Chapter 2 Installation

Chapter 2 Installation

2.1Installation Preparation

2.1.1Environmental Conditions

Make sure the following environmental conditions are satisfied when selecting the installation site:

Table 2-1 Environmental conditions in power room

Environmental conditions

Recommended range

 

-5~50°C (If ambient temperature > 45°C, for the cabinet with

Ambient temperature

400mm depth, it should demount the front door of cabinet to

 

ensure the normal operation of the system.)

 

 

Humidity

≤90%RH, non-condensing

Dust

≤1mg/m3

 

 

Sunlight

No direct sunlight

Corrosives

No pollutants, such as salt, acid, and smoke, etc.

Shake

≤1.5m/s2

 

 

Insects, pests, and termites

None

Mildew

None

Moisture

Water proof

 

 

Fire protection

No flammable on the top/bottom of the cabient.

The DC Power system will be damaged if dust or sand accumulates in it. The following measures are recommended for dusty environment:

1.The system should be installed in an airtight and air-conditioned power room. The air-conditioner filter should be well serviced without being obstructed. To reduce the dust in the power room, un-attendance in the power room is recommended.

2.The air filter should be cleaned periodically.

3.The product should be installed on a cement ground.

2.1.2Power Supply

AC power supply for communication uses AC mains as its main power source. Backup batteries and generator should be configured according to the actual power supply situation. The AC power supply system composed of AC mains and generator should adopt centralized power supply mode to supply power, while low

ACTURA Flex 48330 Power System User Manual

Image 22 Contents
Version V1.0 Revision date May 20 31011084Safety Precautions Electrical SafetyBattery Special Safe Requirements of This Equipment OthersContents System Settings Alarm Settings TestingTemperature Compensation Coefficient Parameters Routine MaintenanceDaily Inspection Replacement Appendix15 Value description of AC settings Changing audible/visual alarm and alarm call back planFunctions of SCU keys Figure List Page Abbreviation FeaturesSystem Description IntroductionSystem Configuration Outline of the DC Power System is illustrated in FigureConfiguration Cabinet dimension % 0.6 % 0.6 m % 0.6 % 0.4 m Configurations of Actura Flex 48330 Power SystemSCU BCU Rectifier Shelf ComponentsOutline Connector board Dimension of Rectifier Shelf are given in TableDimensions of rectifier shelf Manufacture type Wmm ×Dmm ×HmmDimensions RectifierMulti-Communication mode Function of indicatorsDimension H % W % D132mm % 85mm % 287mm Weight 0.76kg 3 SCUAlarm category settings for dry contact output Functions fulfilled by SCU and MC Level Authority Default password Password protection for important operations Authority and default password Multi-Function Unit MFUAlarm output Battery Connection Unit BCUConfiguration of MFU Component Description0m % 0.6m % 0.6m cabinet BCU configurationSystem Cabinet 0m % 0.6m % 0.4m cabinetPower Supply InstallationInstallation Preparation Environmental conditions in power roomSite Survey Tools & MaterialUnpacking Installation on the floor Installation ProceduresCabinet Installation Drill reserve holesInstalling expansive pipe Connection requirements External Electrical Connection InterfaceConnection Of Input Cables AC input modesConnection of input terminals Different cable connection modesConnection of single-phase AC power input Connection Of Load Cables Configuration number of load MCBs and battery MCBsBusbar type Max. load number 12 Connector board in rectifier shelf Connection Of Communication CablesLayout Of Connector Board S6415X2 13 Layout of connector board S6415X2Interface definition of connector board S6415X2 Interface Definition Of Connector Board S6415X2Connector Pin Signal name Mark number Logic relation Pgng POWER+ Power Connection Of Temperature Sensor CablesConnector Pin Signal name Connection With ModemConnecting method Battery Installation And CablingBattery Installation Connection With Dry ContactsBattery Cable Connection Standard configuration16 Connection of battery cables Non-standard configuration 18 Negative battery cables connection in BCUParallel Connection Of Cabinets DC/Parallel connectionsStartup Check the DC Power System according to -1 before startupSystem checklist before startup Checking Before StartupParameters Configuration Startup ProcessTesting Rectifier TestingTesting MFU Testing SCUBCU Test Battery Breaker TestLoad Breaker Test Operation Panel Functions of LED indicatorsOperating SCU Functions of SCU keysOperation Procedures First system information page appearsQuerying System Status First Page Of System InformationBattery information Other System Information ScreenBC prompt and temperature information AC informationQuerying Rectifier Status Querying Alarms And Setting Alarm Plans Querying Active AlarmQuery Alarm History Alarm History Alarm Type Table Alarm type tableLlvd BlvdChapter Operating SCU Serial Alarm Description Default Setting Alarm Type For Dry Contacts Changing Audible/Visual Alarm And Alarm Call Back PlanChanging Alarm Types Of Dry Contacts Changing audible/visual alarm and alarm call back planOptional alarm types Alarm type RemarkSet the Alarm Names Through PLC Function PLC SN and Alarm Logic matrix used for configuring 8 dry contactsExample of PLC setting Alarm Remark DescriptionAlarm Remark Description PLCMaintenance Llvd BlvdOperating SCU Parameter Setting Method Setting System ParametersPress ESC to return to the menu of higher level Password levels and authorities Level AuthorityBatt. Selection First page of the Batt. Selection is shown belowLVD Parameter Description Charging Management Parameters There are 6 related pages, as shown belowOperating SCU BC/FC switchover diagram is shown below Parameter Range Default Value description12 Charging management parameter value description Battery Test Parameters There are 7 related pages, as shown belowSchematic diagram of the test function is shown below 13 Value description of the battery test parametersValue description of the parameters is listed below Temperature Compensation Coefficient Parameters First page of the setting interface is shown belowAC Settings Configuration interface is shown belowDC Setting There are three related pages, as shown belowRect Settings 17 Value description of rectifier settingsSystem Settings There will be a prompt when resetting the system 18 Value description of system settings EEM-MModel description is shown below 48V/50A/SET/NONE 48V/30A/SET/NONEFirst page of the setting interface is show below Alarm SettingsPower system model System type 19 Relationship between system model and system type20 Value description of alarm settings Maintenance Of SCU Routine MaintenanceMaintenance Of Rectifier Maintenance Of MFUCover Plates Battery MaintenanceStore the battery in a cool dry place Storage And SupplementaryReplacement Troubleshooting TroubleshootingTroubleshooting Rectifier Symptom Cause SuggestionMains Failure Disastrous AccidentsParameter Category Appendix System Technical ParametersEMC Mtbf Appendix 2 Engineering Design Diagram Appendix 2 Engineering Design Diagram Connector Connector specs MCBAppendix 3 System Circuit Diagram Appendix 3.1 System Electric Schematic DiagramAppendix 3.2 System Wiring Diagram Appendix 3.3 MFU Electric Wiring Diagram Appendix 3.4 BCU Electric Wiring Diagram Hvsd Appendix GlossaryAbbreviation Full word LVD