Emerson 48330 user manual Connector Connector specs, Mcb

Page 91

Appendix 2 Engineering Design Diagram

81

Appendix 2.3 Engineering Design Diagram For 700mm%600mm%400mm Cabinet

Appendix 2.4 System Input And Output Connector Specs

 

Connector

 

Connector specs

AC Power

 

AC input terminal

H cable terminals, 2-4 pcs (cable section 35mm2)

 

 

1 M8 bolt

 

distribution

 

Grounding busbar

 

 

 

 

 

1 big wire connectors, (cable section 25mm2)

 

 

 

DC Power

 

Positive bus bar

4 M8blots, 6 big wire connectors, (cable section 25mm2)

 

23 small wire connectors, (cable section 16mm2)

 

 

distribution

 

 

 

 

 

Output route

MCB

H cable terminals (cable section 25mm2)

 

 

ACTURA Flex 48330 Power System User Manual

Image 91
Contents 31011084 Version V1.0 Revision date May 20Electrical Safety Safety PrecautionsBattery Others Special Safe Requirements of This EquipmentContents Routine Maintenance TestingTemperature Compensation Coefficient Parameters System Settings Alarm SettingsAppendix Daily Inspection Replacement15 Value description of AC settings Changing audible/visual alarm and alarm call back planFunctions of SCU keys Figure List Page Introduction FeaturesSystem Description AbbreviationOutline of the DC Power System is illustrated in Figure System ConfigurationConfiguration Cabinet dimension % 0.6 % 0.6 m % 0.6 % 0.4 m Configurations of Actura Flex 48330 Power SystemSCU BCU Rectifier Shelf ComponentsOutline Manufacture type Wmm ×Dmm ×Hmm Dimension of Rectifier Shelf are given in TableDimensions of rectifier shelf Connector boardRectifier Dimensions3 SCU Function of indicatorsDimension H % W % D132mm % 85mm % 287mm Weight 0.76kg Multi-Communication modeFunctions fulfilled by SCU and MC Alarm category settings for dry contact outputMulti-Function Unit MFU Password protection for important operationsAuthority and default password Level Authority Default passwordComponent Description Battery Connection Unit BCUConfiguration of MFU Alarm output0m % 0.6m % 0.4m cabinet BCU configurationSystem Cabinet 0m % 0.6m % 0.6m cabinetEnvironmental conditions in power room InstallationInstallation Preparation Power SupplyTools & Material Site SurveyUnpacking Drill reserve holes Installation ProceduresCabinet Installation Installation on the floorInstalling expansive pipe AC input modes External Electrical Connection InterfaceConnection Of Input Cables Connection requirementsDifferent cable connection modes Connection of input terminalsConnection of single-phase AC power input Connection Of Load Cables Configuration number of load MCBs and battery MCBsBusbar type Max. load number Connection Of Communication Cables 12 Connector board in rectifier shelf13 Layout of connector board S6415X2 Layout Of Connector Board S6415X2Interface definition of connector board S6415X2 Interface Definition Of Connector Board S6415X2Connector Pin Signal name Mark number Logic relation Connection With Modem Connection Of Temperature Sensor CablesConnector Pin Signal name Pgng POWER+ PowerConnection With Dry Contacts Battery Installation And CablingBattery Installation Connecting methodStandard configuration Battery Cable Connection16 Connection of battery cables 18 Negative battery cables connection in BCU Non-standard configurationDC/Parallel connections Parallel Connection Of CabinetsChecking Before Startup Check the DC Power System according to -1 before startupSystem checklist before startup StartupStartup Process Parameters ConfigurationTesting SCU TestingTesting MFU Testing RectifierBCU Test Battery Breaker TestLoad Breaker Test Functions of SCU keys Functions of LED indicatorsOperating SCU Operation PanelFirst system information page appears Operation ProceduresFirst Page Of System Information Querying System StatusOther System Information Screen Battery informationAC information BC prompt and temperature informationQuerying Rectifier Status Querying Active Alarm Querying Alarms And Setting Alarm PlansQuery Alarm History Alarm History Alarm type table Alarm Type TableBlvd LlvdChapter Operating SCU Serial Alarm Description Default Changing audible/visual alarm and alarm call back plan Changing Audible/Visual Alarm And Alarm Call Back PlanChanging Alarm Types Of Dry Contacts Setting Alarm Type For Dry ContactsAlarm type Remark Optional alarm typesSet the Alarm Names Through PLC Function Alarm Remark Description Logic matrix used for configuring 8 dry contactsExample of PLC setting PLC SN and AlarmPLC Alarm Remark DescriptionLlvd Blvd MaintenanceOperating SCU Parameter Setting Method Setting System ParametersPress ESC to return to the menu of higher level Level Authority Password levels and authoritiesFirst page of the Batt. Selection is shown below Batt. SelectionLVD Parameter Description There are 6 related pages, as shown below Charging Management ParametersOperating SCU BC/FC switchover diagram is shown below Parameter Range Default Value description12 Charging management parameter value description There are 7 related pages, as shown below Battery Test ParametersSchematic diagram of the test function is shown below 13 Value description of the battery test parametersValue description of the parameters is listed below First page of the setting interface is shown below Temperature Compensation Coefficient ParametersConfiguration interface is shown below AC SettingsThere are three related pages, as shown below DC Setting17 Value description of rectifier settings Rect SettingsSystem Settings There will be a prompt when resetting the system EEM-M 18 Value description of system settings48V/50A/SET/NONE 48V/30A/SET/NONE Model description is shown below19 Relationship between system model and system type Alarm SettingsPower system model System type First page of the setting interface is show below20 Value description of alarm settings Maintenance Of MFU Routine MaintenanceMaintenance Of Rectifier Maintenance Of SCUStorage And Supplementary Battery MaintenanceStore the battery in a cool dry place Cover PlatesReplacement Symptom Cause Suggestion TroubleshootingTroubleshooting Rectifier TroubleshootingDisastrous Accidents Mains FailureParameter Category Appendix System Technical ParametersEMC Mtbf Appendix 2 Engineering Design Diagram Appendix 2 Engineering Design Diagram MCB Connector Connector specsAppendix 3.1 System Electric Schematic Diagram Appendix 3 System Circuit DiagramAppendix 3.2 System Wiring Diagram Appendix 3.3 MFU Electric Wiring Diagram Appendix 3.4 BCU Electric Wiring Diagram LVD Appendix GlossaryAbbreviation Full word Hvsd