Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 Approximate Crank Cycle Times, Overspeed

Page 23

Section 2 — Operation

2.5.3.1 Approximate Crank Cycle Times

15 seconds ON

15 seconds OFF

7 seconds ON

7 seconds OFF

Repeat for 45 seconds Approximately 90 seconds total

Guardian Air-cooled Generators

2.Remote/Common Alarm – This allows for an alarm, light, horn, etc., to activate when any fault has occurred. Lines #210 (common) and #211 (normally open) provide a “closure” on common fault, which can be used for 120 volts, 10 amps maximum. See Figure 2.5.

3.Remote Not Auto – The generator will not auto- matically start during a utility failure.

2.5.4 OVERSPEED

This feature protects the generator from damage by shutting it down if it happens to run faster than the pre- set limit. This protection also prevents the generator from supplying an output that could potentially damage appliances connected to the generator circuit. The over- speed feature will activate as follows:

1.If the generator runs at 72 Hertz for five seconds, the generator will shut down.

2.If the generator reaches 75 Hertz, it will shut down instantly.

2.6ADDITIONAL GENERATOR FEATURES

2.6.1 6 KW, 8 KW AND 10 KW UNITS (NON-SA)

The standard 6 kW, 8 kW and 10 kW air-cooled Guardians offer additional features that are not factory preset:

1.Remote Start – This allows for remote starting of the generator by means of the #183 (common) and #178 (normally open) lines with the Auto/Off/Manual switch set to AUTO. Closure of the circuit starts the unit; opening of the circuit stops the unit. See Figure 2.5.

NOTE:

This function will work ONLY with the unit in the AUTO mode.

Figure 2.5 – Remote Start/Alarm Options

2.6.2 SOUND ATTENUATED UNITS

Model 00844 of the sound attenuated air-cooled Guardians offers additional features that are not factory preset (see Figure 2.6):

1.Remote Start – This allows for remote starting of the generator by means of the #183 and #178 lines with the Auto/Off/Manual switch set to AUTO.

2.Engine Run Signal – The engine run signal is con- trolled by the #14 line. The “volt free” engine run signal relay closes when the #14 line is “hot.”

3.Automatic Transfer Switch (ATS) in Emergency – For this to be active, a microswitch on the transfer switch sends a signal along the #231 line to close the “volt free” contact relay.

4.Shutdown Fault – This signal is controlled by the main printed circuit board along the #229 line. When a common fault occurs (low oil pressure, high temperature, overspeed, overcrank), the control board will send a signal along the #229 line to close the "volt free" contact relay.

Figure 2.6 – Remote Alarms

–Type 14 AWG wire is recommended.

–These options should be wired to the unit by a qualified electrician or Generac/Guardian Authorized Dealer.

Generac® Power Systems, Inc. 21

Image 23
Contents Installation, Start-up and Adjustment Manual Authorized Dealer Location Operation and MaintenanceHOW to Obtain Service IntroductionIntroduction Inside Front Cover InstallationPost-installationStart-up Adjustments TroubleshootingGeneral Hazards Electrical Hazards Unpacking Introduction to InstallationGaseous Fuel System Before InstallationLifting the Generator Engine OIL RecommendationsFuel Pipe Sizing Reconfiguring the Fuel SystemFuel Consumption Generator Transfer SwitchLocation and Mounting Installation Installation Generator Mounting Dimensions Sound Attenuated Total Circuit Isolation Method Emergency Circuit Isolation MethodSound Attenuated Units Wiring Interconnections11.1 6 KW, 8 KW and 10 KW Units NON-SA Installation Generators and GTS Transfer Switches Grounding the Generator Adapting THREE-PHASE Transfer SwitchBattery Fuse Post Installation InspectionBattery Installation OFF Position Using the AUTO/OFF/MANUALAutomatic Transfer Operation Auto PositionManual Transfer Operation Sequence Automatic OperationProtection Systems Transfer Back to Utility Power SourceLOW OIL Pressure Switch High Temperature Switch1 6 KW, 8 KW and 10 KW Units NON-SA Approximate Crank Cycle TimesOverspeed Generator Tests Under Load Check Transfer Switch OperationBefore Initial START-UP Electrical ChecksChecking Automatic Operation Adjusting the Load Block2 8 KW and 10 KW Units NON-SA Engine Governor Adjustment1 6 KW Units NON-SA Overspeed Adjustment Voltage Regulator Adjustment10.1 6 KW, 8 KW and 10 KW Units NON-SA Setting the Exercise TimerProblem Cause Correction Troubleshooting GuideInstallation Checklist Guardian Air-cooled Generators Generac Power SYSTEMS, INC