Generac 004626-1, 004373-2, 004373-2, 004626-1 owner manual Prior to Initial START-UP

Page 13

Section 2 — Installation

Guardian Liquid-cooled 40 kW Generator

2.8.1 PRIOR TO INITIAL START-UP

Prior to initially starting the generator, it must be

!properly prepared for use. Any attempt to crank or start the engine before it has been properly serviced with the recommended types and quanti- ties of engine fluids (oil, coolant, fuel, etc.) may result in an engine failure.

Before starting the generator for the first time, the installer must complete the following procedures. For follow-up maintenance information and/or service inter- vals, please refer to Section 4, “Maintenance.”

2.8.2 Transfer Switch

If this generator is used to supply power to any electri- cal system normally powered by an electric utility, the National Electrical Code requires that a transfer switch be installed. The transfer switch prevents electrical backfeed between two different electrical systems. (For additional information, see the applicable transfer switch manual for this unit.) The transfer switch, as well as the generator and other standby components, must be properly located and mounted in strict compli- ance with applicable codes, standards and regulations.

2.8.3 Fuel System

Make sure the fuel supply system to the generator (a) delivers the correct fuel at the correct pressure and (b) is properly purged and leak tested according to code. No fuel leakage is permitted. See “Specifications” (Page 6) for more information.

2.8.6 Belt Tension

Check the engine fan belt tension and condition prior to placing the unit into service and at recommended intervals. Belt tension is correct when a force of approx- imately 22 pounds (10 kg), applied midway between pulleys, deflects the belt about 3/8- to 5/8-inch (10 to 16 mm).

2.8.7 Electrical System

Make sure the generator is properly connected to an approved earth ground and/or ground rod.

Make sure the generator battery is fully charged, proper- ly installed and interconnected, and ready for use.

Check to ensure that there are no loose electrical con- nections. Restrain any loose wires to keep them clear of any moving generator set components.

2.8.8 Rodent Protection

Make sure the four 3-inch diameter cap plugs (part # 0A8785) are properly installed in the tie-down holes in the side rails of the unit’s base frame (Figure 2.3). The cap plugs are shipped in a plastic bag located in the lower connection box. These plugs are needed to pre- vent rodents from accessing the interior of the genera- tor set. On acoustic units, cap plugs also are needed to stay within noise specification limits.

Figure 2.3 - Base Frame Cap Plugs

2.8.4 Generator Set Lubrication

Check the engine crankcase oil level before operating and add oil to the proper level – the dipstick “FULL” mark. Never operate the engine with the oil level below the dipstick “ADD” mark. See “Specifications” (Page 5) and “Engine Oil Recommendations” (Page 7).

NOTE:

This engine is shipped from the manufacturer with SAE 15W-40 oil. This oil should be changed after 30 hours of operation.

2.8.5 Engine Coolant

Have the engine cooling system properly filled with the recommended coolant mixture. Check the system for leaks and other problems. See “Specifications” (Page 5) and “Coolant” (Page 7).

Generac® Power Systems, Inc. 11

Image 13
Contents Power SYSTEMS, INC Authorized Dealer Location IntroductionInstallation Safety Rules General InformationMaintenance Section Installation Drawings 56-57 Warranty Back CoverGeneral Hazards Electrical Hazards UNPACKING/INSPECTION Prepackaged Transfer SwitchGenerator Generator AC Connection SystemsMain Circuit Breaker SpecificationsEngine Protective Devices Generator and Load Compatibility Fuel Requirements RecommendationsEngine Conversion to LP GAS VaporEmissions Control System CoolantAIR Fuel Ratio Controller Basic Standby Electric System Standby Generator InstallationNfpa Standards Other Published StandardsPre-Packaged Type Switch Transfer Switch Start Signal ConnectionsGTS Type Engineered Switch Emergency Circuit Isolation MethodPreparation Before START-UP Battery InstallationVented Batteries Prior to Initial START-UP Using the AUTO/OFF/MANUAL Switch Manual Position OFF PositionAutomatic Transfer Operation Sequence of Automatic OperationChecking the Engine OIL Level Weekly Exercise CycleChanging the Engine AIR Cleaner Oil and Filter Change ProcedureChanging the Engine OIL and Filter Engine Oil RecommendationsSpark Plugs Battery MaintenanceCleaning the Generator Miscellaneous MaintenanceOverload Protection for Engine DC Electrical System DC FuseRemoval From Service OUT of Service ProcedureReturn To Service SYSTEM/COMPONENT Procedure Frequency Service ScheduleProblem Cause Correction Troubleshooting GuideElectrical Data Section Generac Generac Power Systems,Inc Electrical Data Electrical Data Electrical Data Wiring Diagram Customer Connection HRS Power Systems IncPart NO. QTY. Description Generators Part NO. QTY Description Part NO.QTY Description QTY Description 4640 31 33 Washer Flat 3/8-M10 Zinc Part NO.QTY. DescriptionExploded Views and Parts Lists Flywhl 4.3L GM SAE Stator Leads Scrolldetail To Engine Flywheel QTY Description Part NO. QTY Description QTY Assembly Cover AccessRadiator Copper Brass Gasket Carburetor Adaptor Gasket Carb Impco To Carburetor QTY. DescriptionSupport Solenoid NAT GAS QTY. Description To Starter Solenoid RED Black To Engine Block ALT Leads Sensing Wire Siemens FD 3 Pole QTY Description Exploded Views and Parts Lists Part NO. QTY. Description Muffler 2-1/2 INLET/OUTLET Guardian Liquid-cooled 40 kW Generators Installation Drawings 12V Battery see Note Lifting EYE Places This Warranty Shall not Apply to the Following Warranty Schedule