Battery Installation
Figure 4 Stand-alone battery cabinets, detached from UPS
The junction cabinet provides sufficient conduit landing space and is required for all systems in this configuration.
Liebert
NX
UPS
Additional
Liebert
NX
Battery
Cabinet
Stand-
Alone
Junction
Cabinet
Liebert
NX
Battery
Cabinet
Liebert
NX
Battery
Cabinet
Stand-
Alone
Junction
Cabinet
Additional
Liebert
NX
Battery
Cabinet
Liebert
NX
UPS
2.3Cable Entry
Cables may enter the battery cabinet from the top or bottom. Cable entry is made possible by installing conduit to the removable plate fitted at the top or bottom. See 3.0 - Installation Drawings.
2.4Power Connection
Depending on the site layout, the battery cabinets can be cabled several ways. See Figures 2 through 4.
! CAUTION
Cables between batteries and the UPS should be run in matched pairs,
Grouping
2.4.1Connected System
For cabinets ordered as connected (battery cabinets will bolt to each other), the positive and negative busbars are connected between battery cabinets with the supplied busbar connector extensions. See
Figure 17
2.4.2Stand-Alone System
For cabinets that are ordered as
2.4.3Attached/Detached System
For battery cabinets that are connecting to a Liebert NX UPS, or Liebert NX Junction Cabinet (see Figures 2 through 3), cables will run from the positive and negative busbars of the adjacent battery cabinet to the positive and negative DC connections of UPS or Junction Cabinet.
Liebert® NX™ | 8 |