Emerson 48330 user manual Query Alarm History

Page 51

Chapter 5 Operating SCU

41

2) If there is any alarm, the display will be like the following:

Active Alarm! 3

1 Major Alarm AC! Ph-A Failure 040412 12:30:23

The information in the active alarm information pages includes: alarm serial No., alarm level, alarm name and time (year, month, day, hour, minute and second). The alarm raising time determines the sequence it is displayed, with the latest alarm displayed first. Use “ ” or “ ” to view all active alarms.

While querying rectifier alarms, press “ ”, and the rectifier ID will be displayed, and the “Run” indicator of the corresponding rectifier will blink.

Rect ID 02030405

In the case of battery test alarm or maintenance time alarm, press “ ” to display the prompt information.

Notice:

Press ENT Clear

ESC Key Quit

In the prompt page, press “ENT” to confirm the alarm.

4.At any active alarm information page, press “ESC” repeatedly and you can return to the higher-level menus.

5.5.2Query Alarm History

1.At any system information page, press “ENT” to enter the main menu

2.Press “ ” or “ ” to select the “Status” submenu, and press “ENT” to confirm.

ACTURA Flex 48330 Power System User Manual

Image 51
Contents 31011084 Version V1.0 Revision date May 20Electrical Safety Safety PrecautionsBattery Others Special Safe Requirements of This EquipmentContents Routine Maintenance TestingTemperature Compensation Coefficient Parameters System Settings Alarm SettingsAppendix Daily Inspection ReplacementChanging audible/visual alarm and alarm call back plan 15 Value description of AC settingsFunctions of SCU keys Figure List Page Introduction FeaturesSystem Description AbbreviationOutline of the DC Power System is illustrated in Figure System ConfigurationConfigurations of Actura Flex 48330 Power System Configuration Cabinet dimension % 0.6 % 0.6 m % 0.6 % 0.4 mSCU BCU Components Rectifier ShelfOutline Manufacture type Wmm ×Dmm ×Hmm Dimension of Rectifier Shelf are given in TableDimensions of rectifier shelf Connector boardRectifier Dimensions3 SCU Function of indicatorsDimension H % W % D132mm % 85mm % 287mm Weight 0.76kg Multi-Communication modeFunctions fulfilled by SCU and MC Alarm category settings for dry contact outputMulti-Function Unit MFU Password protection for important operationsAuthority and default password Level Authority Default passwordComponent Description Battery Connection Unit BCUConfiguration of MFU Alarm output0m % 0.6m % 0.4m cabinet BCU configurationSystem Cabinet 0m % 0.6m % 0.6m cabinetEnvironmental conditions in power room InstallationInstallation Preparation Power SupplyTools & Material Site SurveyUnpacking Drill reserve holes Installation ProceduresCabinet Installation Installation on the floorInstalling expansive pipe AC input modes External Electrical Connection InterfaceConnection Of Input Cables Connection requirementsDifferent cable connection modes Connection of input terminalsConnection of single-phase AC power input Configuration number of load MCBs and battery MCBs Connection Of Load CablesBusbar type Max. load number Connection Of Communication Cables 12 Connector board in rectifier shelf13 Layout of connector board S6415X2 Layout Of Connector Board S6415X2Interface Definition Of Connector Board S6415X2 Interface definition of connector board S6415X2Connector Pin Signal name Mark number Logic relation Connection With Modem Connection Of Temperature Sensor CablesConnector Pin Signal name Pgng POWER+ PowerConnection With Dry Contacts Battery Installation And CablingBattery Installation Connecting methodStandard configuration Battery Cable Connection16 Connection of battery cables 18 Negative battery cables connection in BCU Non-standard configurationDC/Parallel connections Parallel Connection Of CabinetsChecking Before Startup Check the DC Power System according to -1 before startupSystem checklist before startup StartupStartup Process Parameters ConfigurationTesting SCU TestingTesting MFU Testing RectifierBattery Breaker Test BCU TestLoad Breaker Test Functions of SCU keys Functions of LED indicatorsOperating SCU Operation PanelFirst system information page appears Operation ProceduresFirst Page Of System Information Querying System StatusOther System Information Screen Battery informationAC information BC prompt and temperature informationQuerying Rectifier Status Querying Active Alarm Querying Alarms And Setting Alarm PlansQuery Alarm History Alarm History Alarm type table Alarm Type TableBlvd LlvdChapter Operating SCU Serial Alarm Description Default Changing audible/visual alarm and alarm call back plan Changing Audible/Visual Alarm And Alarm Call Back PlanChanging Alarm Types Of Dry Contacts Setting Alarm Type For Dry ContactsAlarm type Remark Optional alarm typesSet the Alarm Names Through PLC Function Alarm Remark Description Logic matrix used for configuring 8 dry contactsExample of PLC setting PLC SN and AlarmPLC Alarm Remark DescriptionLlvd Blvd MaintenanceOperating SCU Setting System Parameters Parameter Setting MethodPress ESC to return to the menu of higher level Level Authority Password levels and authoritiesFirst page of the Batt. Selection is shown below Batt. SelectionLVD Parameter Description There are 6 related pages, as shown below Charging Management ParametersOperating SCU Parameter Range Default Value description BC/FC switchover diagram is shown below12 Charging management parameter value description There are 7 related pages, as shown below Battery Test Parameters13 Value description of the battery test parameters Schematic diagram of the test function is shown belowValue description of the parameters is listed below First page of the setting interface is shown below Temperature Compensation Coefficient ParametersConfiguration interface is shown below AC SettingsThere are three related pages, as shown below DC Setting17 Value description of rectifier settings Rect SettingsSystem Settings There will be a prompt when resetting the system EEM-M 18 Value description of system settings48V/50A/SET/NONE 48V/30A/SET/NONE Model description is shown below19 Relationship between system model and system type Alarm SettingsPower system model System type First page of the setting interface is show below20 Value description of alarm settings Maintenance Of MFU Routine MaintenanceMaintenance Of Rectifier Maintenance Of SCUStorage And Supplementary Battery MaintenanceStore the battery in a cool dry place Cover PlatesReplacement Symptom Cause Suggestion TroubleshootingTroubleshooting Rectifier TroubleshootingDisastrous Accidents Mains FailureAppendix System Technical Parameters Parameter CategoryEMC Mtbf Appendix 2 Engineering Design Diagram Appendix 2 Engineering Design Diagram MCB Connector Connector specsAppendix 3.1 System Electric Schematic Diagram Appendix 3 System Circuit DiagramAppendix 3.2 System Wiring Diagram Appendix 3.3 MFU Electric Wiring Diagram Appendix 3.4 BCU Electric Wiring Diagram LVD Appendix GlossaryAbbreviation Full word Hvsd