Emerson 225-600KVA installation manual Safety, Layout

Page 10

Battery Installation

2.0BATTERY INSTALLATION

2.1Safety

Special care should be taken when working with the batteries associated with the Liebert NX Battery System equipment. When all the cells are connected together, the battery terminal voltage will exceed 400V and is potentially lethal. A primary safety consideration is to install the battery equipment in an isolated area, accessible only to properly trained and qualified maintenance personnel.

! WARNING

Risk of electric shock. Can cause equipment damage, personal injury and death.

Hazardous battery voltage present behind covers. No user-serviceable parts are located behind covers that require a tool for removal. Only properly trained and qualified service personnel are authorized to remove such covers or perform installation or maintenance.

The following general battery safety precautions and warnings must be observed at all times:

A battery can present risk of electric shock or burn from high short circuit currents.

When connected in a string, the voltage will exceed 400VDC. This voltage is potentially lethal. Always observe high-voltage precautions.

Eye protection must be worn to prevent injury from accidental electrical arcs.

Remove rings, watches, necklaces, bracelets and all other metal objects.

Use only tools with insulated handles.

Wear appropriate personal protective equipment when handling batteries.

If a battery leaks electrolyte or is otherwise physically damaged, it should be placed in a container resistant to wire and disposed of in accordance with local regulations.

If electrolyte comes into contact with the skin, the affected area should be washed immediately with plenty of clean water.

Batteries must always be disposed of according to local environmental laws.

When replacing batteries, use the same number and type that were originally fitted.

Disconnect charging source prior to connecting or disconnecting battery terminals.

Determine if the battery is grounded. If it is grounded, remove source of ground. Contact with any part of a grounded battery can result in electrical shock.

Battery support tray must be used whenever a battery tray is being pulled out.

2.2Layout

Depending on the site layout, the battery cabinets can be installed in any of several ways:

Connected—Multiple battery cabinets bolted together

Stand-Alone—Cabinet not bolted to Liebert NX equipment

Attached—Battery cabinets are bolted to a Liebert NX UPS

Detached—Battery cabinets are not bolted to a Liebert NX UPS

See Figures 2 through 4.

Liebert® NX

6

Image 10
Contents Liebert NX Battery System Product Warranty Registration Table of Contents Figures Important Safety Instructions Liebert NX Preliminary Checks IntroductionEnvironmental Considerations Shipping bolts-Top-Terminal Battery Cabinet PositioningSystem Composition ClearancesSafety LayoutJunction Battery Attached Liebert Additional Junction BatteryAdditional Liebert Attached Additional Liebert Battery Cabinet Stand Alone Junction Power ConnectionCable Entry Control Connection GroundingExternal Battery Room Temperature Sensor-Optional Alber Monitoring System-OptionalBottom View Main components, Liebert Top-Terminal Battery Cabinet Do not DOUBLE-STACK Lugs Front Top View Front Ground BUS Detail Front View Terminal Details Outline DrawingLiebert NX Battery Cabinet control wiring Attached battery cabinet connections Typical Alber battery monitoring connections Battery Alber battery monitoring assembly diagram Alber battery monitoring assembly connectionsTop-Terminal battery configuration Cable Interconnect Diagram Left-Side Busbar Connections Right-Side Busbar Connections Specifications Liebert NX Battery Cabinet specificationsAlber battery monitoring option specifications Liebert NX Junction Cabinet specificationsDC currents for Liebert NX modules Liebert NX Battery Cabinet internal breaker Liebert NX Battery Cabinet approximate weightsBattery torque values UPS Rating KVA # Conduit Size, Ph, GTorque specifications, unless otherwise labeled Specifications Liebert NX Specifications Liebert NX Page Twor k Ne tIs t Care