| Specifications |
| Table 3 | Liebert NX Junction Cabinet specifications |
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| Value |
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| Battery Specifications | Attached |
|
| Attached | ||
|
| Nominal Battery Bus, VDC |
|
| 480V |
| |
|
| Battery Float Voltage, VDC |
|
| 540V |
| |
|
| Minimum EOD Voltage, VDC | 384V (for VRLA / Flooded Lead Acid) | ||||
|
| Battery Discharging Max current (EOD), A |
|
| Table 5 |
| |
| Physical Parameters |
|
|
|
|
| |
|
| Width, * in (mm) | 15.5 (393) |
| 30.9 (785) |
| 17.5 (445) |
|
| Depth, in (mm) ** | 33.5 (850) |
| 33.5 (850) |
| 33.5 (850) |
|
| Height, in (mm) | 76.8 (1950) |
| 76.8 (1950) |
| 76.8 (1950) |
|
| Weight, lb (kg) approx. | 255 (115) |
| 400 (180) |
| 255 (115) |
|
| Color |
|
| Black |
| |
|
| Degree of Protection for UPS Enclosure |
|
| IP 20 |
| |
|
| Minimum clearance, Top |
|
| 24" (610mm) |
| |
|
| Minimum clearance, Back |
| 0" |
|
| |
|
| Minimum clearance, Sides |
| 0" |
|
| |
|
| Location of cable entrance |
|
| Top or Bottom |
| |
|
|
|
|
| UL 1778 |
| |
| Standards and Conformities |
|
| CSA 22.2 107.3 |
| ||
|
|
| FCC Part 15, Class A |
| |||
|
|
|
|
| ISTA Procedure 1H |
| |
|
|
|
|
| WEEE |
| |
| Environmental |
|
|
|
|
| |
|
| Storage Temperature Range, °F (°C) | |||||
|
| Operating Temperature Range, °F (°C) |
| 32°F to 104°F (0 to 40°C) |
| ||
|
| Relative Humidity | Maximum 95% | ||||
|
| (Operating and | |||||
|
|
| |||||
|
|
| 4920 (1500) (as per IEC 62040/3) - | ||||
|
| Maximum Altitude above MSL, ft (m) | 1% maximum kW derate / 328ft rise between | ||||
|
|
| (100m rise between |
*Width dimensions are with side panels attached. Subtract 1.4" (35mm) for dimensions without side panels.
**Depth dimensions include the front door and rear panel.
Table 4 Alber battery monitoring option specifications
Electrical Data | Value |
|
|
Input Voltage | |
|
|
Input Current | < 0.5A |
|
|
Frequency | 60Hz |
|
|
Table 5 | DC currents for Liebert NX modules | ||
|
|
|
|
UPS Rating | Max Battery |
| |
|
|
| |
kVA | kW | Current at EOD |
|
|
|
|
|
225 | 225 | 586 |
|
|
|
|
|
250 | 250 | 653 |
|
|
|
|
|
300 | 300 | 786 |
|
|
|
|
|
400 | 400 | 1048 |
|
|
|
|
|
500 | 500 | 1310 |
|
|
|
|
|
600 | 600 | 1572 |
|
|
|
|
|
29 | Liebert® NX™ |