Power Wiring Interconnections
All wiring must be the proper size, properly supported and protected by conduit. Utility and generator conduits must enter enclosure above circuit breaker bus in transfer switch. No conductors shall pass over top of control board. Branch circuit conduits must enter sides or bottom of enclosure adjacent to circuit breaker terminals. Do Not use large knockouts in bottom of enclosure.
warning
Low voltage wire cannot be installed in same conduit as power voltage wiring.
•Failure to follow above warning could cause personal injury, damage and/or malfunction of equipment.
Complete the following connections between the transfer switch, main distribution panel, utility power and generator, as shown below.
1.Ensure utility power is turned OFF.
2.Connect main distribution panel feeder conductors from
3.Connect utility Neutral feeder conductor to the transfer switch “NEUTRAL” terminal.
4.Connect main distribution panel “GND” to transfer switch “GROUND” terminal.
5.Connect all essential branch circuit wiring to appropriate circuit breakers in transfer switch.
6.Connect essential branch circuit Neutral conductors to transfer switch “NEUTRAL” terminals.