Section 3 — Post-installation Start-up Adjustments

Guardian Air-cooled Generators

3.7ENGINE GOVERNOR ADJUSTMENT

If both AC frequency and voltage are correspondingly high or low, adjust the engine governor as follows:

3.7.1 6 KW UNITS (NON-SA)

1.Loosen the governor clamp bolt (Figure 3.1).

2.Push the spring end of the governor lever clock- wise to the wide open throttle position of the lever.

Hold the governor lever at wide open throttle and, with a pair of pliers, rotate the governor shaft fully clockwise.

While holding the governor shaft fully clockwise and the governor lever at wide open throttle, tighten the governor clamp bolt to 70 inch- pounds (8 N-m).

3.Start the engine; let it stabilize and warm up at no-load.

4.Turn the adjuster nut to obtain a frequency read- ing of 62 Hertz.

5.Determine if the governor spring is properly located in the slot of the governor lever as follows:

If droop is excessive, move the governor spring down one slot on the lever.

For greater stability, move the governor spring up one slot on the lever.

6.After repositioning the spring on a lever slot, recheck the frequency reading and, if necessary, readjust the adjuster nut to obtain 62 Hertz at no-load.

7.When frequency is correct at no-load, check the AC voltage reading. If voltage is incorrect, the volt- age regulator may require adjustment.

Figure 3.1 – 6 kW

Engine Governor Adjustment

3.7.2 8 KW AND 10 KW UNITS (NON-SA)

1.Loosen the governor clamp bolt (Figure 3.2).

2.Push the spring end of the governor lever clock- wise to the wide open throttle position of the lever.

Hold the governor lever at wide open throttle and, with a screwdriver, rotate the governor shaft fully clockwise.

Before tightening, verify that the governor lever is pushed all the way onto the governor shaft.

While holding the governor shaft fully clockwise and the governor lever at wide open throttle, tighten the governor clamp bolt to 70 inch- pounds (8 N-m).

3.Start the engine; let it stabilize and warm up at no-load.

4.Turn the speed adjust nut to obtain a frequency reading of 62 Hertz.

5.When frequency is correct at no-load, check the AC voltage reading. If voltage is incorrect, the volt- age regulator may require adjustment.

Figure 3.2 – 8 kW and 10 kW

Engine Governor Adjustment

NOTE:

If the engine continues to run fast, use a pair of pliers to bend the bend tab clockwise to release tension on the lower governor spring.

24 Generac® Power Systems, Inc.

Image 26
Contents Installation, Start-up and Adjustment Manual Introduction Operation and MaintenanceHOW to Obtain Service Authorized Dealer LocationTroubleshooting InstallationPost-installationStart-up Adjustments Introduction Inside Front CoverGeneral Hazards Electrical Hazards Introduction to Installation UnpackingEngine OIL Recommendations Before InstallationLifting the Generator Gaseous Fuel SystemFuel Pipe Sizing Reconfiguring the Fuel SystemFuel Consumption Generator Transfer SwitchLocation and Mounting Installation Installation Generator Mounting Dimensions Sound Attenuated Emergency Circuit Isolation Method Total Circuit Isolation MethodSound Attenuated Units Wiring Interconnections11.1 6 KW, 8 KW and 10 KW Units NON-SA Installation Generators and GTS Transfer Switches Adapting THREE-PHASE Transfer Switch Grounding the GeneratorBattery Fuse Post Installation InspectionBattery Installation Auto Position Using the AUTO/OFF/MANUALAutomatic Transfer Operation OFF PositionSequence Automatic Operation Manual Transfer OperationHigh Temperature Switch Transfer Back to Utility Power SourceLOW OIL Pressure Switch Protection Systems1 6 KW, 8 KW and 10 KW Units NON-SA Approximate Crank Cycle TimesOverspeed Electrical Checks Check Transfer Switch OperationBefore Initial START-UP Generator Tests Under LoadAdjusting the Load Block Checking Automatic Operation2 8 KW and 10 KW Units NON-SA Engine Governor Adjustment1 6 KW Units NON-SA Voltage Regulator Adjustment Overspeed AdjustmentSetting the Exercise Timer 10.1 6 KW, 8 KW and 10 KW Units NON-SATroubleshooting Guide Problem Cause CorrectionInstallation Checklist Guardian Air-cooled Generators Generac Power SYSTEMS, INC