44 | Chapter 5 Operating SCU |
Serial | Alarm | Description | Default | Default | |
related | |||||
No. | alarm level | ||||
|
| relay | |||
|
|
|
| ||
|
| Battery temperature is lower than the |
|
| |
14 | Batt Temp Low | set value of parameter “Temp | Observation | None | |
|
| Threshold: Low Temp” |
|
| |
|
|
|
|
| |
15 | Amb Temp High | Ambient temperature is higher than | Observation | None | |
the set alarm point | |||||
|
|
|
| ||
|
|
|
|
| |
16 | Amb Temp Low | Ambient temperature is lower than | Observation | None | |
the alarm point | |||||
|
|
|
| ||
|
|
|
|
| |
17 | No TempSensor1 | Temperature sensor 1 has been set, | Critical | None | |
|
| but no sensor is actually connected |
|
| |
18 | No TempSensor2 | Temperature sensor 2 has been set, | Critical | None | |
|
| but no sensor is actually connected |
|
| |
19 | TempSensor1 | Temperature sensor 1 detected | Critical | None | |
Err | unreasonable temperature | ||||
|
|
| |||
|
|
|
|
| |
20 | TempSensor2 Err | Temperature sensor 2 detected | Critical | None | |
unreasonable temperature | |||||
|
|
|
| ||
|
|
|
|
| |
21 | LLVD | 1. Load disconnection | Critical | 5 | |
2. Manual load disconnection | |||||
|
|
|
| ||
|
|
|
|
| |
|
| 1. When battery discharges till its |
|
| |
|
| voltage is lower than the “BLVD |
|
| |
22 | BLVD | Volt”, or the discharge time is longer | Critical | 4 | |
|
| than the “BLVD Time”, the BLVD |
|
| |
|
| contactor will be open automatically |
|
| |
|
| 2. BLVD through manual operation |
|
| |
|
|
|
|
| |
23 | Load 1 Faiure | Critical | 6 | ||
disconnection or alarm circuit faulty | |||||
|
|
|
| ||
|
|
|
|
| |
24 | Load 2 Faiure | Critical | 6 | ||
disconnection or alarm circuit faulty | |||||
|
|
|
| ||
|
|
|
|
| |
25 | Load 3 Faiure | Critical | 6 | ||
disconnection or alarm circuit faulty | |||||
|
|
|
| ||
|
|
|
|
| |
26 | Load 4 Faiure | Critical | 6 | ||
disconnection or alarm circuit faulty | |||||
|
|
|
| ||
|
|
|
|
| |
27 | Load 5 Faiure | Critical | 6 | ||
disconnection or alarm circuit faulty | |||||
|
|
|
| ||
|
|
|
|
| |
28 | Load 6 Faiure | Critical | 6 | ||
disconnection or alarm circuit faulty | |||||
|
|
|
| ||
|
|
|
|
| |
29 | Load 7 Faiure | Critical | 6 | ||
disconnection or alarm circuit faulty | |||||
|
|
|
| ||
|
|
|
|
| |
30 | Load 8 Faiure | Critical | 6 | ||
disconnection or alarm circuit faulty | |||||
|
|
|
| ||
|
|
|
|
| |
31 | Load 9 Faiure | Critical | 6 | ||
disconnection or alarm circuit faulty | |||||
|
|
|
| ||
|
|
|
|
| |
32 | Aux Load Fails | The last route faulty | Critical | 6 | |
33 | Batt1 Failure | Critical | None | ||
disconnection or alarm circuit faulty | |||||
|
|
|
| ||
|
|
|
|
| |
34 | Batt2 Failure | Critical | None | ||
disconnection or alarm circuit faulty | |||||
|
|
|
| ||
|
|
|
|
| |
35 | Batt3 Failure | Critical | None | ||
disconnection or alarm circuit faulty | |||||
|
|
|
| ||
|
|
|
|
|
Related parameter
configuration
Low temperature alarm point
LLVD enabled
BLVD enabled
ACTURA Flex 48330 Power System User Manual