CHAPTER5 OPERATING

5.3.3 PZD word 3-10

In PZD word 3-10 the user can determine which inverter parameters that should be transferred to/from the inverter every bus-cycle.

With some of the PPO types (PPO2, 4, 5) it is possible to read and write parameters cyclically. Parameter write values are placed in the PZD’s 3-10 transferred from the master to the inverter. Parameter read values are placed in the PZD’s 3-10 transferred from the inverter to the master. However, the meaning of the data transferred in PZD3-10 must be defined in some way so that it can be determined what parameters that shall be written, and also so that the data transferred from the inverter can be connected with the correct parameter.

Parameter 915 and 916 are used to determine what parameters that shall be written (915) and read (916) cyclically (parameter number as specified below, for examples of how to assign these refer to chapter 5.4.2 and 5.4.3).

Assignment of PZD write word 3-10 (PLC -> Inverter) with parameter 915:

915, sub-index 1 = Parameter number for parameter transferred in PZD3 915, sub-index 2 = Parameter number for parameter transferred in PZD4 915, sub-index 3 = Parameter number for parameter transferred in PZD5 915, sub-index 4 = Parameter number for parameter transferred in PZD6 915, sub-index 5 = Parameter number for parameter transferred in PZD7 915, sub-index 6 = Parameter number for parameter transferred in PZD8 915, sub-index 7 = Parameter number for parameter transferred in PZD9 915, sub-index 8 = Parameter number for parameter transferred in PZD10

Assignment of PZD read word 3-10 (Inverter ->PLC) with parameter 916:

916, sub-index 1 = Parameter number for parameter transferred in PZD3 916, sub-index 2 = Parameter number for parameter transferred in PZD4 916, sub-index 3 = Parameter number for parameter transferred in PZD5 916, sub-index 4 = Parameter number for parameter transferred in PZD6 916, sub-index 5 = Parameter number for parameter transferred in PZD7 916, sub-index 6 = Parameter number for parameter transferred in PZD8 916, sub-index 7 = Parameter number for parameter transferred in PZD9 916, sub-index 8 = Parameter number for parameter transferred in PZD10

Please Note:

1.PZD words 3-6 are enabled if PPO 2 or 4 is selected. PZD words 3-10 are enabled with PPO5.

2.Parameter numbers are within the range 1-418. See chapter 5 for an index of the inverter parameter numbers. If a parameter number is set to 0, the actual PZD word will be ignored.

3.Only parameters that are of size two bytes or less can be assigned as PZD objects.

16

Image 20
Contents Hitachi Inverter Revision History Table Safty Precautions Otherwise, there is a danger of connecting error Otherwise, there is a danger of electric shock and/or fireOtherwise, there is a danger of electric shock Otherwise, there is a danger of fireInspection Upon Unpacking Outline of product Appearance and Names of PartsTechnical features of Profibus-DP Profibus-DP Supported VersionProduction specification Application temperature 0 to 50 degreeInstallation of option board Mounting method of option boardProfibus connectors Physical interfacePin Layout of SJ-PB Name Function Pin Layout of SJ-PBTWiring note PROFIBUS-DPProfibus Configuration Node AddressBaudrate PPO-type selectionP001/P002 Action at error detection Remarks Setting of controlling frequency and start/stop commandsAction at communication error PPO- description OperatingPKW-part PCA wordRequest Function Ackn + Response ID FunctionPZD-part Control- / status word STW/ZSWStatus word Profidrive state diagram Frequency set-point/ Actual frequencyPZD word Please NoteWriting a two byte array parameter Parameter ExamplesWriting a four byte parameter Writing a two byte array parameter #2 Profidrive specific parameters Profidrive parametersFault code SJ300/L300P Fault description Parameter Malfunction codesTrip display Protection function listCountermeasure for a trip state LED display and CountermeasureCode Size Range Magn Contents L300P Read Parameter cross-reference listCode Size Range Magn H033 ~655.35A 100 1st No load current Io of motor Auto B023 126 10~30.00 100 Constant value of Overload restriction C111 169 ~200.0% Level2 of overload restriction warning A053 215 ~5.0s Delay time of DC braking start B045 252 00,01 Code Selection of LAD stop by torque Appendix P013 329 00~03 Code Selection of method of Pulse lines input Code Size