Emerson 225-600KVA Liebert NX Junction Cabinet specifications, DC currents for Liebert NX modules

Page 33

 

 

 

 

 

 

 

Specifications

 

Table 3

Liebert NX Junction Cabinet specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Value

 

 

 

 

 

 

 

 

 

 

 

 

Top-Terminal

 

 

 

 

 

Battery Specifications

Attached

 

Stand-Alone

 

Attached

 

 

Nominal Battery Bus, VDC

 

 

480V

 

 

 

Battery Float Voltage, VDC

 

 

540V

 

 

 

Minimum EOD Voltage, VDC

384V (for VRLA / Flooded Lead Acid)

 

 

Battery Discharging Max current (EOD), A

 

 

Table 5

 

 

Physical Parameters

 

 

 

 

 

 

 

Width, * in (mm)

15.5 (393)

 

30.9 (785)

 

17.5 (445)

 

 

Depth, in (mm) **

33.5 (850)

 

33.5 (850)

 

33.5 (850)

 

 

Height, in (mm)

76.8 (1950)

 

76.8 (1950)

 

76.8 (1950)

 

 

Weight, lb (kg) approx.

255 (115)

 

400 (180)

 

255 (115)

 

 

Color

 

 

Black (ZP-7021)

 

 

 

Degree of Protection for UPS Enclosure

 

 

IP 20

 

 

 

Minimum clearance, Top

 

 

24" (610mm)

 

 

 

Minimum clearance, Back

 

0"

 

 

 

 

Minimum clearance, Sides

 

0"

 

 

 

 

Location of cable entrance

 

 

Top or Bottom

 

 

 

 

 

 

UL 1778

 

 

Standards and Conformities

 

 

CSA 22.2 107.3

 

 

 

 

FCC Part 15, Class A

 

 

 

 

 

 

ISTA Procedure 1H

 

 

 

 

 

 

WEEE

 

 

Environmental

 

 

 

 

 

 

 

Storage Temperature Range, °F (°C)

-13°F to 158°F (-25°C to 70°C)

 

 

Operating Temperature Range, °F (°C)

 

32°F to 104°F (0 to 40°C)

 

 

 

Relative Humidity

Maximum 95% Non-Condensing

 

 

(Operating and Non-Operating)

 

 

 

 

 

 

4920 (1500) (as per IEC 62040/3) -

 

 

Maximum Altitude above MSL, ft (m)

1% maximum kW derate / 328ft rise between 4900-9800ft

 

 

 

(100m rise between 1500-3000m)

*Width dimensions are with side panels attached. Subtract 1.4" (35mm) for dimensions without side panels.

**Depth dimensions include the front door and rear panel.

Table 4 Alber battery monitoring option specifications

Electrical Data

Value

 

 

Input Voltage

220-600VAC

 

 

Input Current

< 0.5A

 

 

Frequency

60Hz

 

 

Table 5

DC currents for Liebert NX modules

 

 

 

 

UPS Rating

Max Battery

 

 

 

 

kVA

kW

Current at EOD

 

 

 

 

 

225

225

586

 

 

 

 

 

250

250

653

 

 

 

 

 

300

300

786

 

 

 

 

 

400

400

1048

 

 

 

 

 

500

500

1310

 

 

 

 

 

600

600

1572

 

 

 

 

 

29

Liebert® NX

Image 33
Contents Liebert NX Battery System Product Warranty Registration Table of Contents Figures Important Safety Instructions Liebert NX Introduction Preliminary ChecksEnvironmental Considerations Positioning Shipping bolts-Top-Terminal Battery CabinetClearances System CompositionLayout SafetyAttached Liebert Additional Junction Battery Junction BatteryAdditional Liebert Attached Power Connection Additional Liebert Battery Cabinet Stand Alone JunctionCable Entry Grounding Control ConnectionAlber Monitoring System-Optional External Battery Room Temperature Sensor-OptionalBottom View Main components, Liebert Top-Terminal Battery Cabinet Do not DOUBLE-STACK Lugs Front Top View Front Ground BUS Detail Front View Outline Drawing Terminal DetailsLiebert NX Battery Cabinet control wiring Attached battery cabinet connections Typical Alber battery monitoring connections Battery Alber battery monitoring assembly connections Alber battery monitoring assembly diagramTop-Terminal battery configuration Cable Interconnect Diagram Left-Side Busbar Connections Right-Side Busbar Connections Liebert NX Battery Cabinet specifications SpecificationsLiebert NX Junction Cabinet specifications Alber battery monitoring option specificationsDC currents for Liebert NX modules Liebert NX Battery Cabinet approximate weights Liebert NX Battery Cabinet internal breakerUPS Rating KVA # Conduit Size, Ph, G Battery torque valuesTorque specifications, unless otherwise labeled Specifications Liebert NX Specifications Liebert NX Page Is t Ne tTwor k Care