Page 75

Chapter 5 Operating SCU

65

5.7.9Rect Settings

1.There are three related pages, as shown below:

Rect Over Volt:

59.0V

Default Volt:

42.0V

Walk-in Enabled

N

Walk-in Time:

8s

Fan Speed

Full Speed

HVSD Time:

300s

Use “ ” or “ ” to select one page or one of the parameters, and “ ” or “ ” to select the parameter value. Press “ENT” to confirm and save.

2. The value description of the parameters is listed below:

Table 5-17 Value description of rectifier settings

 

Parameter

 

Range

 

Default

 

Value description

 

 

 

 

 

 

 

The rectifier over voltage alarm will be

 

 

 

Rect Over Volt

56V ~ 59V

 

59V

 

raised when the rectifier output voltage is

 

The “Default Volt” must be

 

 

 

 

 

 

 

higher than the “Rect Over Volt”

 

lower than the “Rect Over Volt”

 

 

 

 

 

 

 

 

 

 

Default Volt

48V ~ 58V

 

53.5V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Walkin Enabled

 

Y, N

 

N

 

The output soft start function means the

rectifier voltage will rise from 0V

 

 

 

 

 

 

 

to the “Default Volt” after the “Walkin Time”

 

 

Walkin Time

 

8s ~ 128s

 

10s

 

 

 

 

 

 

 

 

 

 

 

 

Full Speed,

 

Half

When set to “Half Speed”, the rectifier will regulate the fan speed

 

Fan Speed

 

 

according to the temperature. When set to “Full Speed”, the fan will

 

 

Half Speed

 

speed

 

 

 

 

operate at full speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The rectifier will shut off automatically upon over-voltage, and restart after

 

 

 

 

 

 

 

a certain delay to see whether it is still over-voltage then. That delay is set

 

HVSD Time

50s ~ 300s

 

300s

 

through the parameter “HVSD Time”. If the rectifier’s output voltage is

 

 

 

 

 

 

 

normal within the delay, the rectifier is regarded normal; otherwise, the

 

 

 

 

 

 

 

rectifier will be locked out and auto-restart function will be disabled

 

 

 

 

 

 

 

 

 

 

ACTURA Flex 48330 Power System User Manual

Image 75 Contents
31011084 Version V1.0 Revision date May 20Electrical Safety Safety PrecautionsBattery Others Special Safe Requirements of This EquipmentContents Routine Maintenance TestingTemperature Compensation Coefficient Parameters System Settings Alarm SettingsAppendix Daily Inspection ReplacementChanging audible/visual alarm and alarm call back plan 15 Value description of AC settingsFunctions of SCU keys Figure List Page Introduction FeaturesSystem Description AbbreviationOutline of the DC Power System is illustrated in Figure System ConfigurationConfigurations of Actura Flex 48330 Power System Configuration Cabinet dimension % 0.6 % 0.6 m % 0.6 % 0.4 mSCU BCU Components Rectifier ShelfOutline Manufacture type Wmm ×Dmm ×Hmm Dimension of Rectifier Shelf are given in TableDimensions of rectifier shelf Connector boardRectifier Dimensions3 SCU Function of indicatorsDimension H % W % D132mm % 85mm % 287mm Weight 0.76kg Multi-Communication modeFunctions fulfilled by SCU and MC Alarm category settings for dry contact outputMulti-Function Unit MFU Password protection for important operationsAuthority and default password Level Authority Default passwordComponent Description Battery Connection Unit BCUConfiguration of MFU Alarm output0m % 0.6m % 0.4m cabinet BCU configurationSystem Cabinet 0m % 0.6m % 0.6m cabinetEnvironmental conditions in power room InstallationInstallation Preparation Power SupplyTools & Material Site SurveyUnpacking Drill reserve holes Installation ProceduresCabinet Installation Installation on the floorInstalling expansive pipe AC input modes External Electrical Connection InterfaceConnection Of Input Cables Connection requirementsDifferent cable connection modes Connection of input terminalsConnection of single-phase AC power input Configuration number of load MCBs and battery MCBs Connection Of Load CablesBusbar type Max. load number Connection Of Communication Cables 12 Connector board in rectifier shelf13 Layout of connector board S6415X2 Layout Of Connector Board S6415X2Interface Definition Of Connector Board S6415X2 Interface definition of connector board S6415X2Connector Pin Signal name Mark number Logic relation Connection With Modem Connection Of Temperature Sensor CablesConnector Pin Signal name Pgng POWER+ PowerConnection With Dry Contacts Battery Installation And CablingBattery Installation Connecting methodStandard configuration Battery Cable Connection16 Connection of battery cables 18 Negative battery cables connection in BCU Non-standard configurationDC/Parallel connections Parallel Connection Of CabinetsChecking Before Startup Check the DC Power System according to -1 before startupSystem checklist before startup StartupStartup Process Parameters ConfigurationTesting SCU TestingTesting MFU Testing RectifierBattery Breaker Test BCU TestLoad Breaker Test Functions of SCU keys Functions of LED indicatorsOperating SCU Operation PanelFirst system information page appears Operation ProceduresFirst Page Of System Information Querying System StatusOther System Information Screen Battery informationAC information BC prompt and temperature informationQuerying Rectifier Status Querying Active Alarm Querying Alarms And Setting Alarm PlansQuery Alarm History Alarm History Alarm type table Alarm Type TableBlvd LlvdChapter Operating SCU Serial Alarm Description Default Changing audible/visual alarm and alarm call back plan Changing Audible/Visual Alarm And Alarm Call Back PlanChanging Alarm Types Of Dry Contacts Setting Alarm Type For Dry ContactsAlarm type Remark Optional alarm typesSet the Alarm Names Through PLC Function Alarm Remark Description Logic matrix used for configuring 8 dry contactsExample of PLC setting PLC SN and AlarmPLC Alarm Remark DescriptionLlvd Blvd MaintenanceOperating SCU Setting System Parameters Parameter Setting MethodPress ESC to return to the menu of higher level Level Authority Password levels and authoritiesFirst page of the Batt. Selection is shown below Batt. SelectionLVD Parameter Description There are 6 related pages, as shown below Charging Management ParametersOperating SCU Parameter Range Default Value description BC/FC switchover diagram is shown below12 Charging management parameter value description There are 7 related pages, as shown below Battery Test Parameters13 Value description of the battery test parameters Schematic diagram of the test function is shown belowValue description of the parameters is listed below First page of the setting interface is shown below Temperature Compensation Coefficient ParametersConfiguration interface is shown below AC SettingsThere are three related pages, as shown below DC Setting17 Value description of rectifier settings Rect SettingsSystem Settings There will be a prompt when resetting the system EEM-M 18 Value description of system settings48V/50A/SET/NONE 48V/30A/SET/NONE Model description is shown below19 Relationship between system model and system type Alarm SettingsPower system model System type First page of the setting interface is show below20 Value description of alarm settings Maintenance Of MFU Routine MaintenanceMaintenance Of Rectifier Maintenance Of SCUStorage And Supplementary Battery MaintenanceStore the battery in a cool dry place Cover PlatesReplacement Symptom Cause Suggestion TroubleshootingTroubleshooting Rectifier TroubleshootingDisastrous Accidents Mains FailureAppendix System Technical Parameters Parameter CategoryEMC Mtbf Appendix 2 Engineering Design Diagram Appendix 2 Engineering Design Diagram MCB Connector Connector specsAppendix 3.1 System Electric Schematic Diagram Appendix 3 System Circuit DiagramAppendix 3.2 System Wiring Diagram Appendix 3.3 MFU Electric Wiring Diagram Appendix 3.4 BCU Electric Wiring Diagram LVD Appendix GlossaryAbbreviation Full word Hvsd