Hitachi SJ-PB(T) instruction manual Setting of controlling frequency and start/stop commands

Page 13

CHAPTER 4 SETTING

4.2 Setting of controlling frequency and start/stop commands

The SJ300/L300P inverters can be configured to take reference set-points and commands from several different locations. Refer to the table below for information of how to configure the inverter so that the fieldbus controls frequency and the commands.

Control

Frequency Setting

Operation Setting

 

Selection - A001

Selection - A002

SJ-PB(T) controls frequency and commands

2

1

SJ-PB(T) controls frequency only

2

Not equal to 1.

SJ-PB(T) controls commands only

Not equal to 2.

1

SJ-PB(T) has no control.

Not equal to 2.

Not equal to 1.

However, since the SJ-PB(T) module uses the “Terminal” to give commands and “Operator” to give references to the inverter certain steps must be taken in order to be able to control the inverter manually (not from fieldbus). Study the table below to see how the control word bits shall be set to accomplish control from fieldbus and from the user.

Controlling the inverter with

Control word bit settings

A001

= 2

(Operator),

 

 

 

A002

= 1

(Terminal).

10

12

13

SJ-PB(T) controls frequency and commands

1

0

0

SJ-PB(T) controls frequency only*

1

1

0

SJ-PB(T) controls commands only

1

0

1

SJ-PB(T) has no control.

1

1

1

0

-

-

 

 

 

from the “Terminal” input when a SJ-PB(T) is present in the option slot. In order to do this, bit ten in the Control Word shall be set to zero. That is, by setting A001=2, A002=1, and control word bit 10=0 it is possible to control the inverter with the terminal while giving frequency reference from the fieldbus.

*Please note that when frequency reference is controlled from the fieldbus and commands from another location (such as “Terminal”) the direction of the motor must be controlled from the command source (Reverse/Forward command). In this case changing the sign of reference value cannot control the direction of the motor.

4.3 Action at communication error

In case of occurring transmission errors (communication cut-off with the master), the following actions can be selected.

Depending on what option slot the option module is connected to, P001 (Option 1) or P002 (Option 2) is changed.

P001/P002

Action at error detection

Remarks

0

Inverter will trip.

Option trip E6x or E7x.

Fault can be reset either from

 

 

 

fieldbus or from keypad.

 

Continue operation

 

 

1

according to the last

-

-

 

received command.

 

 

9

Image 13
Contents Hitachi Inverter Revision History Table Safty Precautions Otherwise, there is a danger of electric shock and/or fire Otherwise, there is a danger of connecting errorOtherwise, there is a danger of electric shock Otherwise, there is a danger of fireInspection Upon Unpacking Appearance and Names of Parts Outline of productProfibus-DP Supported Version Technical features of Profibus-DPApplication temperature 0 to 50 degree Production specificationMounting method of option board Installation of option boardPhysical interface Profibus connectorsPin Layout of SJ-PB Name Function Pin Layout of SJ-PBTPROFIBUS-DP Wiring noteNode Address Profibus ConfigurationBaudrate PPO-type selectionAction at communication error Setting of controlling frequency and start/stop commandsP001/P002 Action at error detection Remarks Operating PPO- descriptionPCA word PKW-partResponse ID Function Request Function Ackn +Control- / status word STW/ZSW PZD-partStatus word Frequency set-point/ Actual frequency Profidrive state diagramPlease Note PZD wordWriting a four byte parameter Parameter ExamplesWriting a two byte array parameter Writing a two byte array parameter #2 Profidrive parameters Profidrive specific parametersMalfunction codes Fault code SJ300/L300P Fault description ParameterProtection function list Trip displayCountermeasure for a trip state LED display and CountermeasureParameter cross-reference list Code Size Range Magn Contents L300P ReadCode Size Range Magn H033 ~655.35A 100 1st No load current Io of motor Auto B023 126 10~30.00 100 Constant value of Overload restriction C111 169 ~200.0% Level2 of overload restriction warning A053 215 ~5.0s Delay time of DC braking start B045 252 00,01 Code Selection of LAD stop by torque Appendix P013 329 00~03 Code Selection of method of Pulse lines input Code Size