Section 4 — Maintenance

Guardian Liquid-cooled 40 kW Generator

4.6 COOLING SYSTEM

Figure 4.4 – Location of 15-amp Fuse

Air intake and outlet openings in the generator compart- ment must be open and unobstructed for continued prop- er operation. This includes such obstructions as high grass, weeds, brush, leaves and snow.

Without sufficient cooling and ventilating air flow, the engine/generator quickly overheats, which causes it to shut down.

The exhaust system of this product gets extremely hot and remains hot after shutdown. High grass, weeds, brush, leaves, etc. must remain clear of the exhaust. Such materials may ignite and burn from the heat of the exhaust system.

15

4.7OVERLOAD PROTECTION FOR ENGINE DC ELECTRICAL SYSTEM

Engine cranking, start-up and running are controlled by a solid-state engine controller circuit board. Battery voltage is delivered to that circuit board via a 15-amp fuse. These overcurrent protection devices will open if the circuit is overloaded.

If a circuit breaker opens or a fuse element melts, you should find the cause of the overload before resetting the circuit breaker or replacing the fuse.

4.8 DC FUSE

The generator panel’s 15-amp AGC fuse (Figure 4.4) pro- tects the DC control circuit against overload. The fuse is wired in series with the battery output lead to the panel. If the fuse element has melted open, cranking or starting the engine cannot occur. Replace the fuse using only an identical 15-amp AGC replacement.

4.9 ENGINE COOLANT

Check the coolant level in the coolant recovery bottle.

Add the recommended coolant mixture as necessary. See Section 1.10 on Page 7.

Periodically remove the radiator pressure cap to make sure the coolant recovery system is functioning properly. Coolant should be at the bottom of the radia- tor filler neck. If the coolant level is low, inspect the gasket in the radiator pressure cap. Replace the cap, if necessary. To have the pressure cap tested, contact a Generac/Guardian Authorized Dealer. Inspect the cool- ing system and coolant recovery system for leaks.

4.10 MISCELLANEOUS MAINTENANCE

￿4.10.1 Cleaning the Generator

Keep the generator as clean and as dry as possible. Dirt and moisture that accumulate on internal generator windings have an adverse effect on insulation resist- ance.

Periodically, clean the generator’s exterior surfaces. A soft brush may be used to loosen caked on dirt. Use a vacuum system or dry, low pressure air to remove any accumulations of dirt. The generator is housed inside an all-weather enclosure; clean the enclosure with a soft, damp cloth or sponge and water.

Once each year, have the generator cleaned and inspect- ed by a Generac/Guardian Authorized Dealer. Service technicians will use dry, low pressure air to clean inter- nal windings. Parts inside the control console should be cleaned and inspected at this time as well.

Finally, have the insulation resistance of stator and rotor windings checked. If insulation resistances are excessive- ly low, the generator may require drying.

Generac® Power Systems, Inc. 17

Image 19
Contents Power SYSTEMS, INC Authorized Dealer Location IntroductionSection Installation Drawings 56-57 Warranty Back Cover Safety Rules General InformationInstallation MaintenanceGeneral Hazards Electrical Hazards Generator AC Connection Systems Prepackaged Transfer SwitchUNPACKING/INSPECTION GeneratorMain Circuit Breaker SpecificationsEngine Protective Devices Conversion to LP GAS Vapor Fuel Requirements RecommendationsGenerator and Load Compatibility EngineEmissions Control System CoolantAIR Fuel Ratio Controller Other Published Standards Standby Generator InstallationBasic Standby Electric System Nfpa StandardsEmergency Circuit Isolation Method Transfer Switch Start Signal ConnectionsPre-Packaged Type Switch GTS Type Engineered SwitchPreparation Before START-UP Battery InstallationVented Batteries Prior to Initial START-UP Using the AUTO/OFF/MANUAL Switch Sequence of Automatic Operation OFF PositionManual Position Automatic Transfer OperationChecking the Engine OIL Level Weekly Exercise CycleEngine Oil Recommendations Oil and Filter Change ProcedureChanging the Engine AIR Cleaner Changing the Engine OIL and FilterSpark Plugs Battery MaintenanceDC Fuse Miscellaneous MaintenanceCleaning the Generator Overload Protection for Engine DC Electrical SystemRemoval From Service OUT of Service ProcedureReturn To Service SYSTEM/COMPONENT Procedure Frequency Service ScheduleProblem Cause Correction Troubleshooting GuideElectrical Data Section Generac Generac Power Systems,Inc Electrical Data Electrical Data Electrical Data Wiring Diagram Customer Connection HRS Power Systems IncPart NO. QTY. Description Generators Part NO. QTY Description Part NO.QTY Description QTY Description 4640 31 33 Washer Flat 3/8-M10 Zinc Part NO.QTY. DescriptionExploded Views and Parts Lists Flywhl 4.3L GM SAE Stator Leads Scrolldetail To Engine Flywheel QTY Description Part NO. QTY Description QTY Assembly Cover AccessRadiator Copper Brass Gasket Carburetor Adaptor Gasket Carb Impco To Carburetor QTY. DescriptionSupport Solenoid NAT GAS QTY. Description To Starter Solenoid RED Black To Engine Block ALT Leads Sensing Wire Siemens FD 3 Pole QTY Description Exploded Views and Parts Lists Part NO. QTY. Description Muffler 2-1/2 INLET/OUTLET Guardian Liquid-cooled 40 kW Generators Installation Drawings 12V Battery see Note Lifting EYE Places This Warranty Shall not Apply to the Following Warranty Schedule