Chapter 5 Operating SCU | 65 |
5.7.9Rect Settings
1.There are three related pages, as shown below:
Rect Over Volt:
59.0V
Default Volt:
42.0V
N
8s
Fan Speed
Full Speed
HVSD Time:
300s
Use “ ” or “ ” to select one page or one of the parameters, and “ ” or “ ” to select the parameter value. Press “ENT” to confirm and save.
2. The value description of the parameters is listed below:
Table 5-17 Value description of rectifier settings
| Parameter |
| Range |
| Default |
| Value description | ||
|
|
|
|
|
|
| The rectifier over voltage alarm will be |
|
|
| Rect Over Volt | 56V ~ 59V |
| 59V |
| raised when the rectifier output voltage is |
| The “Default Volt” must be | |
|
|
|
|
|
|
| higher than the “Rect Over Volt” |
| lower than the “Rect Over Volt” |
|
|
|
|
|
|
|
|
| |
| Default Volt | 48V ~ 58V |
| 53.5V |
|
|
|
| |
|
|
|
|
|
|
|
|
| |
| Walkin Enabled |
| Y, N |
| N |
| The output soft start function means the | rectifier voltage will rise from 0V | |
|
|
|
|
|
|
| to the “Default Volt” after the “Walkin Time” |
| |
| Walkin Time |
| 8s ~ 128s |
| 10s |
|
| ||
|
|
|
|
|
|
| |||
|
|
| Full Speed, |
| Half | When set to “Half Speed”, the rectifier will regulate the fan speed | |||
| Fan Speed |
|
| according to the temperature. When set to “Full Speed”, the fan will | |||||
|
| Half Speed |
| speed | |||||
|
|
|
| operate at full speed |
| ||||
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| The rectifier will shut off automatically upon | ||
|
|
|
|
|
|
| a certain delay to see whether it is still | ||
| HVSD Time | 50s ~ 300s |
| 300s |
| through the parameter “HVSD Time”. If the rectifier’s output voltage is | |||
|
|
|
|
|
|
| normal within the delay, the rectifier is regarded normal; otherwise, the | ||
|
|
|
|
|
|
| rectifier will be locked out and | ||
|
|
|
|
|
|
|
|
|
|
ACTURA Flex 48330 Power System User Manual