Emerson 48330 user manual Chapter Operating SCU Serial Alarm Description Default

Page 55

 

 

 

 

Chapter 5

Operating SCU

45

 

 

 

 

 

 

 

 

 

Serial

Alarm

Description

Default

Default

Related parameter

 

 

related

 

 

No.

alarm level

configuration

 

 

 

 

relay

 

 

 

 

 

 

 

 

 

36

Batt4 Failure

Over-load, short circuit, manual

Critical

None

 

 

 

disconnection or alarm circuit faulty

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The charge current of battery group 1

 

 

 

 

 

37

Batt1 Over-curr

is bigger than the set value of

Observation

None

 

 

 

 

 

parameter “Over”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The charge current of battery group 2

 

 

 

 

 

38

Batt2 Over-curr

is bigger than the set value of

Observation

None

 

 

 

 

 

parameter “Over”

 

 

 

 

 

 

 

 

 

 

 

 

 

39

Rect Vac Err

All AC voltages are lower than the

Major

3

 

 

 

AC low-volt point

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

Rect Over Temp

Rectifier internal temperature higher

Observation

None

 

 

 

 

 

than 90°C

 

 

 

 

 

41

Rect Failure

Rectifier over-voltage, higher than

Critical

3

 

 

 

rectifier high threshold

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

42

Rect Protect

AC over-voltage (ƒ295V) or

Observation

3

 

 

 

under-voltage ( 80V)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

43

Rect Fan Fails

Fan faulty

Major

3

 

 

 

 

 

AC voltage lower than 176V, with

 

 

 

 

 

44

Rect PowerLimit

rectifier internal higher than 85°C or

Observation

3

 

 

 

 

 

temperature at inlet higher than 45°C

 

 

 

 

 

 

 

 

 

 

 

 

 

45

Rect Com Failure

Rectifier and monitoring module

Major

3

 

 

 

communication interrupted

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

46

Multi Rect Fail

More than 2 rectifiers raised alarms

Critical

None

 

 

 

47

Self-detect error

Error is detected through hardware

No alarm

None

 

 

 

self-detection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

48

Manual Mode

Battery management in the manual

No alarm

None

 

 

 

state

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

49

Non-FC Status

Including auto-BC, Cyclic Boost,

No alarm

7

 

 

 

constant current test and short test

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

Batt Discharge

Battery being discharging

No alarm

None

 

 

 

 

 

In a system with load shunt, the

 

 

 

 

 

51

Curr Imbalance

detected load current plus battery

No alarm

None

Not existent in this

 

 

 

 

current differs sharply from the

 

 

power system series

 

 

 

 

rectifier output current

 

 

 

 

 

 

 

 

 

 

 

 

 

52

Batt Test Error

Battery discharge time unexpectedly

Observation

None

 

 

 

 

 

short

 

 

 

 

 

 

 

During the short test, the two

 

 

 

 

 

53

Short Test Fault

batteries discharged more than the

Observation

None

 

 

 

 

 

set value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The maintenance FC voltage

 

 

 

 

 

54

Outvolt Fault

different from the busbar voltage, or

Observation

None

 

 

 

the reported data. The difference is

 

 

 

 

 

 

 

 

 

 

 

 

more than 1V

 

 

 

 

 

 

 

 

 

 

 

 

 

55

System Maintain

The pre-set system maintenance

Observation

None

 

 

 

time is due

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

56

Alarm Block

Alarms sent to the host are blocked,

No alarm

None

 

 

 

 

 

valid in EEM-M protocol

 

 

 

 

ACTURA Flex 48330 Power System User Manual

Image 55 Contents
31011084 Version V1.0 Revision date May 20Electrical Safety Safety PrecautionsBattery Others Special Safe Requirements of This EquipmentContents Routine Maintenance TestingTemperature Compensation Coefficient Parameters System Settings Alarm SettingsAppendix Daily Inspection Replacement15 Value description of AC settings Changing audible/visual alarm and alarm call back planFunctions of SCU keys Figure List Page Introduction FeaturesSystem Description AbbreviationOutline of the DC Power System is illustrated in Figure System ConfigurationConfiguration Cabinet dimension % 0.6 % 0.6 m % 0.6 % 0.4 m Configurations of Actura Flex 48330 Power SystemSCU BCU Rectifier Shelf ComponentsOutline Manufacture type Wmm ×Dmm ×Hmm Dimension of Rectifier Shelf are given in TableDimensions of rectifier shelf Connector boardRectifier Dimensions3 SCU Function of indicatorsDimension H % W % D132mm % 85mm % 287mm Weight 0.76kg Multi-Communication modeFunctions fulfilled by SCU and MC Alarm category settings for dry contact outputMulti-Function Unit MFU Password protection for important operationsAuthority and default password Level Authority Default passwordComponent Description Battery Connection Unit BCUConfiguration of MFU Alarm output0m % 0.6m % 0.4m cabinet BCU configurationSystem Cabinet 0m % 0.6m % 0.6m cabinetEnvironmental conditions in power room InstallationInstallation Preparation Power SupplyTools & Material Site SurveyUnpacking Drill reserve holes Installation ProceduresCabinet Installation Installation on the floorInstalling expansive pipe AC input modes External Electrical Connection InterfaceConnection Of Input Cables Connection requirementsDifferent cable connection modes Connection of input terminalsConnection of single-phase AC power input Connection Of Load Cables Configuration number of load MCBs and battery MCBsBusbar type Max. load number Connection Of Communication Cables 12 Connector board in rectifier shelf13 Layout of connector board S6415X2 Layout Of Connector Board S6415X2Interface definition of connector board S6415X2 Interface Definition Of Connector Board S6415X2Connector Pin Signal name Mark number Logic relation Connection With Modem Connection Of Temperature Sensor CablesConnector Pin Signal name Pgng POWER+ PowerConnection With Dry Contacts Battery Installation And CablingBattery Installation Connecting methodStandard configuration Battery Cable Connection16 Connection of battery cables 18 Negative battery cables connection in BCU Non-standard configurationDC/Parallel connections Parallel Connection Of CabinetsChecking Before Startup Check the DC Power System according to -1 before startupSystem checklist before startup StartupStartup Process Parameters ConfigurationTesting SCU TestingTesting MFU Testing RectifierBCU Test Battery Breaker TestLoad Breaker Test Functions of SCU keys Functions of LED indicatorsOperating SCU Operation PanelFirst system information page appears Operation ProceduresFirst Page Of System Information Querying System StatusOther System Information Screen Battery informationAC information BC prompt and temperature informationQuerying Rectifier Status Querying Active Alarm Querying Alarms And Setting Alarm PlansQuery Alarm History Alarm History Alarm type table Alarm Type TableBlvd LlvdChapter Operating SCU Serial Alarm Description Default Changing audible/visual alarm and alarm call back plan Changing Audible/Visual Alarm And Alarm Call Back PlanChanging Alarm Types Of Dry Contacts Setting Alarm Type For Dry ContactsAlarm type Remark Optional alarm typesSet the Alarm Names Through PLC Function Alarm Remark Description Logic matrix used for configuring 8 dry contactsExample of PLC setting PLC SN and AlarmPLC Alarm Remark DescriptionLlvd Blvd MaintenanceOperating SCU Parameter Setting Method Setting System ParametersPress ESC to return to the menu of higher level Level Authority Password levels and authoritiesFirst page of the Batt. Selection is shown below Batt. SelectionLVD Parameter Description There are 6 related pages, as shown below Charging Management ParametersOperating SCU BC/FC switchover diagram is shown below Parameter Range Default Value description12 Charging management parameter value description There are 7 related pages, as shown below Battery Test ParametersSchematic diagram of the test function is shown below 13 Value description of the battery test parametersValue description of the parameters is listed below First page of the setting interface is shown below Temperature Compensation Coefficient ParametersConfiguration interface is shown below AC SettingsThere are three related pages, as shown below DC Setting17 Value description of rectifier settings Rect SettingsSystem Settings There will be a prompt when resetting the system EEM-M 18 Value description of system settings48V/50A/SET/NONE 48V/30A/SET/NONE Model description is shown below19 Relationship between system model and system type Alarm SettingsPower system model System type First page of the setting interface is show below20 Value description of alarm settings Maintenance Of MFU Routine MaintenanceMaintenance Of Rectifier Maintenance Of SCUStorage And Supplementary Battery MaintenanceStore the battery in a cool dry place Cover PlatesReplacement Symptom Cause Suggestion TroubleshootingTroubleshooting Rectifier TroubleshootingDisastrous Accidents Mains FailureParameter Category Appendix System Technical ParametersEMC Mtbf Appendix 2 Engineering Design Diagram Appendix 2 Engineering Design Diagram MCB Connector Connector specsAppendix 3.1 System Electric Schematic Diagram Appendix 3 System Circuit DiagramAppendix 3.2 System Wiring Diagram Appendix 3.3 MFU Electric Wiring Diagram Appendix 3.4 BCU Electric Wiring Diagram LVD Appendix GlossaryAbbreviation Full word Hvsd