Hitachi SJ-PB(T) Physical interface, Profibus connectors, Pin Layout of SJ-PB Name Function

Page 10

CHAPTER 3 WIRING, CONNECTING

3.1 Physical interface

Isolation: The bus is galvanically separated from the other electronics with an on board DC/DC converter. Bus signals (A-line and B-line) are isolated via photo couplers.

Profibus-DP communication ASIC: VPC3 chip from ProfiChip.

Bus connection: The SJ-PB connects to the Profibus network with a 9-pin female DSUB connector. For the pin layout, refer to Table 3-1.

Table 3-1 Pin Layout of SJ-PB

Pin

Name

Function

Housing

Shield

Connected to PE

1

Not Connected

-

2

Not Connected

-

3

B-Line

Positive RxD/TxD according to RS 485 specification

4

RTS

Request To Send (note)

5

GND BUS

Isolated GND from RS 485 side (note)

6

+5V BUS

Isolated +5V from RS 485 side (note)

7

Not Connected

-

8

A-Line

Negative RxD/TxD according to RS 485 specification

9

Not Connected

-

(note) +5V BUS and GND BUS are used for bus termination. Some devices, like optical transceivers (RS485 to fibre optics) might require external power supply from these pins. RTS is used in some equipment to determine the direction of transmission. In standard applications only A-Line, B-Line and Shield are used.

The SJ-PBT connects to the Profibus network with a 6-poles 2pieces connector. For the pin layout, refer to Table 3-2.

 

 

Table 3-2 Pin Layout of SJ-PBT

Pin

Name

 

Function

1

B-Line(in)

 

Positive RxD/TxD according to RS 485 specification

2

A-Line(in)

 

Negative RxD/TxD according to RS 485 specification

3

Shield

 

Connected to PE

4

B-Line(out)

 

Positive RxD/TxD according to RS 485 specification

5

A-Line(out)

 

Negative RxD/TxD according to RS 485 specification

6

Shield

 

Connected to PE

3.2 Profibus connectors

On the SJ-PB, any standard Profibus connector can be used. Depending on baudrate, IP-classing and physical size of connector there are several different manufacturers and models, the prizing may also vary. For more information it is recommended to contact the manufacturer, e.g., Siemens or Erni.

SJ-PBT: In this case, the network connector is attached with SJ-PBT option board.

6

Image 10
Contents Hitachi Inverter Revision History Table Safty Precautions Otherwise, there is a danger of electric shock Otherwise, there is a danger of connecting errorOtherwise, there is a danger of electric shock and/or fire Otherwise, there is a danger of fireInspection Upon Unpacking Outline of product Appearance and Names of PartsTechnical features of Profibus-DP Profibus-DP Supported VersionProduction specification Application temperature 0 to 50 degreeInstallation of option board Mounting method of option boardPin Layout of SJ-PB Name Function Profibus connectorsPhysical interface Pin Layout of SJ-PBTWiring note PROFIBUS-DPBaudrate Profibus ConfigurationNode Address PPO-type selectionAction at communication error Setting of controlling frequency and start/stop commandsP001/P002 Action at error detection Remarks PPO- description OperatingPKW-part PCA wordRequest Function Ackn + Response ID FunctionPZD-part Control- / status word STW/ZSWStatus word Profidrive state diagram Frequency set-point/ Actual frequencyPZD word Please NoteWriting a four byte parameter Parameter ExamplesWriting a two byte array parameter Writing a two byte array parameter #2 Profidrive specific parameters Profidrive parametersFault code SJ300/L300P Fault description Parameter Malfunction codesCountermeasure for a trip state Trip displayProtection function list LED display and CountermeasureCode Size Range Magn Contents L300P Read Parameter cross-reference listCode Size Range Magn H033 ~655.35A 100 1st No load current Io of motor Auto B023 126 10~30.00 100 Constant value of Overload restriction C111 169 ~200.0% Level2 of overload restriction warning A053 215 ~5.0s Delay time of DC braking start B045 252 00,01 Code Selection of LAD stop by torque Appendix P013 329 00~03 Code Selection of method of Pulse lines input Code Size