Hitachi SJ-PB(T) instruction manual PKW-part, PCA word

Page 15

CHAPTER5 OPERATING

5.2 PKW-part

The parameter part (PKW) is fixed to 4 words and can be used for reading and/or updating the parameters in the inverter one by one. Requests and responses is a handshake procedure and cannot be batched, meaning that if the master sends out a read/write request, it has to wait for the response, before it sends a new request.

The PKW is further divided into three parts; PKE- Parameter ID (2 bytes), IND – Sub-index (2 bytes) and PWE- Parameter value (4 bytes).

PKW

PZD

 

 

 

 

 

 

 

 

 

PKE

IND

PWE

PZD1

PZD2

 

 

 

 

 

 

 

 

 

 

 

STW

HSW

PCD3

PCD4

PCD5

PCD6

PCD7

PCD8

PCD9

PCD10

 

 

 

ZSW

HIW

 

 

 

 

 

 

 

 

PKW: Parameter ID/value.

PKE: Parameter ID.

IND: Sub-index (3rd byte, 4th byte is reserved).

PWE: Parameter value (4 bytes).

PKE handling:

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

AK

SPM

PNU

Figure 5-1 PCA word

AK: Request/response characteristics (Range 0-15)

SPM: Toggle bit for Spontaneous Messages, not used by SJ-PB(T).

PNU: Parameter number. Range 1- 418 for Hitachi specific parameters and 900-999 for Profidrive specific parameters. Please refer to chapter 3.5 for which Profidrive specific parameters that are supported.

11

Image 15
Contents Hitachi Inverter Revision History Table Safty Precautions Otherwise, there is a danger of fire Otherwise, there is a danger of connecting errorOtherwise, there is a danger of electric shock and/or fire Otherwise, there is a danger of electric shockInspection Upon Unpacking Appearance and Names of Parts Outline of productProfibus-DP Supported Version Technical features of Profibus-DPApplication temperature 0 to 50 degree Production specificationMounting method of option board Installation of option boardPin Layout of SJ-PBT Profibus connectorsPhysical interface Pin Layout of SJ-PB Name FunctionPROFIBUS-DP Wiring notePPO-type selection Profibus ConfigurationNode Address BaudrateSetting of controlling frequency and start/stop commands Action at communication errorP001/P002 Action at error detection Remarks Operating PPO- descriptionPCA word PKW-partResponse ID Function Request Function Ackn +Control- / status word STW/ZSW PZD-partStatus word Frequency set-point/ Actual frequency Profidrive state diagramPlease Note PZD wordParameter Examples Writing a four byte parameterWriting a two byte array parameter Writing a two byte array parameter #2 Profidrive parameters Profidrive specific parametersMalfunction codes Fault code SJ300/L300P Fault description ParameterLED display and Countermeasure Trip displayProtection function list Countermeasure for a trip stateParameter cross-reference list Code Size Range Magn Contents L300P ReadCode Size Range Magn H033 ~655.35A 100 1st No load current Io of motor Auto B023 126 10~30.00 100 Constant value of Overload restriction C111 169 ~200.0% Level2 of overload restriction warning A053 215 ~5.0s Delay time of DC braking start B045 252 00,01 Code Selection of LAD stop by torque Appendix P013 329 00~03 Code Selection of method of Pulse lines input Code Size