATS Application

Section 2 — Installation

The control board WILL monitor all engine condi- tions and shut down on all the faults listed in this document.

Pos2 OFF — ATS Application

The control board will perform all of the automatic features listed in this document.

The two-wire start connections, wires 178-183, should NOT be connected.

NOTE:

If the generator is installed in conjunction with an engineered GTS type engineered transfer switch, refer to the applicable transfer switch manual for exact operating parameters and timing sequenc- es.

2.10 BATTERY INSTALLATION

2.10 BATTERY INSTALLATION‹2.10.1 VENTED BATTERIES DANGER

Standby generators installed with automatic transfer switches will crank and start automati- cally when NORMAL (UTILITY) source voltage is removed or is below an acceptable preset level. To prevent such automatic start-up and pos- sible injury to personnel, do not connect battery cables until certain that normal source voltage at the transfer switch is correct; the generator main line circuit breaker is switched to OFF; the AUTO/OFF/MANUAL switch on the control con- sole is switched to OFF; the 15A and 5A fuses have been removed from the control console; utility fed supply to battery charger (terminals N1 and N2) is removed; and the system is ready to be placed into operation. Ensure that the 5A and 15A fuses in the control panel are removed when connecting or disconnecting battery cables.

Storage batteries give off explosive hydrogen gas. This gas can form an explosive mixture around the battery for several hours after charg- ing. The slightest spark can ignite the gas and cause an explosion. Such an explosion can shat- ter the battery and cause blindness or other injury. Any area that houses a storage battery must be properly ventilated. Do not allow smok- ing, open flame, sparks or any spark producing tools or equipment near the battery.

Battery electrolyte fluid is an extremely corro- sive sulfuric acid solution that can cause severe burns. Do not permit fluid to contact eyes, skin, clothing, painted surfaces, etc. Wear protective goggles, protective clothing and gloves when handling a battery. If fluid is spilled, flush the affected area immediately with clear water.

Liquid-cooled 25 kW Generators

Do not dispose of the battery in a fire. The bat- tery is capable of exploding.

Do not open or mutilate the battery. Released electrolyte can be toxic and harmful to the skin and eyes.

The battery represents a risk of high short circuit current. When working on the battery, always remove watches, rings or other metal objects, and only use tools that have insulated handles.

‹2.10.1 VENTED BATTERIES

The electrolyte is a dilute sulfuric acid that is harmful to the skin and eyes. It is electrically conductive and corrosive. The following proce- dures are to be observed:

Wear full eye protection and protective clothing,

Where electrolyte contacts the skin, wash it off immediately with water,

Where electrolyte contacts the eyes, flush thor- oughly and immediately with water and seek medical attention, and

Spilled electrolyte is to be washed down with an acid-neutralizing agent. A common practice is to use a solution of one pound (500 grams) bicarbon- ate of soda to one gallon (4 liters) of water. The bicarbonate of soda solution is to be added until the evidence of reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the area dried.

Lead acid batteries present a risk of fire because they generate hydrogen gas. The following pro- cedure are to be followed:

DO NOT SMOKE when near batteries,

DO NOT cause flame or spark in battery area, and

Discharge static electricity from body before touch- ing batteries by first touching a grounded metal surface.

Servicing of batteries is to be performed or super- vised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized person- nel away from batteries.

The recommended battery is Group 26, 12VDC, 550 CCA/75 AH minimum. All batteries must be at 100 percent state-of-charge before they are installed on the generator.

11

Image 13
Contents Liquid-cooled,Prepackaged Standby Generators SHOULD ATTEMPT INSTALLATIONModel Number 005031-225kW This manual should remain with the unit‹OPERATION AND MAINTENANCE AUTHORIZED SERVICE DEALER LOCATION‹HOW TO OBTAIN SERVICE INTRODUCTIONINTRODUCTION ELECTRICAL HAZARDS  GENERAL HAZARDSWARNING   EXPLOSION HAZARDS FIRE HAZARDS‹STANDARDS INDEX 1.1GENERATOR 1.2TRANSFER SWITCH1.3ATS MODE AUTOMATIC OPERATION 1.4GENERATOR AC CONNECTION SYSTEMS‹1.7.2 HIGH COOLANT TEMPERATURE SWITCH ‹1.7.1 LOW OIL PRESSURE SWITCH‹1.7.3 LOW COOLANT LEVEL SWITCH Figure 1.4 - Low Oil Pressure Switch‹1.7.6 LOW BATTERY 1.10 SPECIFICATIONS‹1.8.1 UNPACKING PRECAUTIONS 1.8UNPACKINGFigure 1.8 - Reconfigure the Fuel System 1.12RECONFIGURING THE FUEL SYSTEM FOR LP VAPOR1.11 FUEL CONSUMPTION 1.13 ENGINE OIL RECOMMENDATIONS1.15 BEFORE INSTALLATION 2.1STANDBY GENERATOR INSTALLATION1.14 COOLANT RECOMMENDATIONS ‹2.1.1 NFPA STANDARDS2.3GENERATOR MOUNTING AND SUPPORT 2.2GENERATOR LOCATION2.4BASIC STANDBY ELECTRIC SYSTEM ‹2.1.2 OTHER PUBLISHED STANDARDS2.5EMERGENCY CIRCUIT ISOLATION METHOD 2.9USING A “GTS” TRANSFER SWITCH2.6TOTAL CIRCUIT ISOLATION METHOD 2.7GROUNDING THE GENERATORPos2 OFF — ATS Application 2.10 BATTERY INSTALLATION‹2.10.1 VENTED BATTERIES ‹2.11.2 TRANSFER SWITCH 3.1GTS TRANSFER SWITCH2.11 PREPARATION BEFORE START-UP ‹2.11.4 GENERATOR SET LUBRICATION‹3.2.2 FAULT INDICATOR LEDS ‹3.2.1 AUTO/OFF/MANUAL SWITCH3.2CONTROL CONSOLE COMPONENTS GTS Mode Operation‹3.2.3 15 AMP FUSE ‹3.2.5 SET EXERCISE TIME SWITCH‹3.2.4 5 AMP FUSE ‹3.2.6 SYSTEM READY LED3.3MANUAL TRANSFER AND START-UP 3.4ENGINE GOVERNOR GAIN ADJUSTMENTS3.5MANUAL RETRANSFER AND SHUTDOWN Figure 3.2 - Engine Governor AdjustmentFigure 3.3 - “Set Exercise Time” Switch 3.8CONTROL BOARD DIP SWITCH SETTINGS3.6AUTOMATIC OPERATION 3.7WEEKLY EXERCISE CYCLE‹EVERY THREE MONTHS 3.9VOLTAGE REGULATOR ADJUSTMENT‹ONCE EVERY SIX MONTHS ‹ONCE ANNUALLY4.3INTAKE MANIFOLD PROCEDURE 4.2EXHAUST MANIFOLD PROCEDURE4.4CYLINDER HEAD PROCEDURE Figure 4.1 - Intake Manifold Installation‹4.7.2 BATTERY FLUID 4.8MAINTENANCE OWNER/ OPERATOR CAN PERFORM‹4.8.2 CHECK BATTERY 4.6OVERLOAD PROTECTION FORFigure 4.4 - Setting the Spark Plug Gap ‹4.8.11 CHANGING THE ENGINE AIR CLEANER‹4.8.7 INSPECT EXHAUST SYSTEM ‹4.8.8 CHECK FAN BELT‹4.9.1 CLEANING THE GENERATOR 4.9MISCELLANEOUS MAINTENANCE‹4.9.2 BATTERY ‹4.9.3 BATTERY MAINTENANCEService Maintenance Interval Information 4.10 SCHEDULED MAINTENANCETasks Level PROBLEM TROUBLESHOOTING POINTSCAUSE CORRECTIONSection 6 - Electrical Data Section 6 - Electrical Data Liquid-cooled25 kW Generators Section 6 - Electrical DataSection 6 - Electrical Data Liquid-cooled25 kW Generators Section 6 - Electrical DataSection 6 - Electrical Data Liquid-cooled25 kW Generators Section 6 - Electrical DataSection 6 - Electrical Data Section 7 - Exploded Views and Parts Lists Mounting Base - Drawing No. 0F0104-B DESCRIPTION38 3 45 39 32 18 LATCH DETAIL Enclosure - Drawing No. 0F1645-H Liquid-cooled25 kW Generators 0F0790 Control Panel 25kW - Drawing No. 0E7615-C Liquid-cooled25 kW Generators STEPPER FOR HARNESS GROUNDONLY RADIATOREngine - Drawing No. 0E9918-F COVER Fuel System - Drawing No. 0E9980-D LEADS LOCKTIGHT0F1659A Muffler - Drawing No. 0F2930-C Stepper Motor - Drawing No. 0E9979-C TO THERMOSTAT Radiator - Drawing No. 0E9965-FADAPTER Section 8 - Installation Diagram PURCHASER’S/OWNER’S WARRANTY RESPONSIBILITIES YOUR WARRANTY RIGHTS AND OBLIGATIONSCALIFORNIA EMISSION CONTROL WARRANTY STATEMENT EMISSION RELATED PARTS INCLUDE THE FOLLOWING EMISSION CONTROL SYSTEM WARRANTYTHIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING WARRANTY SCHEDULE