Generac 005031-2 owner manual Troubleshooting Points, Problem, Cause, Correction

Page 27
TROUBLESHOOTING POINTS

Section 5 — Troubleshooting

Liquid-cooled 25 kW Generators

TROUBLESHOOTING POINTS

PROBLEM

CAUSE

CORRECTION

Engine won’t crank.

1.

15 amp fuse blown.

1.

Replace fuse.

2.

Loose or corroded or defective

2.

Tighten, clean or replace

 

battery cables.

 

battery cables as necessary.

3.

Defective starter contactor.

3.

Replace contactor.

4.

Defective starter motor.

4.

Replace starter motor.

5.

Dead or Defective Battery.

5.

Remove, change or replace battery.

6.

5 amp fuse blown.

6.

Replace fuse.

 

 

 

 

 

Engine cranks but won't start

1.

Out of fuel.

1.

Replenish fuel.

2.

Fuel solenoid (FS) is defective

2.

Replace solenoid.

3.

Open Wire #14A from Engine Control

3.

Reconnect wire.

 

circuit board.

 

 

4.

Spark plugs defective.

4.

Clean, regap or replace plugs.

 

 

 

 

 

Engine starts hard, runs rough.

1.

Flame arrestor (air cleaner) plugged or

1.

Clean or replace as needed.

 

 

damaged.

 

 

2.

Plugged fuel line.

2.

Unclog fuel line.

3.

Defective spark plugs.

3.

Clean, regap or replace plugs.

 

 

 

 

 

Engine starts then shuts down.

1.

Engine oil level is low.

1.

Check oil and add oil as needed.

2.

Engine is overheated.

2.

Check cooling system for leaks.

3.

Defective Low Oil Pressure Switch

3.

Replace switch.

4.

Defective Coolant Temperature Switch

4.

Replace switch.

5.

Defective Control Module circuit board.

5.

Replace board.

6.

Coolant Level is Low.

6.

Repair leak - Add coolant.

7.

Defective Low Coolant Level Switch

7.

Replace Switch.

 

 

 

 

 

AUTO/OFF/MANUAL Switch at OFF,

1.

Defective AUTO/OFF/MANUAL switch

1.

Replace switch.

engine continues to run

2.

Open/disconnected wire #15A between

2.

Reconnect/close wire.

 

 

AUTO/OFF/MANUAL switch and Control

 

 

 

 

Module circuit board.

 

 

3.

Defective Control Module circuit board

3.

Replace board.

 

 

 

 

 

No AC output from generator.

1.

Main line circuit breaker open.

1.

Reset to ON or CLOSED.

2.

Circuit breakers & fuses open.

2.

Reset and replace, if necessary.

3.

Transfer switch set to NORMAL position

3.

Set to GENERATOR position.

4.

Generator internal failure.

4.

Contact an Authorized Service Dealer.

5.

Thermal circuit breaker open.

5.

Auto-reset - Wait 5 min. and attempt restart.

25

Image 27
Contents This manual should remain with the unit SHOULD ATTEMPT INSTALLATIONLiquid-cooled,Prepackaged Standby Generators Model Number 005031-225kWINTRODUCTION AUTHORIZED SERVICE DEALER LOCATION‹OPERATION AND MAINTENANCE ‹HOW TO OBTAIN SERVICEINTRODUCTION  GENERAL HAZARDS ELECTRICAL HAZARDSWARNING  FIRE HAZARDS  EXPLOSION HAZARDS‹STANDARDS INDEX 1.4GENERATOR AC CONNECTION SYSTEMS 1.2TRANSFER SWITCH1.1GENERATOR 1.3ATS MODE AUTOMATIC OPERATIONFigure 1.4 - Low Oil Pressure Switch ‹1.7.1 LOW OIL PRESSURE SWITCH‹1.7.2 HIGH COOLANT TEMPERATURE SWITCH ‹1.7.3 LOW COOLANT LEVEL SWITCH1.8UNPACKING 1.10 SPECIFICATIONS‹1.7.6 LOW BATTERY ‹1.8.1 UNPACKING PRECAUTIONS1.13 ENGINE OIL RECOMMENDATIONS 1.12RECONFIGURING THE FUEL SYSTEM FOR LP VAPORFigure 1.8 - Reconfigure the Fuel System 1.11 FUEL CONSUMPTION‹2.1.1 NFPA STANDARDS 2.1STANDBY GENERATOR INSTALLATION1.15 BEFORE INSTALLATION 1.14 COOLANT RECOMMENDATIONS‹2.1.2 OTHER PUBLISHED STANDARDS 2.2GENERATOR LOCATION2.3GENERATOR MOUNTING AND SUPPORT 2.4BASIC STANDBY ELECTRIC SYSTEM2.7GROUNDING THE GENERATOR 2.9USING A “GTS” TRANSFER SWITCH2.5EMERGENCY CIRCUIT ISOLATION METHOD 2.6TOTAL CIRCUIT ISOLATION METHOD2.10 BATTERY INSTALLATION Pos2 OFF — ATS Application‹2.10.1 VENTED BATTERIES ‹2.11.4 GENERATOR SET LUBRICATION 3.1GTS TRANSFER SWITCH‹2.11.2 TRANSFER SWITCH 2.11 PREPARATION BEFORE START-UPGTS Mode Operation ‹3.2.1 AUTO/OFF/MANUAL SWITCH‹3.2.2 FAULT INDICATOR LEDS 3.2CONTROL CONSOLE COMPONENTS‹3.2.6 SYSTEM READY LED ‹3.2.5 SET EXERCISE TIME SWITCH‹3.2.3 15 AMP FUSE ‹3.2.4 5 AMP FUSEFigure 3.2 - Engine Governor Adjustment 3.4ENGINE GOVERNOR GAIN ADJUSTMENTS3.3MANUAL TRANSFER AND START-UP 3.5MANUAL RETRANSFER AND SHUTDOWN3.7WEEKLY EXERCISE CYCLE 3.8CONTROL BOARD DIP SWITCH SETTINGSFigure 3.3 - “Set Exercise Time” Switch 3.6AUTOMATIC OPERATION‹ONCE ANNUALLY 3.9VOLTAGE REGULATOR ADJUSTMENT‹EVERY THREE MONTHS ‹ONCE EVERY SIX MONTHSFigure 4.1 - Intake Manifold Installation 4.2EXHAUST MANIFOLD PROCEDURE4.3INTAKE MANIFOLD PROCEDURE 4.4CYLINDER HEAD PROCEDURE4.6OVERLOAD PROTECTION FOR 4.8MAINTENANCE OWNER/ OPERATOR CAN PERFORM‹4.7.2 BATTERY FLUID ‹4.8.2 CHECK BATTERY‹4.8.8 CHECK FAN BELT ‹4.8.11 CHANGING THE ENGINE AIR CLEANERFigure 4.4 - Setting the Spark Plug Gap ‹4.8.7 INSPECT EXHAUST SYSTEM‹4.9.3 BATTERY MAINTENANCE 4.9MISCELLANEOUS MAINTENANCE‹4.9.1 CLEANING THE GENERATOR ‹4.9.2 BATTERYService Maintenance Interval Information 4.10 SCHEDULED MAINTENANCETasks Level CORRECTION TROUBLESHOOTING POINTSPROBLEM CAUSESection 6 - Electrical Data Section 6 - Electrical Data Liquid-cooled25 kW Generators Section 6 - Electrical DataSection 6 - Electrical Data Liquid-cooled25 kW Generators Section 6 - Electrical DataSection 6 - Electrical Data Liquid-cooled25 kW Generators Section 6 - Electrical DataSection 6 - Electrical Data Section 7 - Exploded Views and Parts Lists Mounting Base - Drawing No. 0F0104-B DESCRIPTION38 3 45 39 32 18 LATCH DETAIL Enclosure - Drawing No. 0F1645-H Liquid-cooled25 kW Generators 0F0790 Control Panel 25kW - Drawing No. 0E7615-C 0F0790 RADIATOR FOR HARNESS GROUNDSTEPPER ONLYEngine - Drawing No. 0E9918-F COVER Fuel System - Drawing No. 0E9980-D LEADS LOCKTIGHT0F1659A Muffler - Drawing No. 0F2930-C Stepper Motor - Drawing No. 0E9979-C Radiator - Drawing No. 0E9965-F TO THERMOSTATADAPTER Section 8 - Installation Diagram YOUR WARRANTY RIGHTS AND OBLIGATIONS PURCHASER’S/OWNER’S WARRANTY RESPONSIBILITIESCALIFORNIA EMISSION CONTROL WARRANTY STATEMENT EMISSION RELATED PARTS INCLUDE THE FOLLOWING EMISSION CONTROL SYSTEM WARRANTYTHIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING WARRANTY SCHEDULE