Appendix 1 System Technical Parameters | 77 |
| Appendix 1 | System Technical Parameters | ||||||
|
|
|
|
|
| |||
| Parameter |
| category | Note |
| |||
|
|
| AC input | Default: 280 ! 5Vac, cofigurable through monitoring module | ||||
|
|
| alarm point |
| ||||
|
|
|
|
|
|
|
| |
|
|
|
|
| ||||
|
|
| AC input | Default: 270 ! 5Vac, 10Vac lower than the AC input | ||||
| AC input alarm and |
| recovery point |
|
|
|
| |
| protection |
|
|
|
|
|
| |
|
| AC input | Default: 180 ! 5Vac, configurable through monitoring module | |||||
|
|
| alarm point |
| ||||
|
|
|
|
|
|
|
| |
|
|
|
|
| ||||
|
|
| AC input | Default: 190 ! 5Vac, 10Vac higher than the AC input | ||||
|
|
| recovery point |
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
| DC output | Default: 59.0 ! 0.2Vdc |
|
|
| |
|
|
| protection point |
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
|
| ||||
|
|
| DC output | Default: 58.5 ! 0.2Vdc, configurable through monitoring | ||||
|
|
| alarm point |
| module |
|
|
|
|
|
|
|
| ||||
|
|
| DC output | Default: 58 ! 0.2Vdc, 0.5Vdc lower than the | ||||
|
|
| recovery point |
| alarm point |
|
|
|
|
|
|
|
| ||||
|
|
| DC output | Default: 45.0 ! 0.2Vdc, configurable through monitoring | ||||
| DC output alarm and |
| alarm point |
| module |
|
|
|
| protection |
| DC output | Default: 45.5 ! 0.2Vdc, 0.5Vdc higher than the | ||||
|
|
| recovery point |
| alarm point |
|
|
|
|
|
|
|
|
| |||
|
|
| LLVD |
| Default: 44 ! 0.2Vdc, configurable through monitoring module | |||
|
|
|
|
|
| |||
|
|
| BLVD |
| Default: 43.2 ! 0.2Vdc, configurable through monitoring | |||
|
|
|
| module |
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
|
|
| |||
|
|
| Output delay |
| Output voltage can rise slowly upon rectifier start up. The rise | |||
|
|
|
| time is configurable |
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
|
| ||||
|
|
| Fan speed adjustable | Rectifier fan speed can be set to half or full speed. | ||||
|
|
|
|
|
|
|
|
|
|
|
| CS |
| EN300386 2001, Class A |
|
|
|
|
|
| RS |
|
|
|
| |
|
|
|
|
|
|
|
| |
| EMC |
| Immunity to EFT |
|
|
| ||
|
|
| Immunity to ESD | Air discharge: 8kV. Contact discharge: 4kV. | ||||
|
|
| Immunity to Surges |
|
|
| ||
|
|
|
|
|
| |||
|
|
|
|
| The AC input side can withstand 10/700μs simulated | |||
| Lightning protection |
| At AC side |
| lightning voltage 5kV for !5 times, or 8/20μs simulated | |||
|
|
| lightning surge current 20kA for | ! | 5 times, or 8/20 | μ | ||
| features |
|
|
|
| s | ||
|
|
|
| simulated lightning surge current 40kA once. The test interval | ||||
|
|
|
|
| ||||
|
|
|
|
| is not smaller than 1 minute. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Acoustic noise |
| 55dB (A) |
|
|
|
|
|
|
|
|
| |||
|
|
|
|
| At temperature of 15°C ~ 35°C and relative humidity not | |||
| Others |
|
|
| higher than 90%RH, apply a test voltage of 500Vdc. The | |||
|
| Insulation resistance | insulation resistances between AC circuit and earth, between | |||||
|
|
|
|
| DC circuit and earth, or between AC and DC circuits are no | |||
|
|
|
|
| less than 10MΩ |
|
|
|
|
|
|
|
|
|
|
|
|
ACTURA Flex 48330 Power System User Manual