52 | Chapter 5 Operating SCU |
To input the password, use “ ” or “ ” to modify numbers, and use “ ” or “ ” to move the cursor. After the input, press “ENT” to confirm.
If the password is incorrect, system will prompt “password incorrect”. If the password is less than 6 digits, end it with a “#”.
Note
You can choose to enter the “Maintenance” menu by using either the user, operator or administrator password, for in this menu, all users have the same authority.
4.Press “ ” or “ ” to scroll to the operation page you need. There are two pages:
Maintenance
Start : BC
Batt: Reconnect
Load: Disconnect
RectTrim: 53.5V
CurrLimit: 110%
Rect 1: DC On
ID 01234567
5. Press " " and " " to select the needed action.
“Start”: The options include “FC”, “BC” and “Test”. If system is not configured with any battery, the control would be invalid. If there is AC power off alarm, or the busbar voltage is too low, the BC and battery test control will not be executed by the system. No battery test control can be conducted when the rectifier communication is interrupted. Finally, after the battery test, the battery management mode will be changed from “Manual” to “Auto” automatically.
“Battery”: The options include “Reconnect” and “Disconnect”. If there is no battery, or there is a battery alarm, the battery operations will be invalid.
“Load”: The options include “Reconnect” and “Disconnect”.
The following maintenance over the rectifier can be conducted only when the power system is in the FC state.
”RectTrim”: Range: 42V ~ 58V. It can be used to improve the current sharing among rectifiers. Note that the value of this parameter cannot exceed the
”RectLimit”: Range: 10% ~ 121%.
ACTURA Flex 48330 Power System User Manual