Appendix 1 System Technical Parameters

77

 

Appendix 1

System Technical Parameters

 

 

 

 

 

 

 

Parameter

 

category

Note

 

 

 

 

AC input over-voltage

Default: 280 ! 5Vac, cofigurable through monitoring module

 

 

 

alarm point

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC input over-voltage

Default: 270 ! 5Vac, 10Vac lower than the AC input

 

AC input alarm and

 

recovery point

 

over-voltage alarm point

 

 

 

 

protection

 

 

 

 

 

 

 

 

AC input under-voltage

Default: 180 ! 5Vac, configurable through monitoring module

 

 

 

alarm point

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC input under-voltage

Default: 190 ! 5Vac, 10Vac higher than the AC input

 

 

 

recovery point

 

under-voltage alarm point

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DC output over-voltage

Default: 59.0 ! 0.2Vdc

 

 

 

 

 

 

protection point

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DC output over-voltage

Default: 58.5 ! 0.2Vdc, configurable through monitoring

 

 

 

alarm point

 

module

 

 

 

 

 

 

 

 

 

 

 

DC output over-voltage

Default: 58 ! 0.2Vdc, 0.5Vdc lower than the over-voltage

 

 

 

recovery point

 

alarm point

 

 

 

 

 

 

 

 

 

 

 

DC output under-voltage

Default: 45.0 ! 0.2Vdc, configurable through monitoring

 

DC output alarm and

 

alarm point

 

module

 

 

 

 

protection

 

DC output under-voltage

Default: 45.5 ! 0.2Vdc, 0.5Vdc higher than the under-voltage

 

 

 

recovery point

 

alarm point

 

 

 

 

 

 

 

 

 

 

 

 

LLVD

 

Default: 44 ! 0.2Vdc, configurable through monitoring module

 

 

 

 

 

 

 

 

 

BLVD

 

Default: 43.2 ! 0.2Vdc, configurable through monitoring

 

 

 

 

module

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output delay

 

Output voltage can rise slowly upon rectifier start up. The rise

 

 

 

 

time is configurable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan speed adjustable

Rectifier fan speed can be set to half or full speed.

 

 

 

 

 

 

 

 

 

 

 

 

CS

 

EN300386 2001, Class A

 

 

 

 

 

 

RS

 

 

 

 

 

 

 

 

 

 

 

 

 

EMC

 

Immunity to EFT

EN61000-4-4, Level 3

 

 

 

 

 

 

Immunity to ESD

Air discharge: 8kV. Contact discharge: 4kV. EN61000-4-2

 

 

 

Immunity to Surges

EN61000-4-5, Level 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The AC input side can withstand 10/700μs simulated

 

Lightning protection

 

At AC side

 

lightning voltage 5kV for !5 times, or 8/20μs simulated

 

 

 

lightning surge current 20kA for

!

5 times, or 8/20

μ

 

features

 

 

 

 

s

 

 

 

 

simulated lightning surge current 40kA once. The test interval

 

 

 

 

 

 

 

 

 

 

is not smaller than 1 minute.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Acoustic noise

 

55dB (A)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

At temperature of 15°C ~ 35°C and relative humidity not

 

Others

 

 

 

higher than 90%RH, apply a test voltage of 500Vdc. The

 

 

Insulation resistance

insulation resistances between AC circuit and earth, between

 

 

 

 

 

DC circuit and earth, or between AC and DC circuits are no

 

 

 

 

 

less than 10MΩ

 

 

 

 

 

 

 

 

 

 

 

 

ACTURA Flex 48330 Power System User Manual

Image 87
Contents 31011084 Version V1.0 Revision date May 20Electrical Safety Safety PrecautionsBattery Others Special Safe Requirements of This EquipmentContents Routine Maintenance TestingTemperature Compensation Coefficient Parameters System Settings Alarm SettingsAppendix Daily Inspection ReplacementChanging audible/visual alarm and alarm call back plan 15 Value description of AC settingsFunctions of SCU keys Figure List Page Introduction FeaturesSystem Description AbbreviationOutline of the DC Power System is illustrated in Figure System ConfigurationConfigurations of Actura Flex 48330 Power System Configuration Cabinet dimension % 0.6 % 0.6 m % 0.6 % 0.4 mSCU BCU Components Rectifier ShelfOutline Manufacture type Wmm ×Dmm ×Hmm Dimension of Rectifier Shelf are given in TableDimensions of rectifier shelf Connector boardRectifier Dimensions3 SCU Function of indicatorsDimension H % W % D132mm % 85mm % 287mm Weight 0.76kg Multi-Communication modeFunctions fulfilled by SCU and MC Alarm category settings for dry contact outputMulti-Function Unit MFU Password protection for important operationsAuthority and default password Level Authority Default passwordComponent Description Battery Connection Unit BCUConfiguration of MFU Alarm output0m % 0.6m % 0.4m cabinet BCU configurationSystem Cabinet 0m % 0.6m % 0.6m cabinetEnvironmental conditions in power room InstallationInstallation Preparation Power SupplyTools & Material Site SurveyUnpacking Drill reserve holes Installation ProceduresCabinet Installation Installation on the floorInstalling expansive pipe AC input modes External Electrical Connection InterfaceConnection Of Input Cables Connection requirementsDifferent cable connection modes Connection of input terminalsConnection of single-phase AC power input Configuration number of load MCBs and battery MCBs Connection Of Load CablesBusbar type Max. load number Connection Of Communication Cables 12 Connector board in rectifier shelf13 Layout of connector board S6415X2 Layout Of Connector Board S6415X2Interface Definition Of Connector Board S6415X2 Interface definition of connector board S6415X2Connector Pin Signal name Mark number Logic relation Connection With Modem Connection Of Temperature Sensor CablesConnector Pin Signal name Pgng POWER+ PowerConnection With Dry Contacts Battery Installation And CablingBattery Installation Connecting methodStandard configuration Battery Cable Connection16 Connection of battery cables 18 Negative battery cables connection in BCU Non-standard configurationDC/Parallel connections Parallel Connection Of CabinetsChecking Before Startup Check the DC Power System according to -1 before startupSystem checklist before startup StartupStartup Process Parameters ConfigurationTesting SCU TestingTesting MFU Testing RectifierBattery Breaker Test BCU TestLoad Breaker Test Functions of SCU keys Functions of LED indicatorsOperating SCU Operation PanelFirst system information page appears Operation ProceduresFirst Page Of System Information Querying System StatusOther System Information Screen Battery informationAC information BC prompt and temperature informationQuerying Rectifier Status Querying Active Alarm Querying Alarms And Setting Alarm PlansQuery Alarm History Alarm History Alarm type table Alarm Type TableBlvd LlvdChapter Operating SCU Serial Alarm Description Default Changing audible/visual alarm and alarm call back plan Changing Audible/Visual Alarm And Alarm Call Back PlanChanging Alarm Types Of Dry Contacts Setting Alarm Type For Dry ContactsAlarm type Remark Optional alarm typesSet the Alarm Names Through PLC Function Alarm Remark Description Logic matrix used for configuring 8 dry contactsExample of PLC setting PLC SN and AlarmPLC Alarm Remark DescriptionLlvd Blvd MaintenanceOperating SCU Setting System Parameters Parameter Setting MethodPress ESC to return to the menu of higher level Level Authority Password levels and authoritiesFirst page of the Batt. Selection is shown below Batt. SelectionLVD Parameter Description There are 6 related pages, as shown below Charging Management ParametersOperating SCU Parameter Range Default Value description BC/FC switchover diagram is shown below12 Charging management parameter value description There are 7 related pages, as shown below Battery Test Parameters13 Value description of the battery test parameters Schematic diagram of the test function is shown belowValue description of the parameters is listed below First page of the setting interface is shown below Temperature Compensation Coefficient ParametersConfiguration interface is shown below AC SettingsThere are three related pages, as shown below DC Setting17 Value description of rectifier settings Rect SettingsSystem Settings There will be a prompt when resetting the system EEM-M 18 Value description of system settings48V/50A/SET/NONE 48V/30A/SET/NONE Model description is shown below19 Relationship between system model and system type Alarm SettingsPower system model System type First page of the setting interface is show below20 Value description of alarm settings Maintenance Of MFU Routine MaintenanceMaintenance Of Rectifier Maintenance Of SCUStorage And Supplementary Battery MaintenanceStore the battery in a cool dry place Cover PlatesReplacement Symptom Cause Suggestion TroubleshootingTroubleshooting Rectifier TroubleshootingDisastrous Accidents Mains FailureAppendix System Technical Parameters Parameter CategoryEMC Mtbf Appendix 2 Engineering Design Diagram Appendix 2 Engineering Design Diagram MCB Connector Connector specsAppendix 3.1 System Electric Schematic Diagram Appendix 3 System Circuit DiagramAppendix 3.2 System Wiring Diagram Appendix 3.3 MFU Electric Wiring Diagram Appendix 3.4 BCU Electric Wiring Diagram LVD Appendix GlossaryAbbreviation Full word Hvsd