Hitachi SJ-PB(T) Trip display, Protection function list, Countermeasure for a trip state

Page 25

CHAPTER 6 COUNTERMEASURE FOR ABNORMALY

6.1 Trip display

When the inverter is in a tripped state, the inverter displays an error code (See table below). The trip history monitor (d081 to d086) also displays the same error code as the inverter.

Trip code

Inverter’s running condition of trip detected

6.2 Protection function list

The table below describes an error code for protecting the inverter and the motor.

Error Display in the table below, X is 6 (Error for option slot 1) or 7 (Error for option slot 2).

No.

Function

Error

Action

 

 

Display

 

1

Profibus communication

EX0

This error is displayed, when disconnection occurred, while

 

error

 

the inverter is operating with Profibus.

2

Inverter communication

EX9

This error is displayed, when communication timeout occurs

 

error

 

between the inverter and the option board.

With regard to the other errors except table above, refer to Inverter instruction manual chapter 4 Explanation of function.

6.3 Countermeasure for a trip state

The table below only corresponds to additional trip codes, with regard to the other countermeasures refer to Inverter instruction manual chapter 4 Explanation of function.

Trip

Name of trip

Cause

 

Conformation

Countermeasure

code

 

 

 

 

 

EX0

Profibus

Defective connector

for

Check the area of

Improve the connection and then

 

Communication

signal cable causes

connection.

reset the power supply.

 

error

connection fail.

 

 

 

 

 

Terminating resistor

is

Check the Connection

Connect the terminating Resistor

 

 

not connected.

 

 

and then reset the power supply

 

 

Wiring distance does not

Check the

Adjust the setting to the matching

 

 

much with baudrate.

 

wiring distance

Baudrate or adjust wiring distance

EX9

Inverter

Option board is

 

Check as mentioned left

Mount the option board again and

 

communication

removed.

 

 

then secure it with screws.

 

error

 

 

 

 

6.4 LED display and Countermeasure

Following states are indicated by three LED's.

LED

Color

 

Function

Countermeasure

Fieldbus

Green

Fieldbus is on-line.

-

On/Off

Red

Fieldbus is off-line.

Confirm connection fails of connector.

Fieldbus

Flash Red 1Hz

Configuration error.

Confirm setting data and send correct data.

Flash Red 2Hz

User configuration data error.

Confirm system setting and adjust adequate.

diagnosis

Flash Red 4Hz

VPC3+ initialization failed.

Need to change the SJ-PB.

 

 

Green

Serial channel status OK.

-

 

Flash Red 1Hz

Serial communication error.

Confirm cable length and connection fails of

Serial channel

 

 

 

connector. And then adjust adequate.

Red

No serial communication.

Confirm cable length and connection fails of

status

 

(Or during

initializing inverter

connector. And then adjust adequate.

 

 

data. In

this case, after

 

 

 

initializing, LED color returns to

 

 

 

green )

 

 

21

Image 25
Contents Hitachi Inverter Revision History Table Safty Precautions Otherwise, there is a danger of electric shock and/or fire Otherwise, there is a danger of connecting errorOtherwise, there is a danger of electric shock Otherwise, there is a danger of fireInspection Upon Unpacking Appearance and Names of Parts Outline of productProfibus-DP Supported Version Technical features of Profibus-DPApplication temperature 0 to 50 degree Production specificationMounting method of option board Installation of option boardPhysical interface Profibus connectorsPin Layout of SJ-PB Name Function Pin Layout of SJ-PBTPROFIBUS-DP Wiring noteNode Address Profibus ConfigurationBaudrate PPO-type selectionAction at communication error Setting of controlling frequency and start/stop commandsP001/P002 Action at error detection Remarks Operating PPO- descriptionPCA word PKW-partResponse ID Function Request Function Ackn +Control- / status word STW/ZSW PZD-partStatus word Frequency set-point/ Actual frequency Profidrive state diagramPlease Note PZD wordWriting a four byte parameter Parameter ExamplesWriting a two byte array parameter Writing a two byte array parameter #2 Profidrive parameters Profidrive specific parametersMalfunction codes Fault code SJ300/L300P Fault description ParameterProtection function list Trip displayCountermeasure for a trip state LED display and CountermeasureParameter cross-reference list Code Size Range Magn Contents L300P ReadCode Size Range Magn H033 ~655.35A 100 1st No load current Io of motor Auto B023 126 10~30.00 100 Constant value of Overload restriction C111 169 ~200.0% Level2 of overload restriction warning A053 215 ~5.0s Delay time of DC braking start B045 252 00,01 Code Selection of LAD stop by torque Appendix P013 329 00~03 Code Selection of method of Pulse lines input Code Size