CHAPTER5 OPERATING

Request/Response handling

The AK portion of the PKE word defines the request/response that may be issued.

Since parameter length of the SJ300/L300P inverter may vary, parameter values are always transferred so that the least significant byte is placed in octet 8.

If the Request/Response contains array elements, the high byte (byte 3) of the IND word will carry the array sub index, low byte (byte 4) is reserved for future use.

AK content (master -> slave)

 

Request

Function

Ackn (+)

Ackn (-)

 

0

No request

0

-

 

 

1

Request parameter value

1

7

 

 

2

Change parameter value (word)

1

7/8

 

 

3

Change parameter value (long word)

2

7/8

 

 

4

Request description element (note)

3

7

 

 

5

Change description element (note)

3

7

 

 

6

Request parameter value (array)

4

7

 

 

7

Change parameter value (array word)

4

7/8

 

 

8

Change parameter value (array long word) (note)

5

7/8

 

 

9

Request number of array elements

6

7

 

AK content (Slave -> master)

 

 

 

 

Response ID

Function

 

 

 

 

0

 

No response

 

 

 

 

1

 

Transfer parameter value (word)

 

 

 

 

2

 

Transfer parameter value (long word)

 

 

 

 

3

 

Transfer description element (note)

 

 

 

 

4

 

Transfer parameter value (array word)

 

 

 

 

5

 

Transfer parameter value (array long word) (note)

 

 

 

6

 

Request number of array elements

 

 

 

 

7

 

Request rejected, followed by fault code (in PWE part).

 

 

 

 

 

0

= Non-admissible parameter number

 

 

 

 

 

 

1

= Parameter value cannot be changed

 

 

 

 

 

 

2

= Upper or lower limit exceeded

 

 

 

 

 

 

3

= Erroneous sub-index

 

 

 

 

 

 

4

= No array

 

 

 

 

 

 

5

= Incorrect data type

 

 

 

 

 

 

7

= Descriptive element cannot be changed

 

 

 

 

 

 

9

= Descriptive data not available

 

 

 

 

 

 

11 = No parameter change rights

 

 

 

 

 

 

17 = Task cannot be executed due to operating status

 

 

 

 

 

102= Task cannot be executed due to communication error.

 

 

 

 

 

106 = Illegal Task, Task ID not allowed.

 

 

 

 

 

 

18 = Other

 

 

 

 

8

 

No parameter change rights by PKW interface

 

 

 

 

9

 

Parameter data signal (word) (note)

 

 

 

 

10

 

Parameter data signal (double word) (note)

 

 

 

If the inverter rejects a request from the master, the AK word in the PPO-read will indicate this by assuming value 7 or 8. The describing fault number will be found in the PWE part.

(note) Not supported by the SJ-PB(T) option board.

12

Image 16
Contents Hitachi Inverter Revision History Table Safty Precautions Otherwise, there is a danger of connecting error Otherwise, there is a danger of electric shock and/or fireOtherwise, there is a danger of electric shock Otherwise, there is a danger of fireInspection Upon Unpacking Outline of product Appearance and Names of PartsTechnical features of Profibus-DP Profibus-DP Supported VersionProduction specification Application temperature 0 to 50 degreeInstallation of option board Mounting method of option boardProfibus connectors Physical interfacePin Layout of SJ-PB Name Function Pin Layout of SJ-PBTWiring note PROFIBUS-DPProfibus Configuration Node AddressBaudrate PPO-type selectionAction at communication error Setting of controlling frequency and start/stop commandsP001/P002 Action at error detection Remarks PPO- description OperatingPKW-part PCA wordRequest Function Ackn + Response ID FunctionPZD-part Control- / status word STW/ZSWStatus word Profidrive state diagram Frequency set-point/ Actual frequencyPZD word Please NoteWriting a four byte parameter Parameter ExamplesWriting a two byte array parameter Writing a two byte array parameter #2 Profidrive specific parameters Profidrive parametersFault code SJ300/L300P Fault description Parameter Malfunction codesTrip display Protection function listCountermeasure for a trip state LED display and CountermeasureCode Size Range Magn Contents L300P Read Parameter cross-reference listCode Size Range Magn H033 ~655.35A 100 1st No load current Io of motor Auto B023 126 10~30.00 100 Constant value of Overload restriction C111 169 ~200.0% Level2 of overload restriction warning A053 215 ~5.0s Delay time of DC braking start B045 252 00,01 Code Selection of LAD stop by torque Appendix P013 329 00~03 Code Selection of method of Pulse lines input Code Size